Weidmuller, Canada10 Spy Court Markham, Ontario L3R 5H6Telephone: (800) 268-4080Facsimile: (877) 300-5635Email: [email protected]: www.weidmuller.ca
Weidmuller, MexicoBlvd. Hermanos Serdán 698, Col. San Rafael Oriente Puebla, Puebla, Mexico C.P. 72029 Telephone: 01 222 2686267Facsimile: 01 222 2686219Email: [email protected]: www.weidmuller.com.mx
Weidmuller, United States821 Southlake Blvd. Richmond, Virginia 23236Telephone: (800) 849-9343Facsimile: (804) 379-2593Email: [email protected]: www.weidmuller.com
DatasheetACT20M Signal Isolation and Conversion
NEW
High quality signal isolation and conversion in a slim 6mm wide housing format is now available with Weidmuller’s ACT20M range. Features include worldwide approvals for both standard and hazardous area installations. This series of single- and dual-channel models extends Weidmuller’s signal conditioning portfolio with a package of solutions for industrial process measurement and control applications.
ACT20M is designed to reduce the time and cost of building control panels. DIN-rail mounted in
Weidmuller’s new 8-pole housing, module power can be distributed through the rail for minimized power wiring and reduced installation costs. This “Power Rail” provides the flexibility to add or remove individual modules quickly and easily without affecting the wiring or operation of other components on the rail.
The ACT20M range offers D.C. and temperature isolators and converters for use in industrial and marine applications. Configuration is simple because the ACT20M modules require no calibration. Models with selectable temperature, voltage and current ranges feature DIP switches. For the Universal input model, Weidmuller provides vendor- independent, FDT-based configuration software available for download from the Weidmuller website.
Features:• Veryhighdensityanalogsignalisolation
and conversion• EasyinstallationwithPowerRailcross-connectoption• DIPswitchesforcalibration-freere-ranging• UniversalinputmodelusesFDTconfigurationsoftware
(and CBX200 interface)• CE,cULus,cFMusClass1Div.2andClass1Zone2ATEX,IECExZone2,DNV,GLapprovals
• Ambienttemperaturerangetypically-13˚Fto158˚F (-25˚Cto70˚C)
2
ACT20M Signal Isolation and Conversion
Universal input converter• Isolatingandconvertingof
temperature signals and DC signals• ConfigurationusingFDT/DTM
software• OptionalpowersupplyviatheDIN-rail-
bus• 3wayisolation
ACT20M-UI-AO-S
4
3
2
1
5
6
7
882 83
I, U
OUT
Supply
I, U, R
IN
Supply
Technical dataInput Sensor
Potentiometer/ResistanceInput currentInput voltageInput resistance, voltageInput resistance, current inputSensor supplyOutputOutput currentOutput voltageLoad resistance, currentLoad resistance, voltageGeneral dataSupply voltagePower consumption
Ambient temperature (operational)Storage temperatureAccuracy
Temperature coefficientInsulation coordinationInsulation voltageRated voltagePollution degreeOvervoltage categoryApprovals
Dimensions Length x width x height mmClampingrange(nominal/min./max.) mm2
Note
Ordering data
Note
Accessories
MarkerUSB interface
Note
Thermocouples: B, E, J, K, L, LR, N, R, S, T, U, W3, W5RTD: PT100, PT1000, Ni120, Ni100, Ni1000 2/3/4wire10Ω…10kΩ0(4)...20 mA0(2)...10 V, 0(1)...5 V>10MΩ<150Ω> 15 V DC at 20 mA
0(4)…20mA0(2)…10V<600Ω>10kΩ
24 V DC ± 30 %0.4W(24Vsupply/Passiveinput/20mAinput&output/100Ωload)-25°C…+70°C-40°C…+85°C< 0.1 % span (DC, RTD)<0.2%+CJerror(TC)<0.01%/K
2.5 kV300 V2II
cULus61010-1,cFMusDiv.2,ATEXzone2,IECExZone2,DNV,GL
114.3 x 6.1 x 112.52.5/0.5/2.5
Type Qty. Part No.ACT20M-UI-AO-S 1 1176030000
Type Qty. Part No.MF5/7.5MCNEUTRAL 1877680000CBX200 USB 8978580000DIN-rail bus, refer to accessories page
1
2
3
4
8
7
6
5
U, I, ϧ
U, I
Power
PLCmA
passive
+
–Out 1
Power24 V
+
–
4-wiremA
active
+
–In
1
2
3
4
8
7
6
5
U, I, ϧ
U, I
Power
PLCmA
passive
+
–Out 1
Power24 V
+
–
2-wiremA
passive
+
–In
ACT20M-UI-AO-S
1
2
3
4
8
7
6
5
U, I, ϧ
U, I
Power
PLCmA
passive
+
–Out 1
Power24 V
+
–
4-wireV
active
+
–In
1
2
3
4
8
7
6
5
U, I, ϧ
