Frankl Et Al 2010
-
Upload
rodrigo-lameiras -
Category
Documents
-
view
219 -
download
0
Transcript of Frankl Et Al 2010
-
8/18/2019 Frankl Et Al 2010
1/13Spr ing 2011 | PCI Journal
C—C—
H
H
–H
–H
Editor’s quick points
n This paper describes the structural behavior of precast,prestressed concrete sandwich wall panels reinforced with a
carbon-fiber-reinforced polymer (CFRP) shear grid to achieve
composite action.
n Use of CFRP as a shear transfer mechanism was intended to
increase thermal insulation efficiency, enhance service life, and
increase overall structural capacity
n Test results of the experimental program were compared with
theoretical predictions of fully composite and noncomposite
actions to evaluate the percent composite action and to assess
the optimum panel configuration.
Behavior
of precast,
prestressed
concrete
sandwich
wall panels
reinforced
with CFRP
shear gridBernard A. Frankl,Gregory W. Lucier, Tarek K. Hassan,and Sami H. Rizkalla
Precast, prestressed concrete sandwich wall panels are
typically used for building envelopes. Such panels con-sist of two outer layers of precast, prestressed concrete
separated by an inner layer of insulation. The panels can
support gravity loads from floors or roofs, resist normal
or transverse lateral wind loads, insulate a structure, and
provide interior and exterior finished wall surfaces. Typical
panels are fabricated with heights up to 45 ft (14 m) and
with widths up to 12 ft (3.7 m). Concrete wythe thick-
nesses range from 2 in. to 6 in. (50 mm to 150 mm) with
overall panel thicknesses ranging from 5 in. to 12 in. (130
mm to 300 mm).
Precast, prestressed concrete sandwich wall panels maybe designed as noncomposite, partially composite, or fully
composite. Defining and designing for a partial degree of
composite action can significantly increase the structural
efficiency and reduce both initial and life-cycle costs of
a panel, compared with the fully noncomposite case. The
degree of composite action depends on the nature of the
connections between the two concrete wythes. Commonly
used shear transfer connectors include wire trusses, bent
wires, and solid zones of concrete penetrating the insula-
tion wythe (Fig. 1). Increasing the degree of composite ac-
tion between wythes increases the structural capacity of a
given panel, making it more structurally efficient. However,
C—C—
H
H
–H
–H
-
8/18/2019 Frankl Et Al 2010
2/13 4PCI Journal | Spr ing 2011
—C—C— –H
–H
–H
–H
Lee and Pessiki found that a three-wythe panel with stag-
gered longitudinal solid concrete zones exhibits behavior
similar to that of a fully composite panel.6 They also
observed that transfer of the prestressing force induced
cracks in the concrete wythes parallel to the prestress-
ing strands. A finite-element analysis was conducted to
investigate the prestressing forces during release. Results
of the analysis showed that modeling the concrete and the
insulation with solid block elements provided results close
to the measured values.
Salmon et al.7 introduced the use of fiber-reinforcedpolymer (FRP) bars formed in a truss orientation in place
of metal wire trusses. Test results showed that the use
of FRP achieved a high level of composite action and
provided thermal benefits similar to noncomposite precast,
prestressed concrete sandwich wall panels. Following the
same concept, a carbon-fiber-reinforced polymer (CFRP)
shear connection grid was used in the construction of pre-
cast, prestressed concrete sandwich wall panels in 2003.8
Because carbon fibers have a thermal conductivity that is
about 14% that of steel, connecting concrete wythes with
carbon grid allows a panel to develop composite structuralaction without thermal bridges. Therefore, the insulating
value of the panel is maintained.1 The grid was oriented di-
agonally between the concrete wythes, normal to the wall
surface, allowing a truss mechanism to develop.
This paper describes the behavior of six full-scale precast,
prestressed concrete sandwich wall panels. The panels
were composed of two outer precast, prestressed concrete
wythes and an internal layer of insulation with shear grid
reinforcement placed through the core into each concrete
wythe. The various parameters considered in the current
study included the type of insulation, presence of solid
traditional composite shear connections have the nega-
tive consequence of thermally bridging the two concrete
wythes, thus decreasing the thermal efficiency.
