Datasheet ACT20M Signal Isolation and Conversion Launches...models extends Weidmuller’s signal...

16
Weidmuller, Canada 10 Spy Court Markham, Ontario L3R 5H6 Telephone: (800) 268-4080 Facsimile: (877) 300-5635 Email: [email protected] Website: www.weidmuller.ca Weidmuller, Mexico Blvd. Hermanos Serdán 698, Col. San Rafael Oriente Puebla, Puebla, Mexico C.P. 72029 Telephone: 01 222 2686267 Facsimile: 01 222 2686219 Email: [email protected] Website: www.weidmuller.com.mx Weidmuller, United States 821 Southlake Blvd. Richmond, Virginia 23236 Telephone: (800) 849-9343 Facsimile: (804) 379-2593 Email: [email protected] Website: www.weidmuller.com Datasheet ACT20M Signal Isolation and Conversion NEW High quality signal isolation and conversion in a slim 6mm wide housing format is now available with Weidmuller’s ACT20M range. Features include worldwide approvals for both standard and hazardous area installations. This series of single- and dual-channel models extends Weidmuller’s signal conditioning portfolio with a package of solutions for industrial process measurement and control applications. ACT20M is designed to reduce the time and cost of building control panels. DIN-rail mounted in Weidmuller’s new 8-pole housing, module power can be distributed through the rail for minimized power wiring and reduced installation costs. This “Power Rail” provides the flexibility to add or remove individual modules quickly and easily without affecting the wiring or operation of other components on the rail. The ACT20M range offers D.C. and temperature isolators and converters for use in industrial and marine applications. Configuration is simple because the ACT20M modules require no calibration. Models with selectable temperature, voltage and current ranges feature DIP switches. For the Universal input model, Weidmuller provides vendor- independent, FDT-based configuration software available for download from the Weidmuller website. Features: • Very high density analog signal isolation and conversion • Easy installation with Power Rail cross-connect option • DIP switches for calibration-free re-ranging • Universal input model uses FDT configuration software (and CBX200 interface) • CE, cULus, cFMus Class 1 Div. 2 and Class 1 Zone 2 ATEX, IECEx Zone 2, DNV, GL approvals • Ambient temperature range typically -13˚F to 158˚F (-25˚C to 70˚C)

Transcript of Datasheet ACT20M Signal Isolation and Conversion Launches...models extends Weidmuller’s signal...

Page 1: Datasheet ACT20M Signal Isolation and Conversion Launches...models extends Weidmuller’s signal conditioning portfolio with a package of solutions for industrial process measurement

Weidmuller, Canada10 Spy Court Markham, Ontario L3R 5H6Telephone: (800) 268-4080Facsimile: (877) 300-5635Email: [email protected]: www.weidmuller.ca

Weidmuller, MexicoBlvd. Hermanos Serdán 698, Col. San Rafael Oriente Puebla, Puebla, Mexico C.P. 72029 Telephone: 01 222 2686267Facsimile: 01 222 2686219Email: [email protected]: www.weidmuller.com.mx

Weidmuller, United States821 Southlake Blvd. Richmond, Virginia 23236Telephone: (800) 849-9343Facsimile: (804) 379-2593Email: [email protected]: www.weidmuller.com

DatasheetACT20M Signal Isolation and Conversion

NEW

High quality signal isolation and conversion in a slim 6mm wide housing format is now available with Weidmuller’s ACT20M range. Features include worldwide approvals for both standard and hazardous area installations. This series of single- and dual-channel models extends Weidmuller’s signal conditioning portfolio with a package of solutions for industrial process measurement and control applications.

ACT20M is designed to reduce the time and cost of building control panels. DIN-rail mounted in

Weidmuller’s new 8-pole housing, module power can be distributed through the rail for minimized power wiring and reduced installation costs. This “Power Rail” provides the flexibility to add or remove individual modules quickly and easily without affecting the wiring or operation of other components on the rail.

The ACT20M range offers D.C. and temperature isolators and converters for use in industrial and marine applications. Configuration is simple because the ACT20M modules require no calibration. Models with selectable temperature, voltage and current ranges feature DIP switches. For the Universal input model, Weidmuller provides vendor- independent, FDT-based configuration software available for download from the Weidmuller website.

Features:• Veryhighdensityanalogsignalisolation

and conversion• EasyinstallationwithPowerRailcross-connectoption• DIPswitchesforcalibration-freere-ranging• UniversalinputmodelusesFDTconfigurationsoftware

(and CBX200 interface)• CE,cULus,cFMusClass1Div.2andClass1Zone2ATEX,IECExZone2,DNV,GLapprovals

• Ambienttemperaturerangetypically-13˚Fto158˚F (-25˚Cto70˚C)

Page 2: Datasheet ACT20M Signal Isolation and Conversion Launches...models extends Weidmuller’s signal conditioning portfolio with a package of solutions for industrial process measurement

2

ACT20M Signal Isolation and Conversion

Universal input converter• Isolatingandconvertingof

temperature signals and DC signals• ConfigurationusingFDT/DTM

software• OptionalpowersupplyviatheDIN-rail-

bus• 3wayisolation

ACT20M-UI-AO-S

4

3

2

1

5

6

7

882 83

I, U

OUT

Supply

I, U, R

IN

Supply

Technical dataInput Sensor

Potentiometer/ResistanceInput currentInput voltageInput resistance, voltageInput resistance, current inputSensor supplyOutputOutput currentOutput voltageLoad resistance, currentLoad resistance, voltageGeneral dataSupply voltagePower consumption

Ambient temperature (operational)Storage temperatureAccuracy

Temperature coefficientInsulation coordinationInsulation voltageRated voltagePollution degreeOvervoltage categoryApprovals

Dimensions Length x width x height mmClampingrange(nominal/min./max.) mm2

Note

Ordering data

Note

Accessories

MarkerUSB interface

Note

Thermocouples: B, E, J, K, L, LR, N, R, S, T, U, W3, W5RTD: PT100, PT1000, Ni120, Ni100, Ni1000 2/3/4wire10Ω…10kΩ0(4)...20 mA0(2)...10 V, 0(1)...5 V>10MΩ<150Ω> 15 V DC at 20 mA

0(4)…20mA0(2)…10V<600Ω>10kΩ

24 V DC ± 30 %0.4W(24Vsupply/Passiveinput/20mAinput&output/100Ωload)-25°C…+70°C-40°C…+85°C< 0.1 % span (DC, RTD)<0.2%+CJerror(TC)<0.01%/K