U, I
Power
PLCmA
passive
+
–Out 1
Power24 V
+
–
TC +
–In
ACT20M-UI-AO-S
1
2
3
4
8
7
6
5
U, I, ϧ
U, I
Power
PLCmA
passive
+
–Out 1
Power24 V
+
–
RTD
Sense +
R +
R –
Sense –
ACT20M-UI-AO-S
3
ACT20M Signal Isolation and Conversion
Signal splitter• Isolating,convertingandsplitting
DC signals• ConfiguredusingDIPswitch• Optionalpowersupplyviathe
DIN-rail bus• 4wayisolation
ACT20M-CI-2CO-S ACT20M-AI-2AO-S
4
3
2
1
5
6
7
882 83
I OUT 1
Supply
I IN
I OUT 2
Supply
4
3
2
1
5
6
7
882 83
I, U
OUT 1
Supply
I, U
IN
I, U
OUT 2
Supply
Technical dataInput Input currentInput voltage
Input resistance, current inputLoad resistance, voltageSensor supplyOutputOutput currentOutput voltage
Load resistance, currentLoad resistance, voltageGeneral dataSupply voltagePower consumption
Ambient temperature (operational)Storage temperatureAccuracyTemperature coefficientCut-off-frequencyInsulation coordinationInsulation voltageRated voltagePollution degreeOvervoltage categoryApprovals
Dimensions Length x width x height mmClampingrange(nominal/min./max.) mm2
Note
Ordering data
Note
Accessories
Marker
Note
0(4)…20mA–
<75Ω––
0(4)…20mA–
<300Ω/channel≥10kΩ
24 V DC ± 30 %
0.4W(24Vsupply/Passiveinput/20mAinput&output/100Ωload)
-25°C…+70°C-40°C…+85°C< 0.05 % of measurement range<0.01%/K100 Hz
2.5 kV300 V2II
cULus61010-1,cFMusDiv.2,ATEXzone2,IECExZone2,DNV,GL
114.3 x 6.1 x 112.52.5/0.5/2.5
Type Qty. Part No.ACT20M-CI-2CO-S 1 1175990000
Type Qty. Part No.MF5/7.5MCNEUTRAL 1877680000
DIN-rail bus, refer to accessories page
0(4)…20mA0(2)…10V0(1)…5V<75Ω>500kΩ> 17 V DC at 20 mA
0(4)…20mA0(2)…10V0(1)…5V<300Ω/channel>10kΩ/channel
24 V DC ± 30 %
0.4W(24Vsupply/Passiveinput/20mAinput&output/100Ωload)
-25°C…+70°C-40°C…+85°C< 0.05 % of measurement range<0.01%/K100 Hz
2.5 kV300 V2II
cULus61010-1,cFMusDiv.2,ATEXzone2,IECExZone2,DNV,GL
114.3 x 6.1 x 112.52.5/0.5/2.5
Type Qty. Part No.ACT20M-AI-2AO-S 1 1176020000
Type Qty. Part No.MF5/7.5MCNEUTRAL 1877680000
DIN-rail bus, refer to accessories page
4
Converters for DC mA and Volts• IsolatingandconvertingDCsignals• DIPswitchforrangechanges
without re-calibration• Optionalpowersupplyviathe
DIN-rail-bus• 3wayisolation• ChoiceofactiveorpassivemAinput
(“E“ model is not hazardous location approved)
ACT20M-AI-AO-S ACT20M-AI-AO-E-S
ACT20M Signal Isolation and Conversion
4
3
2
1
5
6
7
882 83
I, U
OUT
Supply
I, U
IN
Supply
4
3
2
1
5
6
7
882 83
I, U
OUT
Supply
I, U
IN
Supply
Technical dataInput Input currentInput voltageInput resistance, current inputInput resistance, voltageSensor supplyOutputOutput currentOutput voltageLoad resistance, currentLoad resistance, voltageGeneral dataSupply voltagePower consumption
Ambient temperature (operational)Storage temperatureAccuracyTemperature coefficientCut-off-frequencyInsulation coordinationInsulation voltageRated voltagePollution degreeOvervoltage categoryApprovals
Dimensions Length x width x height mmClampingrange(nominal/min./max.) mm2
Ordering data
Accessories
Marker
Note
0(4)…20mA0(2)…10V;0(1)…5V<75Ω>500kΩ> 17 V DC at 20 mA
0(4)…20mA0(2)…10V;0(1)…5V<600Ω>10kΩ
24 V DC ± 30 %0.4W(24Vsupply/Passiveinput/20mAinput&output/100Ωload)-25°C…+70°C-40°C…+85°C< 0.05 % of measurement range<0.01%/K100 Hz
2.5 kV300 V2II
cULus61010-1,cFMusDiv.2,ATEXzone2,IECExZone2,DNV,GL
114.3 x 6.1 x 112.52.5/0.5/2.5
Type Qty. Part No.ACT20M-AI-AO-S 1 1176000000
Type Qty. Part No.MF5/7.5MCNEUTRAL 1877680000DIN-rail bus, refer to accessories page
0(4)…20mA0(2)…10V;0(1)…5V<75Ω>500kΩ–
0(4)…20mA0(2)…10V;0(1)…5V<600Ω>10kΩ
24 V DC ± 30 %0.4W(24Vsupply/Passiveinput/20mAinput&output/100Ωload)0°C…+70°C-40°C…+85°C< 0.2 % of measurement range<0.015%/K100 Hz
2.5 kV300 V2II
cULus61010-1,DNV,GL
114.3 x 6.1 x 112.52.5/0.5/2.5
Type Qty. Part No.ACT20M-AI-AO-E-S 1 1176010000
Type Qty. Part No.MF5/7.5MCNEUTRAL 1877680000DIN-rail bus, refer to accessories page
1
2
3
4
8
7
6
5
U, I
U, I
Power
PLCV, mA
passive
+
–Out 1
Power24 V
+
–
2-wiremA
passive
+
–In
1
2
3
4
8
7
6
5
U, I
U, I
Power
PLCV, mA
passive
+
–Out 1