Wall panels were first introduced during the 1960s as
double-tee sandwich panels.1 Solid concrete zones were
used between the double-tee and the inner concrete wythe
to develop composite action. Double-tee sandwich panels
provided a robust structural wall but sacrificed the poten-
tial thermal savings. Flat concrete slabs were soon used in
place of double-tees to reduce the thickness of the building
envelope and to improve the aesthetics of a structure. Asin double-tee sandwich panels, composite action between
the wythes of flat slab sandwich wall panels was often
achieved through solid concrete zones.
More recently, steel ties and wire trusses were introduced
to replace solid concrete zones. Steel wythe connections
improved the thermal performance of sandwich wall panels
compared with solid concrete zones, but such ties still act
as thermal bridges.1 Noncomposite panels were introduced
in the 1980s and aimed at addressing the thermal deficien-
cies created by steel ties. Noncomposite panels contain
minimal shear connectors to substantially reduce thepotential for thermal bridging but sacrifice the structural
efficiency of a composite structure.
Despite their lower structural capacity, noncomposite
panels became popular due to their thermal savings and
architectural characteristics. The typical design method for
precast, prestressed concrete sandwich wall panels often
assumes noncomposite action.2 In practice, however, panels
generally exhibit partially composite behavior. Test results
by several researchers have shown that significant shear
transfer occurs between the wythes.3–5
Figure 1. Commonly used shear transfer connectors include wire trusses, bent wires, and solid zones of concrete penetrating the insulation core.
Note: CFRP = carbon-fiber-reinforced polymer.
Wire truss connector Bent wire connectors Solid concrete zone CFRP grid material sample CFRP grid shear transfer mechanism in section cut
from a tested pane
(insulation removed)
—C—C— –H
–H
–H
–H
-
8/18/2019 Frankl Et Al 2010
3/13Spr ing 2011 | PCI Journal4
C—C—
H
H
–H
–H
(Fig. 2). All panels were 8 in. (200 mm) thick and consist-
ed of three layers. Table 1 summarizes the configurationsof the tested panels.
Panels EPS1, EPS2, XPS1, XPS3, and XPS4 consisted of
two 2-in.-thick (50 mm) concrete wythes with a 4-in.-thick
(100 mm) insulation layer in between. This arrangement
was designated as a 2-4-2 panel configuration. One wythe
of a 2-4-2 panel included two 2-in.-thick (50 mm) and
24-in.-wide (610 mm) internal pilasters along the full
height of each panel at 1 / 4 and3 / 4 widths (Fig. 3). The two
pilasters were provided to carry axial loads from the two
corbels located at the top of the inner panel face. Lifting
anchors on the inner face were centered on the pilasters in2-4-2 panels, so these anchors did not bridge the concrete
wythes. Two lifting anchors were also included on the
top edge of each panel. These anchors spanned between
concrete wythes. Panel XPS2 consisted of a 4-in.-thick
(100 mm) concrete wythe, a 2-in. (50 mm) layer of insula-
tion, and an outer 2-in. (50 mm) concrete wythe. Figure 4
shows this configuration, which was designated 4-2-2 with
two corbels located at the top of the 4-in.-thick wythe. The
4-2-2 panel was designed to carry the axial load through its
thicker concrete wythe and therefore did not have internal
pilasters.
concrete zones, panel configuration, and shear grid rein-
forcement ratio.
The loading sequence for each panel was selected to simu-
late the effect of service gravity and wind loads for a 50-
year lifespan. Load and support conditions were designed
to mimic field conditions. Test results from the experimen-
tal program were compared with theoretical predictions
to evaluate the percent composite action achieved by each
tested panel.
Experimental program
Six precast, prestressed concrete sandwich wall panelswere designed and tested to evaluate their flexural response
under combined vertical and lateral loads. The study
included panels fabricated with two different insulation
types: expanded polystyrene (EPS) insulation and extruded
polystyrene (XPS) insulation. According to the manufac-
turer, the selected EPS insulation had a nominal density of
1 lb/ft3 (16 kg/m3) and a nominal compressive strength of
13 psi (90 kPa). The selected XPS insulation had a nominal
density of 1.8 lb/ft3 (29 kg/m3) and a nominal compressive
strength of 25 psi (170 kPa).