2.5 kV300 V2II

cULus61010-1,cFMusDiv.2,ATEXzone2,IECExZone2,DNV,GL

114.3 x 6.1 x 112.52.5/0.5/2.5

Type Qty. Part No.ACT20M-UI-AO-S 1 1176030000

Type Qty. Part No.MF5/7.5MCNEUTRAL 1877680000CBX200 USB 8978580000DIN-rail bus, refer to accessories page

1

2

3

4

8

7

6

5

U, I, ϧ

U, I

Power

PLCmA

passive

+

–Out 1

Power24 V

+

4-wiremA

active

+

–In

1

2

3

4

8

7

6

5

U, I, ϧ

U, I

Power

PLCmA

passive

+

–Out 1

Power24 V

+

2-wiremA

passive

+

–In

ACT20M-UI-AO-S

1

2

3

4

8

7

6

5

U, I, ϧ

U, I

Power

PLCmA

passive

+

–Out 1

Power24 V

+

4-wireV

active

+

–In

1

2

3

4

8

7

6

5

U, I, ϧ

U, I

Power

PLCmA

passive

+

–Out 1

Power24 V

+

TC +

–In

ACT20M-UI-AO-S

1

2

3

4

8

7

6

5

U, I, ϧ

U, I

Power

PLCmA

passive

+

–Out 1

Power24 V

+

RTD

Sense +

R +

R –

Sense –

ACT20M-UI-AO-S

Page 3: Datasheet ACT20M Signal Isolation and Conversion Launches...models extends Weidmuller’s signal conditioning portfolio with a package of solutions for industrial process measurement

3

ACT20M Signal Isolation and Conversion

Signal splitter• Isolating,convertingandsplitting

DC signals• ConfiguredusingDIPswitch• Optionalpowersupplyviathe

DIN-rail bus• 4wayisolation

ACT20M-CI-2CO-S ACT20M-AI-2AO-S

4

3

2

1

5

6

7

882 83

I OUT 1

Supply

I IN

I OUT 2

Supply

4

3

2

1

5

6

7

882 83

I, U

OUT 1

Supply

I, U

IN

I, U

OUT 2

Supply

Technical dataInput Input currentInput voltage

Input resistance, current inputLoad resistance, voltageSensor supplyOutputOutput currentOutput voltage

Load resistance, currentLoad resistance, voltageGeneral dataSupply voltagePower consumption

Ambient temperature (operational)Storage temperatureAccuracyTemperature coefficientCut-off-frequencyInsulation coordinationInsulation voltageRated voltagePollution degreeOvervoltage categoryApprovals

Dimensions Length x width x height mmClampingrange(nominal/min./max.) mm2

Note

Ordering data

Note

Accessories

Marker

Note

0(4)…20mA–

<75Ω––

0(4)…20mA–

<300Ω/channel≥10kΩ

24 V DC ± 30 %

0.4W(24Vsupply/Passiveinput/20mAinput&output/100Ωload)

-25°C…+70°C-40°C…+85°C< 0.05 % of measurement range<0.01%/K100 Hz

2.5 kV300 V2II

cULus61010-1,cFMusDiv.2,ATEXzone2,IECExZone2,DNV,GL

114.3 x 6.1 x 112.52.5/0.5/2.5

Type Qty. Part No.ACT20M-CI-2CO-S 1 1175990000

Type Qty. Part No.MF5/7.5MCNEUTRAL 1877680000

DIN-rail bus, refer to accessories page

0(4)…20mA0(2)…10V0(1)…5V<75Ω>500kΩ> 17 V DC at 20 mA

0(4)…20mA0(2)…10V0(1)…5V<300Ω/channel>10kΩ/channel

24 V DC ± 30 %

0.4W(24Vsupply/Passiveinput/20mAinput&output/100Ωload)

-25°C…+70°C-40°C…+85°C< 0.05 % of measurement range<0.01%/K100 Hz

2.5 kV300 V2II

cULus61010-1,cFMusDiv.2,ATEXzone2,IECExZone2,DNV,GL

114.3 x 6.1 x 112.52.5/0.5/2.5

Type Qty. Part No.ACT20M-AI-2AO-S 1 1176020000

Type Qty. Part No.MF5/7.5MCNEUTRAL 1877680000

DIN-rail bus, refer to accessories page

Page 4: Datasheet ACT20M Signal Isolation and Conversion Launches...models extends Weidmuller’s signal conditioning portfolio with a package of solutions for industrial process measurement

4

Converters for DC mA and Volts• IsolatingandconvertingDCsignals• DIPswitchforrangechanges

without re-calibration• Optionalpowersupplyviathe

DIN-rail-bus• 3wayisolation• ChoiceofactiveorpassivemAinput

(“E“ model is not hazardous location approved)

ACT20M-AI-AO-S ACT20M-AI-AO-E-S

ACT20M Signal Isolation and Conversion

4

3

2

1

5

6

7

882 83

I, U

OUT

Supply

I, U

IN

Supply

4

3

2

1

5

6

7

882 83

I, U

OUT

Supply

I, U

IN

Supply

Technical dataInput Input currentInput voltageInput resistance, current inputInput resistance, voltageSensor supplyOutputOutput currentOutput voltageLoad resistance, currentLoad resistance, voltageGeneral dataSupply voltagePower consumption

Ambient temperature (operational)Storage temperatureAccuracyTemperature coefficientCut-off-frequencyInsulation coordinationInsulation voltageRated voltagePollution degreeOvervoltage categoryApprovals

Dimensions Length x width x height mmClampingrange(nominal/min./max.) mm2

Ordering data

Accessories

Marker

Note

0(4)…20mA0(2)…10V;0(1)…5V<75Ω>500kΩ> 17 V DC at 20 mA

0(4)…20mA0(2)…10V;0(1)…5V<600Ω>10kΩ

24 V DC ± 30 %0.4W(24Vsupply/Passiveinput/20mAinput&output/100Ωload)-25°C…+70°C-40°C…+85°C< 0.05 % of measurement range<0.01%/K100 Hz

2.5 kV300 V2II

cULus61010-1,cFMusDiv.2,ATEXzone2,IECExZone2,DNV,GL

114.3 x 6.1 x 112.52.5/0.5/2.5

Type Qty. Part No.ACT20M-AI-AO-S 1 1176000000

Type Qty. Part No.MF5/7.5MCNEUTRAL 1877680000DIN-rail bus, refer to accessories page

0(4)…20mA0(2)…10V;0(1)…5V<75Ω>500kΩ–

0(4)…20mA0(2)…10V;0(1)…5V<600Ω>10kΩ

24 V DC ± 30 %0.4W(24Vsupply/Passiveinput/20mAinput&output/100Ωload)0°C…+70°C-40°C…+85°C< 0.2 % of measurement range<0.015%/K100 Hz