Power24 V
+
–
4-wireV, mAactive
+
–In
ACT20M-AI-AO-S
Input
1 2 3 40 … 20 mA4 … 20 m0 … 10 V2 … 10 V0 … 5 V1 …5 V0 ... 20 mA loop4 ... 20 mA loop
Switch
Output 1
5 6 70 … 20 mA4 … 20 m0 … 10 V2 … 10 V0 … 5 V1 …5 V
Switch
◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼
◼ ◼ ◼◼ ◼ ◼◼ ◼ ◼◼ ◼ ◼◼ ◼ ◼◼ ◼ ◼
◼◼
= on= off
1
2
3
4
8
7
6
5
U, I
U, I
Power
PLCV, mA
passive
+
–Out 1
Power24 V
+
–
4-wireV, mAactive
+
–In
ACT20M-AI-AO-E-S
◼◼
= on= off
Input
1 2 3 40 … 20 mA4 … 20 m0 … 10 V2 … 10 V0 … 5 V1 …5 V0 ... 20 mA loop4 ... 20 mA loop
Switch
Output 1
5 6 70 … 20 mA4 … 20 m0 … 10 V2 … 10 V0 … 5 V1 …5 V
Switch
◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼
◼ ◼ ◼◼ ◼ ◼◼ ◼ ◼◼ ◼ ◼◼ ◼ ◼◼ ◼ ◼
5
ILP and OLP isolators• IsolationofDCmAsignals• Takespowerfromtheinputloop(ILP)
or output loop (OLP)• Availableaseithersingle-channelor
double-channel version• 2wayisolation
ACT20M-CI-CO-ILP-S ACT20M-CI-CO-OLP-S
ACT20M Signal Isolation and Conversion
4
3
2
1
5
6
7
8
I IN 1
I IN 2
I OUT 1
I OUT 2
4
3
2
1
5
6
7
8
I IN 1
I IN 2
I OUT 1
I OUT 2
Technical dataInput Input currentInput resistance, current inputOutputOutput currentLoad resistance, currentGeneral dataPower consumptionAmbient temperature (operational)Storage temperatureAccuracyTemperature coefficientCut-off-frequencyInsulation coordinationInsulation voltageRated voltagePollution degreeOvervoltage categoryApprovals
Dimensions Length x width x height mmClampingrange(nominal/min./max.) mm2
Ordering data
Single-channel versionDouble-channel version
Accessories
Marker
0(4)…20mA<65Ω at 25 °C
0(4)…20mA<600Ω
30 mW per channel - from input loop-25°C…+70°C-40°C…+85°C< 0.1 % of measurement range<0.01%/K100 Hz
2.5 kV300 V2II
cULus61010-1,cFMusDiv.2,ATEXzone2,IECExZone2,DNV,GL
114.3 x 6.1 x 112.52.5/0.5/2.5
Type Qty. Part No.ACT20M CI-CO-ILP-S 1 1176070000ACT20M 2CI-2CO-ILP-S 1 1176080000
Type Qty. Part No.MF5/7.5MCNEUTRAL 1877680000
0(4)…20mAtyp.<125Ω
4 - 20 mA<600Ω
55 mW per channel - from output loop-25°C…+70°C-40°C…+85°C< 0.1 % of measurement range<0.01%/K100 Hz
2.5 kV300 V2II
cULus61010-1,cFMusDiv.2,ATEXzone2,IECExZone2,DNV,GL
114.3 x 6.1 x 112.52.5/0.5/2.5
Type Qty. Part No.ACT20M- CI-CO-OLP-S 1 1176040000ACT20M-2CI-2CO-OLP-S 1 1176050000
Type Qty. Part No.MF5/7.5MCNEUTRAL 1877680000
1
2
3
4
8
7
6
5
I
I
PLCmA
passive
+
–Out
4-wiremA
active
+
–In
1
2
3
4
8
7
6
5 PLCmA
passive
+
–Out 1
Out 2PLCmA
passive
+
–
4-wiremA
active
+
–In 1
4-wiremA
active
+
–In 2
II
II
ACT20M-CI-CO-ILP-S
ACT20M-2CI-2CO-ILP-S
1
2
3
4
8
7
6
5
I
I
PLCmA
active
+
–Out
2-wiremA
passive
+
–In
1
2
3
4
8
7
6
5 PLCmA
active
+
–Out 1
Out 2PLCmA
active
+
–
2-wiremA
passive
+
–In 1
2-wiremA
passive
+
–In 2
II
II
ACT20M-CI-CO-OLP-S
ACT20M-2CI-2CO-OLP-S
6
DC isolator• IsolatingDCsignals• Optionalpowersupplyviathe
DIN-rail-bus• 3wayisolation
ACT20M-CI-CO-S
ACT20M Signal Isolation and Conversion
4
3
2
1
5
6
7
882 83
I OUT
Supply
I IN
Supply
Technical dataInput Input currentLoad resistance, current inputOutputOutput currentLoad resistance, currentGeneral dataSupply voltagePower consumption
Ambient temperature (operational)Storage temperatureAccuracyTemperature coefficientCut-off-frequencyInsulation coordinationInsulation voltageRated voltagePollution degreeOvervoltage categoryApprovals
Dimensions Length x width x height mmClampingrange(nominal/min./max.) mm2
Note
Ordering data
Note
Accessories
MarkerNote
0(4)…20mA<75Ω
0(4)…20mA<600Ω
24 V DC ± 30 %0.4W(24Vsupply/Passiveinput/20mAinput&output/100Ωload)-25°C…+70°C-40°C…+85°C< 0.05 % of measurement range<0.01%span/K100 Hz
2.5 kV300 V2II
cULus61010-1,cFMusDiv.2,ATEXzone2,IECExZone2,DNV,GL
114.3 x 6.1 x 112.5 mm2.5/0.5/2.5mm²
Type Qty. Part No.ACT20M-CI-CO-S 1 1175980000
Type Qty. Part No.MF5/7.5MCNEUTRAL 1877680000DIN-rail bus, refer to accessories page
1
2
3
4
8
7
6
5
I
I
Power
PLCmA
passive
+
–Out 1
Power24 V
+
–
4-wiremA
active
+
–In
ACT20M-CI-CO-S
7
Temperature transmitter• Choiceofisolatingornon-isolating
converters for J or K thermocouples and RTDs.