The panels were 20 ft tall × 12 ft wide (6.1 m × 3.7 m)
Inner panel view during testing Outer panel view during testing
Figure 2. The panels were 20 ft tall × 12 ft wide (6.1 m × 3.7 m).
-
8/18/2019 Frankl Et Al 2010
4/13 4PCI Journal | Spr ing 2011
—C—C— –H
–H
–H
–H
CFRP shear grid was provided between the two concrete
wythes to transfer the shear stresses across the insulation
and to develop a composite action between the wythes.
The CFRP grid was placed in strips running parallel to the
longitudinal axis of each panel (Fig. 5). The CFRP strips
were embedded 3 / 4 in. (19 mm) into each concrete wythe.
All panels except XPS4 contained the same grid layout.
Panel XPS4 contained an additional 30 ft (9.1 m) of shear
grid. In addition to the CFRP grid, panel XPS1 contained
Each concrete wythe was reinforced with a sheet of
welded-wire reinforcement in the plane of the wythe and
prestressed in the longitudinal direction by five 270 ksi
(1860 MPa), low-relaxation prestressing strands. The
diameters of the prestressing strands in the 2-in.-thick (50
mm) and 4-in.-thick (100 mm) concrete wythes were 3 / 8 in.
(10 mm) and 1 / 2 in. (13 mm), respectively. Figures 3 and 4
show the strands used and their initial tension levels.
Figure 3. The configuration and dimensions of 2-4-2 panels. Panel in photo cut to show cross section. Note: CFRP = carbon-fiber-reinforced polymer; WWR = welded-wirereinforcement.
Table 1. Summary of experimental tests and results
Panel
identificationInsulation
Wythe
thicknesses, in.
Solid
zones
Shear grid
layout
Concrete
strength, psi
Failure load
(1.2D + 0.5L r +…)
Service load
deflection
D + L r + W
EPS1 EPS 2-4-2 No Layout 1 7620 2.8W 120 h /460
EPS2 EPS 2-4-2 No Layout 1 7670 1.8W 150 (2.8W 120) h /500
XPS1 XPS 2-4-2 Yes Layout 2 10,080 1.6W 120 h /1480
XPS2 XPS 4-2-2 No Layout 1 8790 3.2W 120 h /755
XPS3 XPS 2-4-2 No Layout 1 7670 0.7W 120 n.a.
XPS4 XPS 2-4-2 No Layout 3 7340 1.8W 120 h /700
Note: D = dead load; h = height = 240 in.; L r = roof live load; n.a. = not applicable; W = wind load at a selected design wind speed; W 120 = 6.96 kip;
W 150 = 10.56 kip. 1 in. = 25.4 mm; 1 kip = 4.448kN; 1 psi = 6.895 kPa.
-
8/18/2019 Frankl Et Al 2010
5/13Spr ing 2011 | PCI Journal
C—C—
H
H
–H
–H
10 discretely located solid concrete zones throughout the
height and width of the panel (Fig. 5).
Test setup
All panels were tested in the laboratory using a steel testing
frame that allowed for simultaneous application of gravity-
and lateral loads (Fig. 2). Reverse-cyclic lateral loads were
applied at a rate of 1 cycle per 10 sec (0.1 Hz) to simulate
wind pressures. The testing frame consisted of one braced
frame on each side of the panel to support an upper cross
beam. This cross beam in turn provided the upper lateralsupport to the panel. The entire setup was anchored to the
laboratory strong floor. A closed-loop hydraulic actuator,
supported by a strong reaction wall, applied the lateral
load.
Each panel was simply supported in the testing frames at
the top and bottom edges. The bottom of the panel was
supported by a hinge, which restrained horizontal and
vertical movements while allowing for rotation. The center
of the hinge was located 1 in. (25 mm) below the bottom
of each panel. The top of each panel was supported using a
sliding pin connection that restrained horizontal motion but
allowed for vertical movement and rotation. The center of
the sliding pin was located 4 in. (100 mm) above the top of
the panel.