2.5 kV300 V2II

cULus61010-1,DNV,GL

114.3 x 6.1 x 112.52.5/0.5/2.5

Type Qty. Part No.ACT20M-AI-AO-E-S 1 1176010000

Type Qty. Part No.MF5/7.5MCNEUTRAL 1877680000DIN-rail bus, refer to accessories page

1

2

3

4

8

7

6

5

U, I

U, I

Power

PLCV, mA

passive

+

–Out 1

Power24 V

+

2-wiremA

passive

+

–In

1

2

3

4

8

7

6

5

U, I

U, I

Power

PLCV, mA

passive

+

–Out 1

Power24 V

+

4-wireV, mAactive

+

–In

ACT20M-AI-AO-S

Input

1 2 3 40 … 20 mA4 … 20 m0 … 10 V2 … 10 V0 … 5 V1 …5 V0 ... 20 mA loop4 ... 20 mA loop

Switch

Output 1

5 6 70 … 20 mA4 … 20 m0 … 10 V2 … 10 V0 … 5 V1 …5 V

Switch

◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼

◼ ◼ ◼◼ ◼ ◼◼ ◼ ◼◼ ◼ ◼◼ ◼ ◼◼ ◼ ◼

◼◼

= on= off

1

2

3

4

8

7

6

5

U, I

U, I

Power

PLCV, mA

passive

+

–Out 1

Power24 V

+

4-wireV, mAactive

+

–In

ACT20M-AI-AO-E-S

◼◼

= on= off

Input

1 2 3 40 … 20 mA4 … 20 m0 … 10 V2 … 10 V0 … 5 V1 …5 V0 ... 20 mA loop4 ... 20 mA loop

Switch

Output 1

5 6 70 … 20 mA4 … 20 m0 … 10 V2 … 10 V0 … 5 V1 …5 V

Switch

◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼

◼ ◼ ◼◼ ◼ ◼◼ ◼ ◼◼ ◼ ◼◼ ◼ ◼◼ ◼ ◼

Page 5: Datasheet ACT20M Signal Isolation and Conversion Launches...models extends Weidmuller’s signal conditioning portfolio with a package of solutions for industrial process measurement

5

ILP and OLP isolators• IsolationofDCmAsignals• Takespowerfromtheinputloop(ILP)

or output loop (OLP)• Availableaseithersingle-channelor

double-channel version• 2wayisolation

ACT20M-CI-CO-ILP-S ACT20M-CI-CO-OLP-S

ACT20M Signal Isolation and Conversion

4

3

2

1

5

6

7

8

I IN 1

I IN 2

I OUT 1

I OUT 2

4

3

2

1

5

6

7

8

I IN 1

I IN 2

I OUT 1

I OUT 2

Technical dataInput Input currentInput resistance, current inputOutputOutput currentLoad resistance, currentGeneral dataPower consumptionAmbient temperature (operational)Storage temperatureAccuracyTemperature coefficientCut-off-frequencyInsulation coordinationInsulation voltageRated voltagePollution degreeOvervoltage categoryApprovals

Dimensions Length x width x height mmClampingrange(nominal/min./max.) mm2

Ordering data

Single-channel versionDouble-channel version

Accessories

Marker

0(4)…20mA<65Ω at 25 °C

0(4)…20mA<600Ω

30 mW per channel - from input loop-25°C…+70°C-40°C…+85°C< 0.1 % of measurement range<0.01%/K100 Hz

2.5 kV300 V2II

cULus61010-1,cFMusDiv.2,ATEXzone2,IECExZone2,DNV,GL

114.3 x 6.1 x 112.52.5/0.5/2.5

Type Qty. Part No.ACT20M CI-CO-ILP-S 1 1176070000ACT20M 2CI-2CO-ILP-S 1 1176080000

Type Qty. Part No.MF5/7.5MCNEUTRAL 1877680000

0(4)…20mAtyp.<125Ω

4 - 20 mA<600Ω

55 mW per channel - from output loop-25°C…+70°C-40°C…+85°C< 0.1 % of measurement range<0.01%/K100 Hz

2.5 kV300 V2II

cULus61010-1,cFMusDiv.2,ATEXzone2,IECExZone2,DNV,GL

114.3 x 6.1 x 112.52.5/0.5/2.5

Type Qty. Part No.ACT20M- CI-CO-OLP-S 1 1176040000ACT20M-2CI-2CO-OLP-S 1 1176050000

Type Qty. Part No.MF5/7.5MCNEUTRAL 1877680000

1

2

3

4

8

7

6

5

I

I

PLCmA

passive

+

–Out

4-wiremA

active

+

–In

1

2

3

4

8

7

6

5 PLCmA

passive

+

–Out 1

Out 2PLCmA

passive

+

4-wiremA

active

+

–In 1

4-wiremA

active

+

–In 2

II

II

ACT20M-CI-CO-ILP-S

ACT20M-2CI-2CO-ILP-S

1

2

3

4

8

7

6

5

I

I

PLCmA

active

+

–Out

2-wiremA

passive

+

–In

1

2

3

4

8

7

6

5 PLCmA

active

+

–Out 1

Out 2PLCmA

active

+

2-wiremA

passive

+

–In 1

2-wiremA

passive

+

–In 2

II

II

ACT20M-CI-CO-OLP-S

ACT20M-2CI-2CO-OLP-S

Page 6: Datasheet ACT20M Signal Isolation and Conversion Launches...models extends Weidmuller’s signal conditioning portfolio with a package of solutions for industrial process measurement

6

DC isolator• IsolatingDCsignals• Optionalpowersupplyviathe

DIN-rail-bus• 3wayisolation

ACT20M-CI-CO-S

ACT20M Signal Isolation and Conversion

4

3

2

1

5

6

7

882 83

I OUT

Supply

I IN

Supply

Technical dataInput Input currentLoad resistance, current inputOutputOutput currentLoad resistance, currentGeneral dataSupply voltagePower consumption

Ambient temperature (operational)Storage temperatureAccuracyTemperature coefficientCut-off-frequencyInsulation coordinationInsulation voltageRated voltagePollution degreeOvervoltage categoryApprovals

Dimensions Length x width x height mmClampingrange(nominal/min./max.) mm2

Note

Ordering data

Note

Accessories

MarkerNote

0(4)…20mA<75Ω

0(4)…20mA<600Ω

24 V DC ± 30 %0.4W(24Vsupply/Passiveinput/20mAinput&output/100Ωload)-25°C…+70°C-40°C…+85°C< 0.05 % of measurement range<0.01%span/K100 Hz

2.5 kV300 V2II

cULus61010-1,cFMusDiv.2,ATEXzone2,IECExZone2,DNV,GL

114.3 x 6.1 x 112.5 mm2.5/0.5/2.5mm²

Type Qty. Part No.ACT20M-CI-CO-S 1 1175980000

Type Qty. Part No.MF5/7.5MCNEUTRAL 1877680000DIN-rail bus, refer to accessories page

1

2

3

4

8

7

6

5

I

I

Power

PLCmA

passive

+

–Out 1

Power24 V

+

4-wiremA

active

+

–In

ACT20M-CI-CO-S

Page 7: Datasheet ACT20M Signal Isolation and Conversion Launches...models extends Weidmuller’s signal conditioning portfolio with a package of solutions for industrial process measurement

7

Temperature transmitter• Choiceofisolatingornon-isolating

converters for J or K thermocouples and RTDs.