• Hundredsofmin/maxrangecombinations
• ConfigurationviaDIPswitches• Powersuppliedfromtheoutputloop• 2-wayisolation(OLP-Smodelonly)• Outputislinearwithtemperature
ACT20M-RTCI-CO-OLP-S ACT20M-RTI-CO-EOLP-S
ACT20M Signal Isolation and Conversion
Technical dataInputSensor
Input measurement range
Temperature input rangeOutputOutput currentLoad ResistanceWire break detectionGeneral dataConfigurationSupply voltagePower consumptionAccuracy
Temperaturecoefficient
GalvanicisolationStep response timeAmbient temperature (operational)Insulation coordinationInsulation voltageRated voltagePollution severitySurge voltage categoryApprovals
DimensionsClampingrange(nominal/min./max.) mm²Depth x width x height mmNote
Ordering data
Note
4
3
2
1
5
6PLC
I
PT 100
8 V DC...35 V DC
TC
Optional external CJC
+
+
–
PT100/2-/3-/4-wire,Thermocoupleacc.toIEC584,type: J, Thermocouple acc. to IEC 584, type: KPT100-200…+850°C,ThermocoupletypeJ-100…+1200°C,ThermocoupletypeK-200…+1370°C(internal or external CJC)Selectable by DIP Switch
4...20mA,20…4mA<600Ω3.5mA⁄23mA⁄noneSelectablebyDIPSwitch
DIP switch8...35 V DC Loop poweredca. 1 Wabsolute accuracy: < ±0.05 % of the measurement range, RTD (PT100) Basic accuracy: < ±0.1 °C of the measurement range, TC (J,K) Basic accuracy: < ±0.5 °C of the measurement rangeRTD(PT100)≤0.01%ofthemeasurementrange ⁄ °Cor0.02°C ⁄ °C‘,TC(J,K)0.1°C ⁄ °C2-way isolator≤30ms/≤300msSelectablebyDIPSwitch-25...+70°C
2.5 kVeff300 Veff
2II
cULus;FMEX;IECEXKEM;KEMAATEX; DETNORVER;GL
2.5/0.5/2.5114.3/6.1/112.5
Type Qty. Part No.ACT20M-RTCI-CO-OLP-S 1 1435590000
4
3
2
1
5
6PLC
I
PT 100
8 V DC...35 V DC
PT100/2-/3-/4-wire
PT100-200…+850°C
Selectable by DIP Switch
4...20mA,20…4mA<600Ω3.5mA⁄23mA⁄noneSelectablebyDIPSwitch
DIP switch8...35 V DC Loop poweredca. 1 Wabsolute accuracy: < ±0.1 % of the measurement range, Basic accuracy: < ±0.2 °C of the measurement range
RTD(PT100)≤0.01%ofthemeasurementrange ⁄ °Cor0.02°C ⁄ °CWithout isolation≤30ms/≤300msSelectablebyDIPSwitch-25...+70°C
N/A
2II
cULus;FMEX;IECEXKEM;KEMAATEX; DETNORVER;GL
2.5/0.5/2.5114.3/6.1/112.5
Type Qty. Part No.ACT20M-RTI-CO-EOLP-S 1 1435610000
8
Temperature transmitter• Choiceofisolatingornon-isolating
converters for RTDs.• Hundredsofmin/maxrange
combinations• OptionalPowerRailaccessory
simplifies jumpering and saves wiring time.
• ConfigurationviaDIPswitches• 3-wayisolation(AO-Smodelonly)
ACT20M-RTI-AO-S ACT20M-RTI-AO-E-S
ACT20M Signal Isolation and Conversion
Technical dataInputSensorInput measurement rangeTemperature input rangeOutputOutput currentOutput voltageload impedance currentload impedance voltageWire break detectionGeneral dataConfigurationSupply voltagePower consumptionAccuracy
GalvanicisolationTemperaturecoefficientStep response timeAmbient temperature (operational)Insulation coordinationInsulation voltage
Rated voltagePollution severitySurge voltage categoryApprovals
4
3
2
1
5
6
7
882 83
Supply
PLC
I, V
Supply
PT 100
PT100/2-/3-/4-wirePT100-200…+850°CSelectable by DIP Switch
0...20 mA, 4...20 mA Selectable by DIP Switch0(1)...5 V, 0(2)...10 V Selectable by DIP Switch≤600Ω≥10kΩ3.5mA⁄23mA⁄noneSelectablebyDIPSwitch
DIP switch24 V DC ± 30 %1 Wabsolute accuracy: < ±0.05 % of the measurement range, Basic accuracy: < ±0.1 % of the measurement range3-way isolator≤0.01%ofthemeasurementrange°Cor0.02°C⁄°C≤30ms/≤300msSelectablebyDIPSwitch-25...+70°C
2.5 kVeff
300 Veff
2II
cULus;FMEX;IECEXKEM;KEMAATEX; DETNORVER;GL
4
3
2
1
5
6
7
8
I, VOUT 1
Supply
PT 100
PT100/2-/3-/4-wirePT100-200…+850°CSelectable by DIP Switch
0...20 mA, 4...20 mA Selectable by DIP Switch0(1)...5 V, 0(2)...10 V Selectable by DIP Switch≤600Ω≥10kΩ3.5mA⁄23mA⁄noneSelectablebyDIPSwitch
DIP switch24 V DC ± 30 %1 Wabsolute accuracy: < ±0.1 % of the measurement range
Without isolation≤0.01%ofthemeasurementrange°Cor0.02°C⁄°C≤30ms/≤300msSelectablebyDIPSwitch-25...+70°C
N/AN/A2II
cULus;FMEX;IECEXKEM;KEMAATEX; DETNORVER;GL
DimensionsClampingrange(nominal/min./max.) mm²Depth x width x height mm
Note
2.5/0.5/2.5114.3/6.1/112.5
2.5/0.5/2.5114.3/6.1/112.5
Ordering data
Note
Type Qty. Part No.ACT20M-RTI-AO-S 1 1375510000
Type Qty. Part No.ACT20M-RTI-AO-E-S 1 1375520000
9
ACT20M Signal Isolation and Conversion
Temperature transmitter•Choiceofisolatingornon-isolating
converters for J or K thermocouples• Hundredsofmin/maxrange
combinations• OptionalPowerRailaccessory
simplifies jumpering and saves wiring time.