Vertical loads were applied to the top of each corbel by a
hydraulic jack and cable (Fig. 2) to simulate the effects of
a 60-ft-span (18.3 m) double-tee roof system. The jack was
connected to an accumulator to maintain a constant axial
load as the panel deformed. Lateral loads were applied by
the actuator connected to a spreader beam system, which
was used to push and pull the panel to simulate wind pres-
sure and suction. Two loading tubes were provided at each¼-height of each panel, one on each wythe, to distribute
the lateral load across the width of the panel. The lateral-
loading mechanism included a vertical spreader beam
that could shorten and elongate as the panel deformed to
prevent the transfer of any unintended forces to the panel.
Each panel was subjected to reverse-cyclic loading begin-
ning at a level equivalent to 70% of the service load. The
loading regime was selected using a Weibull distribution to
simulate wind loads over a 50-year service life.9
All panels were instrumented to measure lateral deflection,
relative displacement between the two concrete wythes,
Figure 4. The configuration in this drawing was designated as 4-2-2 with two corbels located at the top of the 4-in.-thick wythe. Panel cut to show cross section. Note:
CFRP = carbon-fiber-reinforced polymer; WWR = welded-wire reinforcement. 1 in. = 25.4 mm; 1 ft = 0.305 m; 1 lb = 4.448 N.
-
8/18/2019 Frankl Et Al 2010
6/13 4PCI Journal | Spr ing 2011
—C—C— –H
–H
–H
–H
surface strain of the concrete, and applied axial and lateral
loads. The strain profile across the thickness of each panel
was measured with four electrical-resistance strain gauges
across the panel section at three locations along the height.
Each panel was subjected to 3710 fully reversed lateral-
load cycles at 45% of the factored lateral wind load, equiv-alent to 0.7W , with a factored axial load of 1.2 D + 0.5 Lr in
place, where W is wind load, D is dead load, and Lr is roof
live load. The initial cycles were followed by 177 cycles at
50% of the factored lateral wind load (0.8W ) with the fac-
tored axial load applied. Subsequent individual cycles were
applied at 60%, 80%, and 100% of the factored lateral
wind load (1.0W , 1.3W , 1.6W ), all with the factored axial
load applied. After completion of all lateral cycle loads in
the presence of gravity load, the lateral load was increased
in one direction only until failure.
Results and discussion
Lateral displacements
Figure 6 depicts the measured lateral displacement at
midheight for the different panels. In general, the measured
lateral deflections due to the applied axial load only were
found to depend on the thickness of the panel configuration
(2-4-2 or 4-2-2) and also on the type and configuration of
shear transfer mechanism used. Lateral deflection due to
axial load alone was shown as the offset deflection at zero
lateral-load level.
The allowable displacement of h /360 (where h is the height
of the panel) at service load level (as per the American
Concrete Institute’s ACI 533R-93, Guide for Precast
Concrete Wall Panels10) was compared with the measured
values for the tested panels. The two EPS-insulation panels
EPS1 and EPS2 behaved almost identically throughout the
loading cycles. The panels’ stiffnesses remained constantto a lateral load of 15 kip (67 kN), or 2.2W 120 (where W 120
is the wind load at a wind speed of 120 mph), beyond
which concrete cracking occurred, considerably reducing
the stiffness (Fig. 6). Similar behavior was observed for
XPS2. The behavior of panels XPS1 and XPS4 remained
linear to a lateral load level of about 10 kip (44.5kN), or
1.4W 120. Panel XPS3 failed prematurely at a lateral load
level of 5 kip (22 kN).
The maximum measured displacements at service-load lev-
el for EPS1 and EPS2 were equivalent to h /460 and h /500,
respectively. These service-level displacements were wellwithin the ACI 533R limit. Among the XPS-insulation
panels, XPS1 experienced the least stiffness degradation
with increased load cycles because of the presence of solid
concrete zones connecting the inner and outer wythes. The
maximum lateral displacement at service-load level for
XPS1 was equivalent to h /1480.