• Hundredsofmin/maxrangecombinations

• ConfigurationviaDIPswitches• Powersuppliedfromtheoutputloop• 2-wayisolation(OLP-Smodelonly)• Outputislinearwithtemperature

ACT20M-RTCI-CO-OLP-S ACT20M-RTI-CO-EOLP-S

ACT20M Signal Isolation and Conversion

Technical dataInputSensor

Input measurement range

Temperature input rangeOutputOutput currentLoad ResistanceWire break detectionGeneral dataConfigurationSupply voltagePower consumptionAccuracy

Temperaturecoefficient

GalvanicisolationStep response timeAmbient temperature (operational)Insulation coordinationInsulation voltageRated voltagePollution severitySurge voltage categoryApprovals

DimensionsClampingrange(nominal/min./max.) mm²Depth x width x height mmNote

Ordering data

Note

4

3

2

1

5

6PLC

I

PT 100

8 V DC...35 V DC

TC

Optional external CJC

+

+

PT100/2-/3-/4-wire,Thermocoupleacc.toIEC584,type: J, Thermocouple acc. to IEC 584, type: KPT100-200…+850°C,ThermocoupletypeJ-100…+1200°C,ThermocoupletypeK-200…+1370°C(internal or external CJC)Selectable by DIP Switch

4...20mA,20…4mA<600Ω3.5mA⁄23mA⁄noneSelectablebyDIPSwitch

DIP switch8...35 V DC Loop poweredca. 1 Wabsolute accuracy: < ±0.05 % of the measurement range, RTD (PT100) Basic accuracy: < ±0.1 °C of the measurement range, TC (J,K) Basic accuracy: < ±0.5 °C of the measurement rangeRTD(PT100)≤0.01%ofthemeasurementrange ⁄ °Cor0.02°C ⁄ °C‘,TC(J,K)0.1°C ⁄ °C2-way isolator≤30ms/≤300msSelectablebyDIPSwitch-25...+70°C

2.5 kVeff300 Veff

2II

cULus;FMEX;IECEXKEM;KEMAATEX; DETNORVER;GL

2.5/0.5/2.5114.3/6.1/112.5

Type Qty. Part No.ACT20M-RTCI-CO-OLP-S 1 1435590000

4

3

2

1

5

6PLC

I

PT 100

8 V DC...35 V DC

PT100/2-/3-/4-wire

PT100-200…+850°C

Selectable by DIP Switch

4...20mA,20…4mA<600Ω3.5mA⁄23mA⁄noneSelectablebyDIPSwitch

DIP switch8...35 V DC Loop poweredca. 1 Wabsolute accuracy: < ±0.1 % of the measurement range, Basic accuracy: < ±0.2 °C of the measurement range

RTD(PT100)≤0.01%ofthemeasurementrange ⁄ °Cor0.02°C ⁄ °CWithout isolation≤30ms/≤300msSelectablebyDIPSwitch-25...+70°C

N/A

2II

cULus;FMEX;IECEXKEM;KEMAATEX; DETNORVER;GL

2.5/0.5/2.5114.3/6.1/112.5

Type Qty. Part No.ACT20M-RTI-CO-EOLP-S 1 1435610000

Page 8: Datasheet ACT20M Signal Isolation and Conversion Launches...models extends Weidmuller’s signal conditioning portfolio with a package of solutions for industrial process measurement

8

Temperature transmitter• Choiceofisolatingornon-isolating

converters for RTDs.• Hundredsofmin/maxrange

combinations• OptionalPowerRailaccessory

simplifies jumpering and saves wiring time.

• ConfigurationviaDIPswitches• 3-wayisolation(AO-Smodelonly)

ACT20M-RTI-AO-S ACT20M-RTI-AO-E-S

ACT20M Signal Isolation and Conversion

Technical dataInputSensorInput measurement rangeTemperature input rangeOutputOutput currentOutput voltageload impedance currentload impedance voltageWire break detectionGeneral dataConfigurationSupply voltagePower consumptionAccuracy

GalvanicisolationTemperaturecoefficientStep response timeAmbient temperature (operational)Insulation coordinationInsulation voltage

Rated voltagePollution severitySurge voltage categoryApprovals

4

3

2

1

5

6

7

882 83

Supply

PLC

I, V

Supply

PT 100

PT100/2-/3-/4-wirePT100-200…+850°CSelectable by DIP Switch

0...20 mA, 4...20 mA Selectable by DIP Switch0(1)...5 V, 0(2)...10 V Selectable by DIP Switch≤600Ω≥10kΩ3.5mA⁄23mA⁄noneSelectablebyDIPSwitch

DIP switch24 V DC ± 30 %1 Wabsolute accuracy: < ±0.05 % of the measurement range, Basic accuracy: < ±0.1 % of the measurement range3-way isolator≤0.01%ofthemeasurementrange°Cor0.02°C⁄°C≤30ms/≤300msSelectablebyDIPSwitch-25...+70°C

2.5 kVeff

300 Veff

2II

cULus;FMEX;IECEXKEM;KEMAATEX; DETNORVER;GL

4

3

2

1

5

6

7

8

I, VOUT 1

Supply

PT 100

PT100/2-/3-/4-wirePT100-200…+850°CSelectable by DIP Switch

0...20 mA, 4...20 mA Selectable by DIP Switch0(1)...5 V, 0(2)...10 V Selectable by DIP Switch≤600Ω≥10kΩ3.5mA⁄23mA⁄noneSelectablebyDIPSwitch

DIP switch24 V DC ± 30 %1 Wabsolute accuracy: < ±0.1 % of the measurement range

Without isolation≤0.01%ofthemeasurementrange°Cor0.02°C⁄°C≤30ms/≤300msSelectablebyDIPSwitch-25...+70°C

N/AN/A2II

cULus;FMEX;IECEXKEM;KEMAATEX; DETNORVER;GL

DimensionsClampingrange(nominal/min./max.) mm²Depth x width x height mm

Note

2.5/0.5/2.5114.3/6.1/112.5

2.5/0.5/2.5114.3/6.1/112.5

Ordering data

Note

Type Qty. Part No.ACT20M-RTI-AO-S 1 1375510000

Type Qty. Part No.ACT20M-RTI-AO-E-S 1 1375520000

Page 9: Datasheet ACT20M Signal Isolation and Conversion Launches...models extends Weidmuller’s signal conditioning portfolio with a package of solutions for industrial process measurement

9

ACT20M Signal Isolation and Conversion

Temperature transmitter•Choiceofisolatingornon-isolating

converters for J or K thermocouples• Hundredsofmin/maxrange

combinations• OptionalPowerRailaccessory

simplifies jumpering and saves wiring time.