• ConfigurationviaDIPswitches• 3-wayisolation(AO-Smodelonly)
ACT20M-TCI-AO-S ACT20M-TCI-AO-E-S
Technical data
4
3
2
1
5
6
7
882 83
Supply
PLC
I, V
Supply
TC
Optional external CJC
+
+
–
4
3
2
1
5
6
7
8
I, VOUT
Supply
TC
Optional external CJC
+
+
–
InputSensorInput measurement range
Temperature input rangeOutputOutput currentOutput voltageload impedance currentload impedance voltageWire break detectionGeneral dataConfigurationSupply voltagePower consumptionAccuracy
GalvanicisolationTemperaturecoefficientStep response timeAmbient temperature (operational)Insulation coordinationInsulation voltageRated voltagePollution severitySurge voltage categoryApprovals
DimensionsClampingrange(nominal/min./max.) mm²Depth x width x height mm
Note
Thermocouple (Type J, K)ThermocoupletypeJ-100…+1200°C,ThermocoupletypeK-200…+1370°C(internalorexternalCJC)Selectable by DIP Switch
0...20 mA, 4...20 mA Selectable by DIP Switch0(1)...5 V, 0(2)...10 V Selectable by DIP Switch≤600Ω≥10kΩ3.5mA⁄23mA⁄noneSelectablebyDIPSwitch
DIP switch24 V DC ± 30 %ca. 1 Wabsolute accuracy: < ±0.05 % of the measurement range, TC (J,K) Basic accuracy: < ±0.5 °C of the measurement range3-way isolator<0.1%/°C≤30ms/≤300msSelectablebyDIPSwitch-25...+70°C
2.5 kVeff300 Veff2II
cULus;FMEX;IECEXKEM;KEMAATEX; DETNORVER;GL
2.5/0.5/2.5114.3/6.1/112.5
Thermocouple (Type J, K)ThermocoupletypeJ-100…+1200°C,ThermocoupletypeK-200…+1370°C(internalorexternalCJC)Selectable by DIP Switch
0...20 mA, 4...20 mA Selectable by DIP Switch0(1)...5 V, 0(2)...10 V Selectable by DIP Switch≤600Ω≥10kΩ3.5mA⁄23mA⁄noneSelectablebyDIPSwitch
DIP switch24 V DC ± 30 %ca. 1 Wabsolute accuracy: < ±0.1 % of the measurement range, Basic accuracy: < ±1 °C
Without isolation≤0.01%/°C≤30ms/≤300msSelectablebyDIPSwitch-25...+70°C
N/AN/A2II
cULus;FMEX;IECEXKEM;KEMAATEX; DETNORVER;GL
2.5/0.5/2.5114.3/6.1/112.5
Ordering data
Note
Type Qty. Part No.ACT20M-TCI-AO-S 1 1375480000
Type Qty. Part No.ACT20M-TCI-AO-E-S 1 1375500000
10
Bipolar converters• Forusewithcenter-zerosensors,
e.g. actuator position control, or bi-directional flow monitoring.
• DIPswitchessimplifyconfiguration• Conversionchoices:bipolarin/unipolar
out,orbipolarin/2xunipolarout.• OptionalPowerRailaccessorysimplifies
jumpering and saves wiring time.
ACT20M-BAI-AO-S ACT20M-BAI-2AO-S
ACT20M Signal Isolation and Conversion
4
3
5
6
7
882 83Supply
I, VOUT 1
± I, ± V IN
Supply
2
1
4
3
5
6
7
882 83Supply
I, VOUT 1
OUT 2
I, V
± I, ± V IN
Supply
Technical dataInput Input current
Input voltage
Input resistance, voltageInput resistance, current inputsOutputCut-off frequency (-3 dB)load impedance voltageNumber of outputsload impedance currentOutput voltage, noteOutput currentGeneral dataAccuracyConfigurationGalvanicisolationMounting railPower consumptionPower consumption, max.Step response timeSupply voltageTemperature coefficientType of connectionInsulation coordinationEMC standardsGalvanicisolationInsulation voltagePollution severityRated voltageStandardsSurge voltage categoryApprovalsApprovalsROHSDimensions Depth x width x height (mm)Note
Ordering data
Note
-10mA…0…+10mA,-20mA…0…+20mA-5V…0…+5V,-10V…0…+10V Selectable by DIP Switch≥1MΩ50Ωat20mA
≥100Hz,10HzSelectable by DIP Switch≥10kΩ1≤600Ω0(2)...10 V, 0(1)...5 V Selectable by DIP Switch0...20 mA, 4...20 mA Selectable by DIP Switch
< 0.05 % of measuring rangeDIP switch3-wayisolator;TS 35Typ. 400 mW0.8 W≤7ms,≤100ms,Selectable by DIP Switch24 V DC ± 30 %<0.01%ofspan/°C(TU)Screw connection
EN 61326-13-wayisolator;2.5 kVeff
2300 Veff
DIN EN 61010-1, DIN EN 60079II
cULus, DNV, FM, IECEx, Ex Conform
114.3 x 6.1 x 112.5
Type Qty. Part No.ACT20M-BAI-AO-S 1 1375450000
-10mA…0…+10mA,-20mA…0…+20mA-5V…0…+5V,-10V…0…+10V Selectable by DIP Switch≥1MΩ50Ωat20mA
≥100Hz,10HzSelectable by DIP Switch≥10kΩ22x300Ω0(2)...10 V, 0(1)...5 V Selectable by DIP Switch0...20 mA, 4...20 mA Selectable by DIP Switch
< 0.05 % of measuring rangeDIP switch4-wayisolator;TS 35Typ. 400 mW0.8 W≤7ms,≤100ms,Selectable by DIP Switch24 V DC ± 30 %<0.01%ofspan/°C(TU)Screw connection
EN 61326-14-wayisolator;2.5 kVeff
2300 Veff
DIN EN 61010-1, DIN EN 60079II
cULus, DNV, FM, IECEx, Ex Conform
114.3 x 6.1 x 112.5
Type Qty. Part No.ACT20M-BAI-2AO-S 1 1375470000
11
Rail bus accessories
ACT20M Signal Isolation and Conversion
CH20M BUS-PROFIL TS35x7.5/1000Support section for bus PCB
CH20M BUS-PROFIL TS35x15/1000Support section for bus PCB
CH20M BUS 4.50/05 AU/1000Bus PCB
•BusPCBforuseonTS35x7.5andTS35x15•Length:250,500or750mm•Fiveconductorpaths,goldplated•Electricalrating:63VAC,5A/conductorpath
Ordering dataType Qty. Part No.CH20MBUS4.50/ 05AU/250
10 1248220000
CH20MBUS4.50/ 05AU/500
10 1248230000
CH20MBUS4.50/ 05AU/750
5 1248240000
•SupportsectionforTS35x7.5•Length:250,500or750mm
Ordering dataType Qty. Part No.CH20M BUS-PROFIL TS35x7.5/250
10 1248150000
CH20M BUS-PROFIL TS35x7.5/500
10 1248160000
CH20M BUS-PROFIL TS35x7.5/750
5 1248170000
•SupportsectionforTS35x15•Length:250,500or750mm
Ordering dataType Qty. Part No.CH20M BUS-PROFIL TS35x15/250
5 1248180000
CH20M BUS-PROFIL TS35x15/500
5 1248190000
CH20M BUS-PROFIL TS35x15/750
5 1248210000
CH20M BUS-ADP TS35/1000Cover plate
CH20M BUS-AP LI TS35x7.5 & 15End plate
CH20M BUS-AP RE TS35x7.5 & 15End plate
•Endplateforrailbus•FitsonTS35x7.5andTS35x15•Right
Ordering dataType Qty. Part No.CH20M BUS-AP RE TS35x7.5&15
50 1193170000
•Coverplateforrailbus•Length:250,500or750mm
Ordering dataType Qty. Part No.