Panels XPS2 and XPS4 exhibited minimal lateral-load
degradation. The measured lateral displacements for both
panels did not increase noticeably throughout the fatigue
cycles. The maximum lateral displacements at service-
load level for XPS2 and XPS4 were equivalent to h /755
Figure 5. Layout of CFRP shear grids. Note: CFRP = carbon-fiber-reinforced polymer. 1 in. = 25.4 mm; 1 ft = 0.305 m.
-
8/18/2019 Frankl Et Al 2010
7/13Spr ing 2011 | PCI Journal
C—C—
H
H
–H
–H
Figure 6. Measured lateral displacement at mid-height for the different panels.
-
8/18/2019 Frankl Et Al 2010
8/13 4PCI Journal | Spr ing 2011
—C—C— –H
–H
–H
–H
XPS4 showed a clear reduction in composite action with
increasing lateral load. A significant discontinuity in the
strain at ultimate load was observed for these panels, indi-
cating a partial composite behavior at ultimate.
Failure modes
The observed failure modes for EPS1, XPS1, and XPS2
were localized at the tops of the panels in the corbel zones.
Failure was characterized by a shear failure around the cor-bels extending down about 2 ft (600 mm). Figure 8 shows
an example of these failures, which were accompanied by
separation of the top of the panel. Panel EPS2 exhibited a
flexural-shear failure across the width of the panel at about7 / 8 the panel’s height. Panels XPS3 and XPS4 exhibited a
flexural-shear failure across the width of the panel at about7 / 8 the panel’s height along with a simultaneous top-of-
panel separation.
All panels with sufficient shear transfer mechanisms
exhibited deflections well below the limiting value speci-
fied by ACI 533R and sustained loads prior to failure inexcess of their factored design loads (Table 1). However,
panel XPS3, which had a gap between the outer wythe and
foam, failed prematurely prior to the service load with high
deflections.
Uniform design pressures for panels EPS1, XPS1, XPS2,
XPS3, and XPS4 were assumed to be 29 lb/ft2 (1.4 kPa),
corresponding to a design wind speed of 120 mph (193
km/hr). Although designed for 29 lb/ft2 (1.4 kPa), EPS2
was tested for an equivalent pressure of 44 lb/ft2 (2.1 kPa),
corresponding to a design wind speed of 150 mph (241
km/hr). Thus, the lateral fatigue loading on EPS2 was
and h /700, respectively. Failure of panel XPS3 occurred
before reaching the design service-load level. Test results
suggested that the accumulated degradation for XPS3 was
substantial compared with other panels. A gap between
the outer concrete wythe and the foam, observed before
testing, likely contributed to the premature failure. This
gap measured about 1 / 4 in. (6 mm) and was visible along
the majority of both 20 ft (6.1 m) panel sides. The gap was
identified by the precast concrete producer after stripping
the forms, but because the panel was intended for testing, itwas decided not to reject the piece.
Strain profiles
The strain profiles across the thickness of the panels were
measured to determine the degree of composite action
between the two concrete wythes. Figure 7 shows typical
results recorded during the testing of the panels at ultimate
load. For all panels, the inner wythe experienced com-
pressive strains while the outer wythe experienced tensile
strains under the effect of applied factored gravity loads.
Test results showed that EPS-insulation panels EPS1 andEPS2 as well as XPS1 with solid concrete zones exhib-
ited and maintained a high level of composite action until
failure.
The strain profile at ultimate load indicates that the neutral
axes of these panels were located closer to the elastic cen-
troid of the composite cross section rather than the elastic
centroid of each individual wythe. The measured strains for
XPS2 (4-2-2 configuration) indicated that each wythe acted
independently in carrying the applied loads and the neutral
axis was located within the thickness of each wythe. This
behavior indicated noncomposite action. Panels XPS3 and
Figure 7. Strain profile distribution for different panels at ultimate loads. Note: The negative (-) sign indicates compression. Note: 1 kip = 4.448 kN.