• ConfigurationviaDIPswitches• 3-wayisolation(AO-Smodelonly)

ACT20M-TCI-AO-S ACT20M-TCI-AO-E-S

Technical data

4

3

2

1

5

6

7

882 83

Supply

PLC

I, V

Supply

TC

Optional external CJC

+

+

4

3

2

1

5

6

7

8

I, VOUT

Supply

TC

Optional external CJC

+

+

InputSensorInput measurement range

Temperature input rangeOutputOutput currentOutput voltageload impedance currentload impedance voltageWire break detectionGeneral dataConfigurationSupply voltagePower consumptionAccuracy

GalvanicisolationTemperaturecoefficientStep response timeAmbient temperature (operational)Insulation coordinationInsulation voltageRated voltagePollution severitySurge voltage categoryApprovals

DimensionsClampingrange(nominal/min./max.) mm²Depth x width x height mm

Note

Thermocouple (Type J, K)ThermocoupletypeJ-100…+1200°C,ThermocoupletypeK-200…+1370°C(internalorexternalCJC)Selectable by DIP Switch

0...20 mA, 4...20 mA Selectable by DIP Switch0(1)...5 V, 0(2)...10 V Selectable by DIP Switch≤600Ω≥10kΩ3.5mA⁄23mA⁄noneSelectablebyDIPSwitch

DIP switch24 V DC ± 30 %ca. 1 Wabsolute accuracy: < ±0.05 % of the measurement range, TC (J,K) Basic accuracy: < ±0.5 °C of the measurement range3-way isolator<0.1%/°C≤30ms/≤300msSelectablebyDIPSwitch-25...+70°C

2.5 kVeff300 Veff2II

cULus;FMEX;IECEXKEM;KEMAATEX; DETNORVER;GL

2.5/0.5/2.5114.3/6.1/112.5

Thermocouple (Type J, K)ThermocoupletypeJ-100…+1200°C,ThermocoupletypeK-200…+1370°C(internalorexternalCJC)Selectable by DIP Switch

0...20 mA, 4...20 mA Selectable by DIP Switch0(1)...5 V, 0(2)...10 V Selectable by DIP Switch≤600Ω≥10kΩ3.5mA⁄23mA⁄noneSelectablebyDIPSwitch

DIP switch24 V DC ± 30 %ca. 1 Wabsolute accuracy: < ±0.1 % of the measurement range, Basic accuracy: < ±1 °C

Without isolation≤0.01%/°C≤30ms/≤300msSelectablebyDIPSwitch-25...+70°C

N/AN/A2II

cULus;FMEX;IECEXKEM;KEMAATEX; DETNORVER;GL

2.5/0.5/2.5114.3/6.1/112.5

Ordering data

Note

Type Qty. Part No.ACT20M-TCI-AO-S 1 1375480000

Type Qty. Part No.ACT20M-TCI-AO-E-S 1 1375500000

Page 10: Datasheet ACT20M Signal Isolation and Conversion Launches...models extends Weidmuller’s signal conditioning portfolio with a package of solutions for industrial process measurement

10

Bipolar converters• Forusewithcenter-zerosensors,

e.g. actuator position control, or bi-directional flow monitoring.

• DIPswitchessimplifyconfiguration• Conversionchoices:bipolarin/unipolar

out,orbipolarin/2xunipolarout.• OptionalPowerRailaccessorysimplifies

jumpering and saves wiring time.

ACT20M-BAI-AO-S ACT20M-BAI-2AO-S

ACT20M Signal Isolation and Conversion

4

3

5

6

7

882 83Supply

I, VOUT 1

± I, ± V IN

Supply

2

1

4

3

5

6

7

882 83Supply

I, VOUT 1

OUT 2

I, V

± I, ± V IN

Supply

Technical dataInput Input current

Input voltage

Input resistance, voltageInput resistance, current inputsOutputCut-off frequency (-3 dB)load impedance voltageNumber of outputsload impedance currentOutput voltage, noteOutput currentGeneral dataAccuracyConfigurationGalvanicisolationMounting railPower consumptionPower consumption, max.Step response timeSupply voltageTemperature coefficientType of connectionInsulation coordinationEMC standardsGalvanicisolationInsulation voltagePollution severityRated voltageStandardsSurge voltage categoryApprovalsApprovalsROHSDimensions Depth x width x height (mm)Note

Ordering data

Note

-10mA…0…+10mA,-20mA…0…+20mA-5V…0…+5V,-10V…0…+10V Selectable by DIP Switch≥1MΩ50Ωat20mA

≥100Hz,10HzSelectable by DIP Switch≥10kΩ1≤600Ω0(2)...10 V, 0(1)...5 V Selectable by DIP Switch0...20 mA, 4...20 mA Selectable by DIP Switch

< 0.05 % of measuring rangeDIP switch3-wayisolator;TS 35Typ. 400 mW0.8 W≤7ms,≤100ms,Selectable by DIP Switch24 V DC ± 30 %<0.01%ofspan/°C(TU)Screw connection

EN 61326-13-wayisolator;2.5 kVeff

2300 Veff

DIN EN 61010-1, DIN EN 60079II

cULus, DNV, FM, IECEx, Ex Conform

114.3 x 6.1 x 112.5

Type Qty. Part No.ACT20M-BAI-AO-S 1 1375450000

-10mA…0…+10mA,-20mA…0…+20mA-5V…0…+5V,-10V…0…+10V Selectable by DIP Switch≥1MΩ50Ωat20mA

≥100Hz,10HzSelectable by DIP Switch≥10kΩ22x300Ω0(2)...10 V, 0(1)...5 V Selectable by DIP Switch0...20 mA, 4...20 mA Selectable by DIP Switch

< 0.05 % of measuring rangeDIP switch4-wayisolator;TS 35Typ. 400 mW0.8 W≤7ms,≤100ms,Selectable by DIP Switch24 V DC ± 30 %<0.01%ofspan/°C(TU)Screw connection

