Power Quality Improvement of Incoming Supply (TNEB)
Steps planned to Improve Power Quality:
1. Install HT AVR to ensure Voltage variation within ±1%.
2. Install UPS to reduce losses due to Power Brown outs & Black
outs (M/c Breakdown, Tool Breakdown etc.).
3. Upgrade the Voltage from 11KV to 33KV.
Steps Planned to Improve Power Quality
• Failure of Motor windings in Heat Treatment Machines due to Low voltage (VHF, SQF etc.,). • Imported CNC,PLC M/c’s fails to run without coolant pump due to voltage fluctuation.
• lights are flickering and capacitors burst due to low voltage.
• Frequent tripping of Circuit breakers due to low voltage during full load.
• Frequent tripping of Air conditioner and compressors due to voltage fluctuation.
Problems occurred before installing AVR
4
AVR Installation
BeforeAfter
Incoming supply (TNEB)VCB
2
Bus bar
Tr-1 Tr-2 Tr-3 Tr-4
Load LoadLoadLoad
Tr-1 Tr-2 Tr-3 Tr-4
Load LoadLoadLoad
Bus barVCB 2
VCB 1
Incoming supply (TNEB)
6.3 MVA AVR
Additionally Inserted
5
AVR system installed
Voltage stabilization process in LT side
Input voltage to AVR : 9000V to 12000VOutput voltage from AVR : 11000V ± 1% (10890V to 11110V)
Stabilization process : HT voltage LT voltage
conventional : 9000V to 12000V 340V to 470V
Recommended : 11000V±1% 415V±6% (i.e.390V
to 440V)
By AVR : 11000V±1% 410V to 420V
7
voltage bandwidth for motors
D
GOOD
ALLOWED
DANGEROUS
410V
420V
390V
440V
340V
470V
Voltage Bandwidth
Voltage in LT before & after installation of AVRVoltage in LT side
050
100150200250300350400450500
Time
Volta
ge
Before After Required
9
After installation of AVRAvoided M/c brownouts, blackouts due to voltage
variation.
Avoided failure of Motor winding and CNC M/c down time due
to voltage fluctuation.
Avoided failure of lights and fans due to low voltage.
Avoided tripping of Air conditioner and compressors due to under voltage.
10
Up gradation of voltage from 11 KV to 33 KV
6.3 MVA AVR
33 KV TNEB SUPPLY
RMG 33 KV VCB
6.3 MVA,33KV / 11KV TRANSFORMER
11 KV VCB
VCB
VCB VCB VCB
To Power House To
DI building To E & D
11
Increasing the Capacity of UPS
Bus bar
Tr-1 Tr-2 Tr-3 Tr-4
Load LoadLoad
160 KVA
Existing
160 KVA 550 KVA 160 KVA
Load
Existing CapacityRotary = 870 KVAUPCR = 160 KVA
Planned CapacityRotary = 2360KVAUPCR = 320 KVA