-
8/18/2019 Frankl Et Al 2010
9/13Spr ing 2011 | PCI Journal
C—C—
H
H
–H
–H
M cr = cracking moment
M a = acting moment
I g = gross moment of inertia of the section
I cr = cracked transformed moment of inertia of the section
Recent research findings by Bischoff and Scanlon have
demonstrated that Eq. (2) is only applicable for flexural
members with an I g / I cr ratio less than 3, which corresponds
to beams or slabs with a steel reinforcing ratio greater than
1%.12 It has been demonstrated that applying Eq. (2) tocross sections with an I g / I cr ratio greater than 3 consider-
ably overestimates the member stiffness.11 Equation (3)
is an alternative formulation of the effective moment of
inertia that was proposed by Bischoff and Scanlon.11
1
I
M
M
I
I
I I
1
ef f
a
cr
g
cr
cr
g2 #=
- -f p > H (3)
The ratios of I g / I cr for the inner and outer wythes of thetested panels ranged from 20 to 183, which is significantly
higher than the limiting value of 3 proposed by Bischoff
and Scanlon.11 Figure 9 shows comparisons between the
measured and predicted displacements for different panels
using both approaches for the effective moment of inertia.
For the theoretical fully composite case, applied loads and
moments were assumed to act on the fully composite sec-
tion. For the theoretical noncomposite case, it was assumed
that the applied axial load was resisted by the inner wythe
(with corbels) alone. Applied moments were assumed to
be distributed to the inner and outer wythes depending on
higher than the load used for the other panels.
Analysis of sandwichwall panels
To evaluate the degree of composite action for the panels,
the measured lateral displacements were compared with the
predicted values assuming both fully composite and fully
noncomposite behaviors. The percentage of composite ac-
tion k was evaluated for all tested panels using Eq. (1).
k 100exp
noncomposite
n on co mp os it e e rim en ta l
compositeD D
D D=
-- a k (1)
where
∆experimental = measured displacement at a selected load level
∆composite = corresponding theoretical displacement as-
suming fully composite behavior
∆noncomposite = corresponding theoretical displacement as-
suming fully noncomposite behavior
To determine theoretical panel displacements beyond
cracking, the effective moment of inertia I eff was calcu-
lated by Eq. (2) in accordance with ACI’s Building Code
Requirements for Structural Concrete (ACI 318-05) and
Commentary (ACI 318R-05).11
1 I M
M
M
M I I I
ef f
a
cr
a
cr
g cr g
33
#= + -f fp pR
T
SSSS
V
X
WWWW
(2)
where
Figure 8. Typical observed failure modes for EPS1, XPS1, and XPS2.
Corbel-zone shear failure on inner wythe Outer wythe cracking following top-of-panel separation at failure
-
8/18/2019 Frankl Et Al 2010
10/13 5PCI Journal | Spr ing 2011
—C—C— –H
–H
–H
–H
for XPS2 was significantly lower than for other panels,the maximum displacement at service load level was still
within the ACI 533R limitations. Panel XPS3 failed prior
to reaching the combined axial and lateral service-load
condition.
Conclusion
The flexural behaviors of six full-scale insulated precast,
prestressed concrete sandwich wall panels were investi-
gated. The panels were subjected to monotonic axial and
reverse-cyclic lateral loading to simulate gravity and wind
pressure loads, respectively. Based on the findings of this
their individual stiffnesses.
The distribution ratio was calculated using the average of
their gross and cracked moments of inertia. The percentage
of composite action was calculated for each panel under
the combined axial and lateral service load, and Table 2
summarizes the results. In all calculations, a 20 ft (6.1 m)
nominal span was assumed.
The estimated composite action for EPS1, EPS2, XPS1,
and XPS4 was nearly 100%. Panel XPS2 exhibited 18%
composite action under the combined axial and lateral
service load. Although the percent of composite action
Figure 9. Load-lateral displacement behavior for the panels.
-
8/18/2019 Frankl Et Al 2010
11/13Spr ing 2011 | PCI Journal
C—C—
H
H
–H
–H
study, several conclusions were made:
• Panel stiffness and deflections are significantly af-
fected by the type and configuration of the shear
transfer mechanism. Panel stiffness is also affected by
the type of foam.