EN 61326-14-wayisolator;2.5 kVeff

2300 Veff

DIN EN 61010-1, DIN EN 60079II

cULus, DNV, FM, IECEx, Ex Conform

114.3 x 6.1 x 112.5

Type Qty. Part No.ACT20M-BAI-2AO-S 1 1375470000

Page 11: Datasheet ACT20M Signal Isolation and Conversion Launches...models extends Weidmuller’s signal conditioning portfolio with a package of solutions for industrial process measurement

11

Rail bus accessories

ACT20M Signal Isolation and Conversion

CH20M BUS-PROFIL TS35x7.5/1000Support section for bus PCB

CH20M BUS-PROFIL TS35x15/1000Support section for bus PCB

CH20M BUS 4.50/05 AU/1000Bus PCB

•BusPCBforuseonTS35x7.5andTS35x15•Length:250,500or750mm•Fiveconductorpaths,goldplated•Electricalrating:63VAC,5A/conductorpath

Ordering dataType Qty. Part No.CH20MBUS4.50/ 05AU/250

10 1248220000

CH20MBUS4.50/ 05AU/500

10 1248230000

CH20MBUS4.50/ 05AU/750

5 1248240000

•SupportsectionforTS35x7.5•Length:250,500or750mm

Ordering dataType Qty. Part No.CH20M BUS-PROFIL TS35x7.5/250

10 1248150000

CH20M BUS-PROFIL TS35x7.5/500

10 1248160000

CH20M BUS-PROFIL TS35x7.5/750

5 1248170000

•SupportsectionforTS35x15•Length:250,500or750mm

Ordering dataType Qty. Part No.CH20M BUS-PROFIL TS35x15/250

5 1248180000

CH20M BUS-PROFIL TS35x15/500

5 1248190000

CH20M BUS-PROFIL TS35x15/750

5 1248210000

CH20M BUS-ADP TS35/1000Cover plate

CH20M BUS-AP LI TS35x7.5 & 15End plate

CH20M BUS-AP RE TS35x7.5 & 15End plate

•Endplateforrailbus•FitsonTS35x7.5andTS35x15•Right

Ordering dataType Qty. Part No.CH20M BUS-AP RE TS35x7.5&15

50 1193170000

•Coverplateforrailbus•Length:250,500or750mm

Ordering dataType Qty. Part No.

CH20MBUS-ADPTS35/250 10 1248250000

CH20MBUS-ADPTS35/500 10 1248260000

CH20MBUS-ADPTS35/750 5 1248270000

•Endplateforrailbus•FitsonTS35x7.5andTS35x15•Left

Ordering dataType Qty. Part No.CH20M BUS-AP LI TS35x7.5 &15

50 1193160000

SET CH20M BUS 250MM TS 35X15Set

• SETconsistsofoneeachof

CH20MBUS4.50/05AU/250

CH20MBUS-ADPTS35/250

CH20MBUS-APLITS35X7.5&15

CH20MBUS-APRETS35X7.5&15

CH20MBUS-PROFILTS35X15/250

Ordering dataType Qty. Part No.SET CH20M BUS 250MM TS 35X15

1 1335150000

SET CH20M BUS 250MM TS 35X7.5Set

• SETconsistsofoneeachof

CH20MBUS4.50/05AU/250

CH20MBUS-ADPTS35/250

CH20MBUS-APLITS35X7.5&15

CH20MBUS-APRETS35X7.5&15

CH20MBUS-PROFILTS35X7.5/250

Ordering dataType Qty. Part No.SET CH20M BUS 250MM TS 35X7.5

1 1335140000

Page 12: Datasheet ACT20M Signal Isolation and Conversion Launches...models extends Weidmuller’s signal conditioning portfolio with a package of solutions for industrial process measurement

12

ACT20M Signal Isolation and Conversion

Output-current loop-powered•Galvanicisolation•Verylowpowerconsumption•InputrangeselectedviaDIPswitch•Nocalibrationnecessary

OLP

U/I

I

Technical dataInputInput voltageInputresistance,voltage/currentInput currentRated current OutputOutput currentOutput signal limitLoadimpedance,voltage/currentCut-off frequency (-3 dB)General dataConfigurationSupply voltageAmbient temperature Default settingAccuracyTemperaturecoefficientStep response timeApprovalsInsulation coordinationStandardsEMC standardsRated voltageImpulse withstand voltageInsulation voltage

Surge voltage categoryPollution severityClearance&creepagedistances

DimensionsClampingrange(nominal/min./max.) mm²Length x width x height mmNote

Ordering data

Screw connectionNote

0...5V: 210 kΩ;0...10V:430kΩ/51Ω0(4)...20 mA40 mA

4...20 mA (current loop)Approx. 31 mA/RL = (UB-12V)/20mAz.B.600Ω at 24 V10Hz/100Hzswitchable

DIP switchmin.12VDC/max.30VDC0°C...+55°C0...20mA, 10 Hz0.2%ofmeasuringrangefinalvalue≤150ppm/K<10Hz:80ms;100Hz:50msCE;cULus

DIN EN 50178, DIN EN 61000-4-2EN 55011, EN 61000-6300 V4 kV4 kVeff/5s

III2≥ 5.5 mm

2.5/0.5/2.592.4/17.5/112.4

Type Qty. Part No.WAS5 OLP 1 8543720000

Setting options/switch position

Example of application

SW 1 1 2 3 4Input

0 … 20 mA n n n n

4 … 20 mA ◼

◼n n n

0 … 5 V n

0 … 10 V n ◼

◼ ◼

n n

Transmission frequency10 Hz n n n ◼

100 Hz n n n n

◼ = onn = off

7

8

9

1

2

3

SPSRL

4 ... 20mA0...10V

24 V DC

230 V AC

~230 V AC

24V DC

~

Sensor

WAVE ANALOGUEOLP

8543720000/8543730000

UL Class I, Div. 2

Page 13: Datasheet ACT20M Signal Isolation and Conversion Launches...models extends Weidmuller’s signal conditioning portfolio with a package of solutions for industrial process measurement

13

Thermal converter type: K,J,T,E,N,R,S,B•3-wayisolation•Internalcold-junctioncompensation•Powersupplycanbecross-connected

using plug-in jumpers•Suitableforinsulatedanduninsulated

thermocouples•WAVETOOLsoftwarehelpswith

configuration, download at www.weidmuller.com

ACT20M Signal Isolation and Conversion

PRO Thermo

J U/I

VC

Technical dataInputSensorTemperature input rangeOutputOutputvoltage/OutputcurrentLoadimpedance,voltage/currentOffsetcurrent/OffsetvoltageLine resistance in measuring circuitWire break detectionFine adjustmentStatus indicator

General dataConfigurationSupply voltagePower consumptionStep response timeCurrent-carrying capacity of cross-connect.Ambient temperature Storage temperatureDefault setting