CH20MBUS-ADPTS35/250 10 1248250000
CH20MBUS-ADPTS35/500 10 1248260000
CH20MBUS-ADPTS35/750 5 1248270000
•Endplateforrailbus•FitsonTS35x7.5andTS35x15•Left
Ordering dataType Qty. Part No.CH20M BUS-AP LI TS35x7.5 &15
50 1193160000
SET CH20M BUS 250MM TS 35X15Set
• SETconsistsofoneeachof
CH20MBUS4.50/05AU/250
CH20MBUS-ADPTS35/250
CH20MBUS-APLITS35X7.5&15
CH20MBUS-APRETS35X7.5&15
CH20MBUS-PROFILTS35X15/250
Ordering dataType Qty. Part No.SET CH20M BUS 250MM TS 35X15
1 1335150000
SET CH20M BUS 250MM TS 35X7.5Set
• SETconsistsofoneeachof
CH20MBUS4.50/05AU/250
CH20MBUS-ADPTS35/250
CH20MBUS-APLITS35X7.5&15
CH20MBUS-APRETS35X7.5&15
CH20MBUS-PROFILTS35X7.5/250
Ordering dataType Qty. Part No.SET CH20M BUS 250MM TS 35X7.5
1 1335140000
12
ACT20M Signal Isolation and Conversion
Output-current loop-powered•Galvanicisolation•Verylowpowerconsumption•InputrangeselectedviaDIPswitch•Nocalibrationnecessary
OLP
U/I
I
Technical dataInputInput voltageInputresistance,voltage/currentInput currentRated current OutputOutput currentOutput signal limitLoadimpedance,voltage/currentCut-off frequency (-3 dB)General dataConfigurationSupply voltageAmbient temperature Default settingAccuracyTemperaturecoefficientStep response timeApprovalsInsulation coordinationStandardsEMC standardsRated voltageImpulse withstand voltageInsulation voltage
Surge voltage categoryPollution severityClearance&creepagedistances
DimensionsClampingrange(nominal/min./max.) mm²Length x width x height mmNote
Ordering data
Screw connectionNote
0...5V: 210 kΩ;0...10V:430kΩ/51Ω0(4)...20 mA40 mA
4...20 mA (current loop)Approx. 31 mA/RL = (UB-12V)/20mAz.B.600Ω at 24 V10Hz/100Hzswitchable
DIP switchmin.12VDC/max.30VDC0°C...+55°C0...20mA, 10 Hz0.2%ofmeasuringrangefinalvalue≤150ppm/K<10Hz:80ms;100Hz:50msCE;cULus
DIN EN 50178, DIN EN 61000-4-2EN 55011, EN 61000-6300 V4 kV4 kVeff/5s
III2≥ 5.5 mm
2.5/0.5/2.592.4/17.5/112.4
Type Qty. Part No.WAS5 OLP 1 8543720000
Setting options/switch position
Example of application
SW 1 1 2 3 4Input
0 … 20 mA n n n n
4 … 20 mA ◼
◼n n n
0 … 5 V n
0 … 10 V n ◼
◼ ◼
n n
Transmission frequency10 Hz n n n ◼
100 Hz n n n n
◼ = onn = off
7
8
9
1
2
3
SPSRL
4 ... 20mA0...10V
24 V DC
230 V AC
~230 V AC
24V DC
~
Sensor
WAVE ANALOGUEOLP
8543720000/8543730000
UL Class I, Div. 2
13
Thermal converter type: K,J,T,E,N,R,S,B•3-wayisolation•Internalcold-junctioncompensation•Powersupplycanbecross-connected
using plug-in jumpers•Suitableforinsulatedanduninsulated
thermocouples•WAVETOOLsoftwarehelpswith
configuration, download at www.weidmuller.com
ACT20M Signal Isolation and Conversion
PRO Thermo
J U/I
VC
Technical dataInputSensorTemperature input rangeOutputOutputvoltage/OutputcurrentLoadimpedance,voltage/currentOffsetcurrent/OffsetvoltageLine resistance in measuring circuitWire break detectionFine adjustmentStatus indicator
General dataConfigurationSupply voltagePower consumptionStep response timeCurrent-carrying capacity of cross-connect.Ambient temperature Storage temperatureDefault setting
ApprovalsInsulation coordinationStandardsEMC standardsRated voltageImpulse withstand voltageInsulation voltageSurge voltage categoryPollution severityClearance&creepagedistances
DimensionsClampingrange(nominal/min./max.) mm²Length x width x height mmNote
Ordering data
Screw connectionNote
Thermo element (IEC 584) type: K,J,T,E,N,R,S,B-200...+1820°C
0...10V/0(4)...20mA≥ 1 kΩ/≤ 600 Ωmax.100µA/max.0.05V50 ΩLEDflashing(outputvalue:>20mA,>10V)± 5% (switchable)Moduleactive:LEDon/wirebreakage:LEDflashing/ Error: LED off
DIP switch24 V DC ± 25 %800...850...950 mW at IOUT = 20 mAwithoutfilter:max.1.4s;withfilter:max.7.5s≤ 2 A0°C...+55°C-20°C...+85°CTypeK;0...1000°C;4...20mA;filter:off;man. calibration: offCE;cULusEX;GL
