8/19/2019 Y23_ET101 http://slidepdf.com/reader/full/y23et101 1/6 Bulletin 5715-483 Installation Manual Series ET101 Power Amplifier for Flow Valves Parker Hannifin GmbH Hydraulic Controls Division Gutenbergstr. 38 41564 Kaarst, Germany Tel.: (+) 2131-513-0 Fax: (+) 2131-513-230 www.parker.com Copyright 2000, Parker Hannifin GmbH Contents

Transcript of Y23_ET101

Page 1: Y23_ET101

8/19/2019 Y23_ET101

http://slidepdf.com/reader/full/y23et101 1/6

Bulletin 5715-483

Installation ManualSeries ET101

Power Amplifier forFlow Valves

Parker Hannifin GmbHHydraulic Controls DivisionGutenbergstr. 3841564 Kaarst, GermanyTel.: (+) 2131-513-0

Fax: (+) 2131-513-230www.parker.com

Copyright 2000, Parker Hannifin GmbHContents

Page 2: Y23_ET101

8/19/2019 Y23_ET101

http://slidepdf.com/reader/full/y23et101 2/6

2 Parker Hannifin GmbHHydraulic Controls DivisionHydraulics

IA ET101 UK A5.PM6.5 MM

Power Amplifier for Flow ValvesSeries ET101Installation Manual

Note

This document and other information from Parker Hannifin GmbH, itssubsidiaries, sales offices and authorized distributors provide productor system options for further investigation by users having technicalexpertise. Before you select or use any product or system it is importantthat you analyse all aspects of your application and review theinformation concerning the product or system in the current product

catalogue. Due to the variety of operating conditions and applicationsfor these products or systems, the user, through his own analysis andtesting, is solely responsible for making the final selection of theproducts and systems and assuring that all performance and safetyrequirements of the application are met. The products are subject tochange by Parker Hannifin GmbH at any time without notice.

Home

Page 3: Y23_ET101

8/19/2019 Y23_ET101

http://slidepdf.com/reader/full/y23et101 3/6

3 Parker Hannifin GmbHHydraulic Controls DivisionHydraulics

IA ET101 UK A5.PM6.5 MM

Power Amplifier for Flow ValvesSeries ET101Installation Manual

Features

• Modulated output signals to the control solenoidthrough four selectable commands and ramppotentiometers, adjustablefrom 0 to 100%.

• DIP switch from internal ramp generation toexternal ramp setting.

• Pulsed low loss amplifier power stage withsupporting constant current control for con-stant, temperature-independant, solenoidforces.

• Dither generator with applied frequency toimprove static characteristics.

• Diagnosis by means of diagnostic sockets aswell as LEDs for indicating working conditions.

Ordering CodeET 101

DesignSeries

ModuleType

ElectronicModule

Flow Valves

ValveSize

Module Type

Amplifier4 Scommand channels,

Up/Down ramps

Code Valve Sol.

00 TDA...LAF E16 to E 50 35mm00 TEA...LAF E16 to E 50 35mm

99 TDA...LAF E63 to E100 60mm99 TEA...LAF E63 to E100 60mm

Connection 31 pole male connector, DIN 41617Power supply filtered: 22-38V, unfiltered: 18–26VCommand voltage 0 to +10DC and 0 to -10VDCInput select voltage 5 to 30VDCPower required 40VAReference outputs +10VDC 10mAMax. solenoid output current 1.3A with 10V commandAmbient temperature 0 to 70°CRamps adjustable from 0 to 5sec.Shielded cable connection Supply connections + valve: AWG15

Commands: AWG20Fuse 2A medium lag, DIN 41571/5x20 mm

Characteristics

Electronic module for the control of proportionalthrottle valves. The valve opening and its changesare achieved by command and ramp poten-tiometers. The measured value (Volts) on themodule is indirectly proportional with the throttleopening or alternatively the resulting volume flowQ (l/min). )(