ApprovalsInsulation coordinationStandardsEMC standardsRated voltageImpulse withstand voltageInsulation voltageSurge voltage categoryPollution severityClearance&creepagedistances

DimensionsClampingrange(nominal/min./max.) mm²Length x width x height mmNote

Ordering data

Screw connectionNote

Thermo element (IEC 584) type: K,J,T,E,N,R,S,B-200...+1820°C

0...10V/0(4)...20mA≥ 1 kΩ/≤ 600 Ωmax.100µA/max.0.05V50 ΩLEDflashing(outputvalue:>20mA,>10V)± 5% (switchable)Moduleactive:LEDon/wirebreakage:LEDflashing/ Error: LED off

DIP switch24 V DC ± 25 %800...850...950 mW at IOUT = 20 mAwithoutfilter:max.1.4s;withfilter:max.7.5s≤ 2 A0°C...+55°C-20°C...+85°CTypeK;0...1000°C;4...20mA;filter:off;man. calibration: offCE;cULusEX;GL

DIN EN 50178, DIN EN 61000-4-2EN 55011, EN 61000-63004 kV2 kVeff/5s

III2≥ 3 mm

2.5/0.5/2.592.4/17.5/112.4

Type Qty. Part No.WAS5 PRO Thermo 1 8560720000

Select ofthermocoupler

SW1TypKJTENRSB

1 2 3◼ ◼ ◼◼ ◼ ◼◼ ◼ ◼◼ ◼ ◼◼ ◼ ◼◼ ◼ ◼◼ ◼ ◼◼ ◼ ◼

Selection of minimumtemperature

SW1 1 2 3 4◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼◼ ◼ ◼ ◼

0 °C– 10 °C– 20 °C– 30 °C– 40 °C– 50 °C– 100 °C– 150 °C– 200 °C+ 50 °C+ 100 °C+ 150 °C+ 200 °C+ 250 °C+ 500 °CSpecial range

minϑ

Selection of outputSwitch 2

Output0 ... 10 V0 ... 20 V4 ... 20 V

6 7◼ ◼ ◼ ◼◼ ◼

Switching on themanual fine adjustment

SW 2man. adjust.offon

6◼◼

Switching on thefilter function

SW 2Filteroffon

8◼◼

AccuracyK -200 °C … -150 °C ± (5K + 0.1 % of set range) -150 °C … 1200 °C ± (3K + 0.1 % of set range) 1200 °C … 1372 °C ± (4K + 0.1 % of set range)J -200 °C … -150 °C ± (4K + 0.1 % of set range) -150 °C … 1200 °C ± (3K + 0.1 % of set range)T -200 °C … -150 °C ± (5K + 0.1 % of set range) -150 °C … 400 °C ± (3K + 0.1 % of set range)E -200 °C … -150 °C ± (4K + 0.1 % of set range) -150 °C … 1000 °C ± (3K + 0.1 % of set range)N -200 °C … -150 °C ± (6K + 0.1 % of set range) -150 °C … 1300 °C ± (3K + 0.1 % of set range)R -50 °C … 200 °C ± (10K + 0.1 % of set range) 200 °C … 1760 °C ± (6K + 0.1 % of set range)S -50 °C … 200 °C ± (10K + 0.1 % of set range) 200 °C … 1760 °C ± (6K + 0.1 % of set range)B 50 °C … 250 °C ± (25K + 0.1 % of set range) 250 °C … 500 °C ± (10K + 0.1 % of set range) 500 °C … 1820 °C ± (6K + 0.1 % of set range)

Selection oftemperature span

SW2

100 °C150 °C200 °C250 °C300 °C350 °C400 °C450 °C500 °C550 °C600 °C650 °C700 °C750 °C800 °C850 °C900 °C950 °C

1000 °C1050 °C1100 °C1150 °C1200 °C1250 °C1300 °C1350 °C1400 °C1450 °C1500 °C1600 °C1700 °C1800 °C

Span 1 2 3 4 5◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼◼ ◼ ◼ ◼ ◼

◼◼

= on= off

UL Class I, Div. 2

Page 14: Datasheet ACT20M Signal Isolation and Conversion Launches...models extends Weidmuller’s signal conditioning portfolio with a package of solutions for industrial process measurement

14

RTD signal isolator/converter•UniversallyadjustableviaDIPswitch•3-wayisolation•Linearisation•Powersupplycanbecross-connected

using plug-in jumpers•WAVETOOLsoftwarehelpswith

configuration,download at www.weidmuller.com

PRO RTD

ACT20M Signal Isolation and Conversion

RTDJ,R U/I

VC

Technical dataInputSensor

Temperature input rangeOutputOutputcurrent/OutputvoltageOffsetcurrent/OffsetvoltageLoadimpedance,voltage/currentWire break detectionFine adjustment

Status indicator

General dataConfigurationSupply voltagePower consumptionStep response time

Ambient temperature ApprovalsInsulation coordinationStandardsEMC standardsRated voltageImpulse withstand voltageInsulation voltage

Surge voltage categoryPollution severityClearance&creepagedistancesDimensionsClampingrange(nominal/min./max.) mm²Length x width x height mmNote

Screw connectionNote

PT100/2-/3-/4-wire,Ni100/2-/3-/4-wire,potentio-meter: min. 0–100 Ω, max. 0–100 kΩ, Resistance: 0–450 Ωconfigurable

0(4)...20mA/0...10Vmax.100µA/max.0.05V≥ 1 kΩ/≤ 600 ΩLEDflashing(outputvalue:>20mA,>10V)≥ ± 5 %, Version 1 and later: ≥12.5%/ potentiometer: 12.5%...25%Moduleactive:LEDon/wirebreakage:LEDflashing/ Error: LED off

DIP switch, Potentiometer24 V DC ± 25 %830...880...980mW at IOUT = 20 mAfast/slow:2-/3-/4-conductor:1.2s/2.2s; potentiometer:0.5s/1.1s0°C...+55°CCE;cULus;GL

DIN EN 50178, DIN EN 61000-4-2EN 55011, EN 61000-6300 V4 kV2 kVeff/5sIII2≥ 3 mm

2.5/0.5/2.592.4/17.5/112.4

Type Qty. Part No.WAS5 PRO RTD 1 8560700000

Ordering data

UL Class I, Div. 2

Page 15: Datasheet ACT20M Signal Isolation and Conversion Launches...models extends Weidmuller’s signal conditioning portfolio with a package of solutions for industrial process measurement

15

PRO RTD

ACT20M Signal Isolation and Conversion

Switch position / setting options

Choice of inputs ■ = on Switch 1 □ = off

Input 1 2 3PT100 2-wire ■ ■ ■PT100 3-wire □ ■ ■PT100 4-wire ■ □ ■R 2-wire □ □ ■NI100 2-wire ■ ■ □NI100 3-wire □ ■ □NI100 4-wire ■ □ □Potentiometer □ □ □