DIN EN 50178, DIN EN 61000-4-2EN 55011, EN 61000-63004 kV2 kVeff/5s
III2≥ 3 mm
2.5/0.5/2.592.4/17.5/112.4
Type Qty. Part No.WAS5 PRO Thermo 1 8560720000
Select ofthermocoupler
SW1TypKJTENRSB
1 2 3◼ ◼ ◼◼ ◼ ◼◼ ◼ ◼◼ ◼ ◼◼ ◼ ◼◼ ◼ ◼◼ ◼ ◼◼ ◼ ◼
Selection of minimumtemperature
SW1 1 2 3 4◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼
0 °C– 10 °C– 20 °C– 30 °C– 40 °C– 50 °C– 100 °C– 150 °C– 200 °C+ 50 °C+ 100 °C+ 150 °C+ 200 °C+ 250 °C+ 500 °CSpecial range
minϑ
Selection of outputSwitch 2
Output0 ... 10 V0 ... 20 V4 ... 20 V
6 7◼ ◼ ◼ ◼◼ ◼
Switching on themanual fine adjustment
SW 2man. adjust.offon
6◼◼
Switching on thefilter function
SW 2Filteroffon
8◼◼
AccuracyK -200 °C … -150 °C ± (5K + 0.1 % of set range) -150 °C … 1200 °C ± (3K + 0.1 % of set range) 1200 °C … 1372 °C ± (4K + 0.1 % of set range)J -200 °C … -150 °C ± (4K + 0.1 % of set range) -150 °C … 1200 °C ± (3K + 0.1 % of set range)T -200 °C … -150 °C ± (5K + 0.1 % of set range) -150 °C … 400 °C ± (3K + 0.1 % of set range)E -200 °C … -150 °C ± (4K + 0.1 % of set range) -150 °C … 1000 °C ± (3K + 0.1 % of set range)N -200 °C … -150 °C ± (6K + 0.1 % of set range) -150 °C … 1300 °C ± (3K + 0.1 % of set range)R -50 °C … 200 °C ± (10K + 0.1 % of set range) 200 °C … 1760 °C ± (6K + 0.1 % of set range)S -50 °C … 200 °C ± (10K + 0.1 % of set range) 200 °C … 1760 °C ± (6K + 0.1 % of set range)B 50 °C … 250 °C ± (25K + 0.1 % of set range) 250 °C … 500 °C ± (10K + 0.1 % of set range) 500 °C … 1820 °C ± (6K + 0.1 % of set range)
Selection oftemperature span
SW2
100 °C150 °C200 °C250 °C300 °C350 °C400 °C450 °C500 °C550 °C600 °C650 °C700 °C750 °C800 °C850 °C900 °C950 °C
1000 °C1050 °C1100 °C1150 °C1200 °C1250 °C1300 °C1350 °C1400 °C1450 °C1500 °C1600 °C1700 °C1800 °C
Span 1 2 3 4 5◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼
◼◼
= on= off
UL Class I, Div. 2
14
RTD signal isolator/converter•UniversallyadjustableviaDIPswitch•3-wayisolation•Linearisation•Powersupplycanbecross-connected
using plug-in jumpers•WAVETOOLsoftwarehelpswith
configuration,download at www.weidmuller.com
PRO RTD
ACT20M Signal Isolation and Conversion
RTDJ,R U/I
VC
Technical dataInputSensor
Temperature input rangeOutputOutputcurrent/OutputvoltageOffsetcurrent/OffsetvoltageLoadimpedance,voltage/currentWire break detectionFine adjustment
Status indicator
General dataConfigurationSupply voltagePower consumptionStep response time
Ambient temperature ApprovalsInsulation coordinationStandardsEMC standardsRated voltageImpulse withstand voltageInsulation voltage
Surge voltage categoryPollution severityClearance&creepagedistancesDimensionsClampingrange(nominal/min./max.) mm²Length x width x height mmNote
Screw connectionNote
PT100/2-/3-/4-wire,Ni100/2-/3-/4-wire,potentio-meter: min. 0–100 Ω, max. 0–100 kΩ, Resistance: 0–450 Ωconfigurable
0(4)...20mA/0...10Vmax.100µA/max.0.05V≥ 1 kΩ/≤ 600 ΩLEDflashing(outputvalue:>20mA,>10V)≥ ± 5 %, Version 1 and later: ≥12.5%/ potentiometer: 12.5%...25%Moduleactive:LEDon/wirebreakage:LEDflashing/ Error: LED off
DIP switch, Potentiometer24 V DC ± 25 %830...880...980mW at IOUT = 20 mAfast/slow:2-/3-/4-conductor:1.2s/2.2s; potentiometer:0.5s/1.1s0°C...+55°CCE;cULus;GL
DIN EN 50178, DIN EN 61000-4-2EN 55011, EN 61000-6300 V4 kV2 kVeff/5sIII2≥ 3 mm
2.5/0.5/2.592.4/17.5/112.4
Type Qty. Part No.WAS5 PRO RTD 1 8560700000
Ordering data
UL Class I, Div. 2
15
PRO RTD
ACT20M Signal Isolation and Conversion
Switch position / setting options
Choice of inputs ■ = on Switch 1 □ = off
Input 1 2 3PT100 2-wire ■ ■ ■PT100 3-wire □ ■ ■PT100 4-wire ■ □ ■R 2-wire □ □ ■NI100 2-wire ■ ■ □NI100 3-wire □ ■ □NI100 4-wire ■ □ □Potentiometer □ □ □
Choice of minimum input sizeSwitch 1
ϑmin Rmin Potimin 4 5 6 70 °C 0Ω 0 % ■ ■ ■ ■
