Note n 1 Hypotheses Radier Alfort Fifi

36
S.E.R.F. IMMEUBLE BUREAUX ZAC D’ALFORT ILOT5 VILLE DE MAISON-ALFORT 4,rue E. Renault-Place de la Resistance HYPOTHESES DE CALCUL POUR LE RADIER CONFORME AU D.T.U 14. 1 NOTE N°- 1 - du 21/11/06 SERF - SARL - RCS. 408 196 293 RM 782 SIEGE SOCIAL: 12, RUE MATHILDE BURGUE - 95 600 EAUBONNE TEL : 01.34.17.49.19. - FAX –01.34.17.47.42 1

Transcript of Note n 1 Hypotheses Radier Alfort Fifi

Page 1: Note n 1 Hypotheses Radier Alfort Fifi

S.E.R.F.IMMEUBLE BUREAUX ZAC D’ALFORT ILOT5

VILLE DE MAISON-ALFORT4,rue E. Renault-Place de la

Resistance

HYPOTHESES DE CALCUL POUR LE RADIER CONFORME AU D.T.U 14. 1

NOTE N°- 1 - du 21/11/06

Nbr. Pg 28

SERF - SARL - RCS. 408 196 293 RM 782 SIEGE SOCIAL: 12, RUE MATHILDE BURGUE - 95 600 EAUBONNE

TEL : 01.34.17.49.19. - FAX –01.34.17.47.42

1

Page 2: Note n 1 Hypotheses Radier Alfort Fifi

S.E.R.F.

1. HYPOTESES GENERALE

1.1 Epaisseur du radier 0.50 m PB. AS = 28.84 NVP.

1.2 La fonction du radier est de reprendre la poussée hydrostatique de la nappe phréatique et de transmettre par le moyen des longrines aux pieux.

1.3 Niveaux de la nappe : EE = 33,75 NVP qw3

1.4 Le calcul est réalisé avec le niveau d’eau E = EE qui est le plus défavorable. 1.5 La caractéristique du béton utilisé pour le radier:

fc28 = 30 Mpa ft28 = 0.6 + 0.06*fc28 = 2.4 Mpa

fcj = 1.1 fc28 pour J > 60 jours fcj= 33 Mpa

t = 1.1 ft28 pour = 5/3 t=4.4 Mpa

1.6 Les caractéristiques des aciers utilisés pour les armatures du radier fe = 500 MPa seront limitées aux valeurs de la contrainte de traction a l’Etat Limite de Service. Pour le calcul à l’Etat préjudiciable d’un cuvelage à structure relative étanche au sens du DTU 14.1. art.7.3.1.1

La plus petite valeur de  :

s max= 2/3 fe ou s = *ft28/ + 30

Avec = 320 = 1.6 (HA)ou TS en mm

SERF - SARL - RCS. 408 196 293 RM 782 SIEGE SOCIAL: 12, RUE MATHILDE BURGUE - 95 600 EAUBONNE

TEL : 01.34.17.49.19. - FAX –01.34.17.47.42

2

Page 3: Note n 1 Hypotheses Radier Alfort Fifi

S.E.R.F.Deux cas ce présente :

a) Surface du radier en contacte avec l’eau :

Pour - fcj = 30 Mpa ftj = 2.4 Mpa EE = 33.75 NVP = 1.732 = 320

< HA14 fe = 333 Mpa = HA16 fe = 320 Mpa = HA20 fe = 291 Mpa = HA25 fe = 265 Mpa = HA32 fe = 240 Mpa

b) Surface recevant le revêtement d’imperméabilisation :

= HA 6 fe = 305 Mpa = HA 7 fe = 285 Mpa = HA 8 fe = 270 Mpa = HA 10 fe = 247 Mpa = HA 12 fe = 229 Mpa = HA 14 fe = 216 Mpa = HA 16 fe = 205 Mpa = HA 20 fe = 188 Mpa = HA 25 fe = 173 Mpa = HA 32 fe = 159 Mpa

1.7) Charges hydrostatiques pris en compte dans le calcul du radier :

Poussée hydrostatique en phase définitive. EE = 33.75 NVP

PB(pousse eau) ge = [33.75 – (28.84-0.5)]*1.0 = 5.41 t/m² ou 5410 daN/m²PB(poids propre) gp = 0.5*2.5 = 1.25 t/m² ou 1250daN/m²