A

B Y

Home

Page 4: Y23_ET101

8/19/2019 Y23_ET101

http://slidepdf.com/reader/full/y23et101 4/6

4 Parker Hannifin GmbHHydraulic Controls DivisionHydraulics

IA ET101 UK A5.PM6.5 MM

Power Amplifier for Flow ValvesSeries ET101Installation Manual

Block Diagram

Connector(Elevation B) 2

1

EMC

EN 50081-2 EN 55011EN 50082-2 ENV 50140 EN 61000-4-4 ENV 50204 EN 61000-4-5 EN 61000-4-2 EN 61000-4-6

2 Input preselection channel 24 Input preselection channel 46 Input set value lock on channel 28 Input set value lock on channel 4

16 Output +10V reference18 Output 24VDC supply

22 Input external ramp option

26 Output control solenoid

1 Input preselection channel 13 Input preselection channel 35 Input set value lock on channel 17 Input set value lock on channel 3

11 Reference potential 0V supply

13 Input ramp disable

25 Output control solenoid

27 Input external ramp option

Home

Page 5: Y23_ET101

8/19/2019 Y23_ET101

http://slidepdf.com/reader/full/y23et101 5/6

5 Parker Hannifin GmbHHydraulic Controls DivisionHydraulics

IA ET101 UK A5.PM6.5 MM

Power Amplifier for Flow ValvesSeries ET101Installation Manual

Operating and Diagnostic Elements(Elevation A)

Dimensional Drawing(Eurocard)

2

6

3

7

4

8

11

9

1213

10

1415

5

1 S 1S 1

S 2

S 3

S 4

A

B

A

B

- +

0 , 1

V =

1 A

Notes:Turn off the electrical power

to this board whenever thehydraulic supply to the valveis not on.Always turn off the power tothis board before removing itfrom the card holder.

Only potential-free measuring

equipment to be used

1–4 Command potentiometersS1–S4

5–8 Green LED`s for:channel activity of the setvalues

9 Red LED (A) for:-function indicator controlsolenoid-(B not used)

10 Yellow LED for:-correct voltage supply

11 Red socket for currentdiagnostic

12 Black socket for currentdiagnostic

13 Green grip strip withreference informationfor measured values

14 UP ramp potentiometer15 DOWN ramp potentiometer

Home

Page 6: Y23_ET101

8/19/2019 Y23_ET101

http://slidepdf.com/reader/full/y23et101 6/6

6 Parker Hannifin GmbHHydraulic Controls DivisionHydraulics

IA ET101 UK A5.PM6.5 MM

Power Amplifier for Flow ValvesSeries ET101Installation Manual

INSTALLATION GUIDE TO ELECTRONIC MODULESTO PROVISION OF ELECTROMAGNETIC COMPATIBILITY.

Power Supply

The utilized power supply has to comply with the EMC-standards (CE-sign, certificate of conformity).Parker is offering the following power supplies:

EX00-N01 ( 2.5 Amp.)EX00-N04 ( 5.0 Amp.)EX00-N08 (10.0 Amp.)

Relais and solenoids operating from the same supply circuit as the valve electronics have to be fittedby surge protection elements.

Wiring Cable

The wires between the installation site of the module and the peripheral units, as power supply, valvesolenoids, command signal source have to be shielded. The following wire sizes must be reached:power supply AWG 16, other connections AWG 20. The capacity should not exceed a value of approx.130 pF/m (wire/wire). The maximum cable length is 50 m. No power current lines may be placed withinthe wired shielded cables to the electronic module. The cable shield has to be connected to groundat both ends (see also chapter „Grounding“). Please be aware of ground loops.

Installation

The module has to be mounted within a conductive, shielded enclosure. Usable is i.e. an EMC-approved control cabinet. A perfect grounding of the enclosure is mandatory (see also chapter"Grounding“).

Grounding

The mounting plate of the valve has to be connected to the grounded metal machine frame. The cableshields must be tied to ground at the control cabinet. A low-ohmic potential compensation wire hasto be provided between the control cabinet and the machine frame (cable wire >AWG 7 cross section)to prevent ground loops.