-10 °C 10Ω 10 % ■ ■ ■ □-20 °C 20Ω 20 % ■ ■ □ ■-25 °C 20Ω 25 % ■ ■ □ □-30 °C 30Ω 30 % ■ □ ■ ■-40 °C 40Ω 40 % ■ □ ■ □-50 °C 50Ω 50 % ■ □ □ ■-60 °C 60Ω 60 % ■ □ □ □-70 °C 70Ω 70 % □ ■ ■ ■-80 °C 80Ω 80 % □ ■ ■ □-90 °C 90Ω □ ■ □ ■
-100 °C 100Ω □ ■ □ □-150 °C 150Ω □ □ ■ ■-200 °C 200Ω □ □ ■ □
Special area □ □ □ ■
Choice of measuring rangeSwitch 2
T R Poti 1 2 3 4 540 K 20Ω 20 % ■ ■ ■ ■ ■50 K 25Ω 25 % ■ ■ ■ ■ □60 K 30Ω 30 % ■ ■ ■ □ ■70 K 35Ω 35 % ■ ■ ■ □ □80 K 40Ω 40 % ■ ■ □ ■ ■90 K 45Ω 45 % ■ ■ □ ■ □
100 K 50Ω 50 % ■ ■ □ □ ■110 K 55Ω 55 % ■ ■ □ □ □120 K 60Ω 60 % ■ □ ■ ■ ■125 K 62,5Ω 62,5 % ■ □ ■ ■ □130 K 65Ω 65 % ■ □ ■ □ ■140 K 70Ω 70 % ■ □ ■ □ □150 K 75Ω 75 % ■ □ □ ■ ■160 K 80Ω 80 % ■ □ □ ■ □170 K 85Ω 85 % ■ □ □ □ ■180 K 90Ω 90 % ■ □ □ □ □190 K 95Ω 95 % □ ■ ■ ■ ■200 K 100Ω 100 % □ ■ ■ ■ □250 K 125Ω --- □ ■ ■ □ ■300 K 150Ω --- □ ■ ■ □ □350 K 175Ω --- □ ■ □ ■ ■400 K 200Ω --- □ ■ □ ■ □450 K 225Ω --- □ ■ □ □ ■500 K 250Ω --- □ ■ □ □ □550 K 275Ω --- □ □ ■ ■ ■600 K 300Ω --- □ □ ■ ■ □650 K 325Ω --- □ □ ■ □ ■700 K 350Ω --- □ □ ■ □ □750 K 375Ω --- □ □ □ ■ ■800 K 400Ω --- □ □ □ ■ □850 K 425Ω --- □ □ □ □ ■900 K 450Ω --- □ □ □ □ □
Choice of outputs Switch on the manual fine adjustmentsSwitch 2
Output 6 7 S. 10...10 V ■ □ Man. adjustment 80...5 V ■ ■ off □0...20 mA □ □ on ■4...20 mA □ ■
Choice of step response time
S. 2Step response time 8slow ■fast □
Accuracy, slow/fast step response timePT 100,Ni 100: 0,3 % from measuring range 0,8 %frommeasuringrange<100K/0,3K/0,8KPotentiometer:0.2%fromendvalue/0.3%Resistance:0.2%fromendvalue/0.3%
Temperature coefficientMeasuringrange≥200K ≤200ppm/°C100K≤Measuringrange<200K ≤250ppm/°C40K≤Measuringrange<100K ≤400ppm/°C
Adjustment example for zero and spanTemperature adjustment:Output 4…20mADIP switch -10°C…+110°CSpan 75…110°CRange 120 °CAdjustment range ± 12.5 %
Zero
–25° C–10° C
–5° C
Span
5° C
95° C110° C
125° C
110° C125° C
140° C
Wavetool adjustment tool This service tool enables quick and straightforwardconfigurationofthe WAVEANALOG PRO.Internet download:http://www.weidmuller.com
16
ACT20M Signal Isolation and Conversion
ACT20 power feed module• Distributesthevoltagesupplyonthe
busbar• CompatiblewithWeidmuller‘sCH20
rail bus• Optionalbackupsupplyconnection• ApprovedforinstallationinExZone2
/Div.2• Monitorsthesupplyvoltage• Alarmalertsviathestatusrelay
ACT20M-FEED-IN-PRO-S ACT20-FEED-IN-BASIC-S
Subject to technical changes • 03/14 • LIT1126
Technical dataInputPower supplyMax. input currentBackup power supplyTrigger level for the power supplyOutput, power supplyOutput voltage Output powerOutput currentOutput, status relay in safe zoneMax. voltageMax. currentMax. AC powerGeneral dataEfficiency degreeAmbient temperatureStorage temperaturePower consumptionProtection degreeWeightHumidityApprovalsDimensions Clampingrange(nominal/min./max.) mmLength x width x height mm2
Note
Ordering data
Note
51
52
53
54
Power supply, 0 V
Power supply, +24 V
Backup, 0 V
Backup, +24 V
NC
Status relay, N.C.
Status relay, shared
Status relay, N.O.
44
43
42
41
8182838485N
C
NC 0 V
+24
V
Sta
tus
Alarm
21.6...26.4 V DC4A21.6...26.4 V DCFault < 21 V DC
Input voltage -0.5 V DC @ 4 Amax. 96 Wmax. 4 A
250AC/30VDC2AAC/2ADC500VA/60W
> 97.9 %-20...+60°C-20...+85°C< 2 WIP20140 g< 95 %, no condensationcULus, cFMus, ATEX,IECExZone2,DNV,GOSTScrew connection2.5/0.5/2.5119.2/22.5/113.6
Type Qty. Part No.ACT20-Feed-In-PRO-S 1 8965500000
Power supply, +24 V
Power supply, 0 V
NC
NC
NC 0 V V 42
+
16.8...31.2 V DC2.5A
= U input= P input= I input
100 %-25...+70°C-40...+85°C< 2 WIP2070 g< 95 %, no condensationcULus, ATEX,IECExZone2,GL,DNV,cFMus,GOSTScrew connection2.5/0.5/2.5114.3/6.1/112.5
Type Qty. Part No.ACT20-FEED-IN-BASIC-S 1 12824900000
Top Related