• Values of percent composite action near 100% can be
achieved with CFRP grid shear connections or with
solid concrete zones.
• Appropriate use of CFRP shear grid can provide an
effective shear transfer mechanism in precast, pre-
stressed concrete sandwich wall panels, as evidencedby the behavior of panels EPS1, EPS2, XPS2, and
XPS4. All panels sustained loads in excess of their
factored design loads and exhibited large deformations
before failure. CFRP grid can provide the required
composite action between wythes using either EPS or
XPS foam.
• Appropriate selection of the CFRP shear-grid quantity
and configuration is critical to achieve optimal struc-
tural performance of a panel. Proper quality control in
production is especially important for composite wall
panels.
• For a given shear transfer mechanism, a higher percent
composite action can be achieved using EPS insula-
tion rather than XPS insulation. Use of XPS insulation
requires an increase of the shear reinforcement ratio
compared with EPS insulation.
Acknowledgments
The authors are grateful for the support of AltusGroup and
the assistance provided by Harry Gleich of Metromont
Corp. and Steve Brock of Gate Precast.
Table 2. Percentage of composite action for different panels at service load level
Panel
identification
Experimental
displacement, in.
Composite
displacement, in.
Noncomposite displacement, in. k , % k , %
Bischoff formula
for I eff
ACI 318 formula
for I eff
Bischoff formula
for I eff
ACI 318 formula
for I eff
EPS1 0.21 0.200 39.6 6.70 100.0 99.8
EPS2 0.24 0.200 39.6 6.70 99.9 99.4
XPS1 0.14 0.087 28.8 2.20 99.8 97.6
XPS2 0.46 0.089 0.5 0.50 17.7 17.7
XPS3 n.a.* 0.087 n.a. n.a. n.a. n.a.
XPS4 0.31 0.087 20.1 3.40 98.9 93.5
*Specimen XPS3 failed at a lateral load level less than the design service load.
Note: Composite displacements differ between EPS and XPS 2-4-2 panels due to different values for concrete elastic modulus. I eff = effective moment
of inertia; k = percentage of composite action; n.a. = not applicable. 1 in. = 25.4 mm.
-
8/18/2019 Frankl Et Al 2010
12/13 5PCI Journal | Spr ing 2011
—C—C— –H
–H
–H
–H
References
• Gleich, H. 2007. New Carbon Fiber Reinforcement
Advances Sandwich Wall Panels. Structure Magazine
(April): pp. 61–63.
• PCI Committee on Precast Sandwich Wall Panels.
1997. State-of-the-Art of Precast/Prestressed Sand-wich Wall Panels. PCI Journal, V. 42, No. 2 (March–
April): pp. 92–134.
• Pessiki, S., and A. Mlynarczyk. 2003. Experimental
Evaluation of Composite Behavior of Precast Con-
crete Sandwich Wall Panels. PCI Journal, V. 48, No. 2
(March–April): pp. 54–71.
• Bush, T. D., and G. L. Stine. 1994. Flexural Behavior
of Composite Prestressed Sandwich Panels. PCI Jour-
nal, V. 39, No. 2 (March–April): pp. 112–121.
• Lee, B., and S. Pessiki. 2007. Design and Analysis of
Precast, Prestressed Concrete Three-Wythe Sandwich
Wall Panels. PCI Journal, V. 52, No. 4 (July–August):
pp. 70–83.
• Lee, B., and S. Pessiki. 2008. Experimental Evaluation
of Precast, Prestressed Concrete, Three-Wythe Sand-
wich Wall Panels. PCI Journal, V. 53, No. 2 (March–
April): pp. 95–115.
• Salmon, D. C., A. Einea, M. K. Tadros, and T. D.
Culp. 1997. Full Scale Testing of Precast Concrete
Sandwich Panels. ACI Structural Journal, V. 94, No. 4(July–August): pp. 354–362.
• Frankl, B. 2008. Structural Behavior of Insulated Pre-
cast Prestressed Concrete Sandwich Panels Reinforced
with CFRP Grid. M.Sc. thesis. Department of Civil,
Construction and Environmental Engineering, North
Carolina State University, Raleigh, NC.