Choice of minimum input sizeSwitch 1

ϑmin Rmin Potimin 4 5 6 70 °C 0Ω 0 % ■ ■ ■ ■

-10 °C 10Ω 10 % ■ ■ ■ □-20 °C 20Ω 20 % ■ ■ □ ■-25 °C 20Ω 25 % ■ ■ □ □-30 °C 30Ω 30 % ■ □ ■ ■-40 °C 40Ω 40 % ■ □ ■ □-50 °C 50Ω 50 % ■ □ □ ■-60 °C 60Ω 60 % ■ □ □ □-70 °C 70Ω 70 % □ ■ ■ ■-80 °C 80Ω 80 % □ ■ ■ □-90 °C 90Ω □ ■ □ ■

-100 °C 100Ω □ ■ □ □-150 °C 150Ω □ □ ■ ■-200 °C 200Ω □ □ ■ □

Special area □ □ □ ■

Choice of measuring rangeSwitch 2

T R Poti 1 2 3 4 540 K 20Ω 20 % ■ ■ ■ ■ ■50 K 25Ω 25 % ■ ■ ■ ■ □60 K 30Ω 30 % ■ ■ ■ □ ■70 K 35Ω 35 % ■ ■ ■ □ □80 K 40Ω 40 % ■ ■ □ ■ ■90 K 45Ω 45 % ■ ■ □ ■ □

100 K 50Ω 50 % ■ ■ □ □ ■110 K 55Ω 55 % ■ ■ □ □ □120 K 60Ω 60 % ■ □ ■ ■ ■125 K 62,5Ω 62,5 % ■ □ ■ ■ □130 K 65Ω 65 % ■ □ ■ □ ■140 K 70Ω 70 % ■ □ ■ □ □150 K 75Ω 75 % ■ □ □ ■ ■160 K 80Ω 80 % ■ □ □ ■ □170 K 85Ω 85 % ■ □ □ □ ■180 K 90Ω 90 % ■ □ □ □ □190 K 95Ω 95 % □ ■ ■ ■ ■200 K 100Ω 100 % □ ■ ■ ■ □250 K 125Ω --- □ ■ ■ □ ■300 K 150Ω --- □ ■ ■ □ □350 K 175Ω --- □ ■ □ ■ ■400 K 200Ω --- □ ■ □ ■ □450 K 225Ω --- □ ■ □ □ ■500 K 250Ω --- □ ■ □ □ □550 K 275Ω --- □ □ ■ ■ ■600 K 300Ω --- □ □ ■ ■ □650 K 325Ω --- □ □ ■ □ ■700 K 350Ω --- □ □ ■ □ □750 K 375Ω --- □ □ □ ■ ■800 K 400Ω --- □ □ □ ■ □850 K 425Ω --- □ □ □ □ ■900 K 450Ω --- □ □ □ □ □

Choice of outputs Switch on the manual fine adjustmentsSwitch 2

Output 6 7 S. 10...10 V ■ □ Man. adjustment 80...5 V ■ ■ off □0...20 mA □ □ on ■4...20 mA □ ■

Choice of step response time

S. 2Step response time 8slow ■fast □

Accuracy, slow/fast step response timePT 100,Ni 100: 0,3 % from measuring range 0,8 %frommeasuringrange<100K/0,3K/0,8KPotentiometer:0.2%fromendvalue/0.3%Resistance:0.2%fromendvalue/0.3%

Temperature coefficientMeasuringrange≥200K ≤200ppm/°C100K≤Measuringrange<200K ≤250ppm/°C40K≤Measuringrange<100K ≤400ppm/°C

Adjustment example for zero and spanTemperature adjustment:Output 4…20mADIP switch -10°C…+110°CSpan 75…110°CRange 120 °CAdjustment range ± 12.5 %

Zero

–25° C–10° C

–5° C

Span

5° C

95° C110° C

125° C

110° C125° C

140° C

Wavetool adjustment tool This service tool enables quick and straightforwardconfigurationofthe WAVEANALOG PRO.Internet download:http://www.weidmuller.com

Page 16: Datasheet ACT20M Signal Isolation and Conversion Launches...models extends Weidmuller’s signal conditioning portfolio with a package of solutions for industrial process measurement

16

ACT20M Signal Isolation and Conversion

ACT20 power feed module• Distributesthevoltagesupplyonthe

busbar• CompatiblewithWeidmuller‘sCH20

rail bus• Optionalbackupsupplyconnection• ApprovedforinstallationinExZone2

/Div.2• Monitorsthesupplyvoltage• Alarmalertsviathestatusrelay

ACT20M-FEED-IN-PRO-S ACT20-FEED-IN-BASIC-S

Subject to technical changes • 03/14 • LIT1126

Technical dataInputPower supplyMax. input currentBackup power supplyTrigger level for the power supplyOutput, power supplyOutput voltage Output powerOutput currentOutput, status relay in safe zoneMax. voltageMax. currentMax. AC powerGeneral dataEfficiency degreeAmbient temperatureStorage temperaturePower consumptionProtection degreeWeightHumidityApprovalsDimensions Clampingrange(nominal/min./max.) mmLength x width x height mm2

Note

Ordering data

Note

51

52

53

54

Power supply, 0 V

Power supply, +24 V

Backup, 0 V

Backup, +24 V

NC

Status relay, N.C.

Status relay, shared

Status relay, N.O.

44

43

42

41

8182838485N

C

NC 0 V

+24

V

Sta

tus

Alarm

21.6...26.4 V DC4A21.6...26.4 V DCFault < 21 V DC

Input voltage -0.5 V DC @ 4 Amax. 96 Wmax. 4 A

250AC/30VDC2AAC/2ADC500VA/60W

> 97.9 %-20...+60°C-20...+85°C< 2 WIP20140 g< 95 %, no condensationcULus, cFMus, ATEX,IECExZone2,DNV,GOSTScrew connection2.5/0.5/2.5119.2/22.5/113.6

Type Qty. Part No.ACT20-Feed-In-PRO-S 1 8965500000

Power supply, +24 V

Power supply, 0 V

NC

NC

NC 0 V V 42

+

16.8...31.2 V DC2.5A

= U input= P input= I input

100 %-25...+70°C-40...+85°C< 2 WIP2070 g< 95 %, no condensationcULus, ATEX,IECExZone2,GL,DNV,cFMus,GOSTScrew connection2.5/0.5/2.5114.3/6.1/112.5

Type Qty. Part No.ACT20-FEED-IN-BASIC-S 1 12824900000