• Xu, Y. L. 1995. Determination of Wind-Induced Fa-
tigue Loading on Roof Cladding. Journal of Engineer-
ing Mechanics, ASCE, V. 121, No. 9 (September): pp.
956–963.
• American Concrete Institute (ACI) Committee 533R.
2004. Guide for Precast Concrete Wall Panels. ACI
533R-93. Farmington Hills, MI: ACI.
• ACI Committee 318. 2005. Building Code Require-
ments for Structural Concrete (ACI 318-05) and
Commentary (ACI 318R-05). Farmington Hills, MI:
American Concrete Institute (ACI).
• Bischoff, P. H., and A. Scanlon. 2007. Effective Mo-
ment of Inertia for Calculating Deflections of Concrete
Members Containing Steel Reinforcement and Fiber-
Reinforced Polymer Reinforcement. ACI Structural
Journal, V. 104, No. 1 (January): pp. 68–75.
-
8/18/2019 Frankl Et Al 2010
13/13
C—C—
H
H
–H
–H
Notation
D = dead load
h = height of the panel
I cr = cracked transformed moment of inertia of the
section
I eff = effective moment of inertia
I g = gross moment of inertia of the section
k = percentage of composite action
Lr = roof live load
M a = acting moment
M cr = cracking moment
W = wind load
W 120 = wind load at a wind speed of 120 mph
W 150 = wind load at a wind speed of 150 mph
∆composite = corresponding theoretical displacement as-
suming fully composite behavior
∆experimental = measured displacement at a selected load level
∆noncomposite = corresponding theoretical displacement as-
suming fully noncomposite behavior
About the authors
Bernard A. Frankl graduated with
his MS in civil engineering fromNorth Carolina State University in
Raleigh, N.C., and now works for
the South Dakota Department of
Transportation.
Gregory W. Lucier is the manager
of the Constructed Facilities
Laboratory at North Carolina
State University.
Tarek K. Hassan, PhD, is an
associate professor for the
Structural Engineering Depart-
ment at the Faculty of Engineer-
ing at Ain Shams University, and
a senior structural engineer at Dar
Al Handasa, Cairo, Egypt.
Sami H. Rizkalla, PhD, P.Eng., is
a Distinguished Professor of Civil,
Construction and Environmental
Engineering, director of the
Constructed Facilities Laboratory,and director of the National
Science Foundation Industry/
University Cooperative Research Center at North
Carolina State University.
Synopsis
This paper describes the structural behavior of precast,
prestressed concrete sandwich wall panels reinforced
with carbon-fiber-reinforced polymer (CFRP) sheargrid to achieve composite action. Use of CFRP as a
shear transfer mechanism was intended to increase
the thermal insulation efficiency, enhance the service
life, and increase the overall structural capacities of the
panels.
This study included testing of six full-scale sandwichwall panels, each measuring 20 ft × 12 ft (6.1 m × 3.7
m). The panels consisted of two outer prestressed con-
crete wythes and an inner insulation wythe. The study
included two types of insulation and several shear
transfer mechanisms with different CFRP reinforce-
ment ratios to examine the degree of composite action
developed between the two concrete wythes.
All panels were simultaneously subjected to applied
gravity and lateral loads. Reverse-cyclic lateral loads
simulated the effects of wind pressure and suction. All
panels were subjected to approximately 4000 cycles
of lateral loading with the presence of factored gravity
load. Following each fatigue regime, the lateral loads
were increased until failure was achieved. Test results
of the experimental program were compared with theo-
retical predictions of fully composite and noncompos-
ite actions to evaluate the percent composite action and
to assess the optimum panel configuration.
Keywords
Carbon-fiber-reinforced polymer, CFRP, composite,
insulated wall panel, sandwich wall panel, shear grid.
Review policy
This paper was reviewed in accordance with the
Precast/Prestressed Concrete Institute’s peer-review
process.
Reader comments
Please address any reader comments to journal@pci.
org or Precast/Prestressed Concrete Institute, c/o PCI
Journal, 200 W. Adams St., Suite 2100, Chicago, IL
60606. J