COMB 1 = gp – ge = 1.25 - 5.41 = -4.16 t/m2 ou -4160 daN/m2

COMB 2 = gp = 1.25 t/m2 ou 1250 daN/m2

q = 0.25t/m2 ou 250 daN/m2

SERF - SARL - RCS. 408 196 293 RM 782 SIEGE SOCIAL: 12, RUE MATHILDE BURGUE - 95 600 EAUBONNE

TEL : 01.34.17.49.19. - FAX –01.34.17.47.42

3

Page 4: Note n 1 Hypotheses Radier Alfort Fifi

S.E.R.F.2. MAILLAGES DES RADIERS

SERF - SARL - RCS. 408 196 293 RM 782 SIEGE SOCIAL: 12, RUE MATHILDE BURGUE - 95 600 EAUBONNE

TEL : 01.34.17.49.19. - FAX –01.34.17.47.42

4

Page 5: Note n 1 Hypotheses Radier Alfort Fifi

S.E.R.F.3. RESULTATS DE PLAQUE

SERF - SARL - RCS. 408 196 293 RM 782 SIEGE SOCIAL: 12, RUE MATHILDE BURGUE - 95 600 EAUBONNE

TEL : 01.34.17.49.19. - FAX –01.34.17.47.42

Type de ferraillage DALLE Direction du ferraillage : automatique

Fissuration : préjudiciable

Appliquer DTU 14.1 Milieu :eau agressive, Niveau d'eau :exceptionnel, Coefficient alpha :320.00

Béton : fc28 = 30.00(MPa)

Acier HA : fe = 500.00(MPa) Diamètres des aciers inférieurs : d1 = 16.00(mm), d2 = 16.00(mm)

Diamètres des aciers supérieurs :

d1 = 16.00(mm), d2 = 16.00(mm)

Enrobage : inférieure c1 = 3.00(cm), supérieur c2 = 3.00(cm)

Type de dimenstionnement flexion simple

Distribution des armatures dans deux directions Poinçonnement et cisaillement : ne sont pas analysés

Calcul suivant : BAEL 91 mod. 99

Utilisé dans les panneaux : 228, 229, 230, 231, 232, 233, 234, 235, 236, 237, 238, 239, 240, 241, 242, 243, 244, 245, 246, 247, 248, 249, 250, 251, 252, 253, 254, 255, 256, 257, 258, 259

Type de ferraillage DIRECTION Y

Direction du ferraillage : suivant l'axe Y

Fissuration : préjudiciable

Appliquer DTU 14.1 Milieu :eau agressive, Niveau d'eau :exceptionnel, Coefficient alpha :320.00

Béton : fc28 = 30.00(MPa) Acier HA : fe = 500.00(MPa)

Diamètres des aciers inférieurs : d1 = 16.00(mm), d2 = 16.00(mm)

Diamètres des aciers supérieurs :

d1 = 16.00(mm), d2 = 16.00(mm)

Enrobage : inférieure c1 = 3.00(cm), supérieur c2 = 3.00(cm)

Type de dimenstionnement flexion simple Distribution des armatures dans deux directions

Poinçonnement et cisaillement : ne sont pas analysés

Calcul suivant : BAEL 91 mod. 99

Utilisé dans les panneaux : 260, 261, 262, 263, 264

Type de ferraillage DIRECTION X

Direction du ferraillage : suivant l'axe X

Fissuration : préjudiciable

Appliquer DTU 14.1 Milieu :eau agressive, Niveau d'eau :exceptionnel, Coefficient alpha :320.00

Béton : fc28 = 30.00(MPa) Acier HA : fe = 500.00(MPa)

Diamètres des aciers inférieurs : d1 = 16.00(mm), d2 = 16.00(mm)

Diamètres des aciers supérieurs :

d1 = 16.00(mm), d2 = 16.00(mm)

Enrobage : inférieure c1 = 3.00(cm), supérieur c2 = 3.00(cm)

Type de dimenstionnement flexion simple Distribution des armatures dans deux directions

Poinçonnement et cisaillement : ne sont pas analysés

Calcul suivant : BAEL 91 mod. 99

Utilisé dans les panneaux : 265, 266

5

Page 6: Note n 1 Hypotheses Radier Alfort Fifi

S.E.R.F.

4. MOMENTS POUR LE COMB 1

COMB 1 = gp – ge = 1.25 - 5.41 = -4.16 t/m2 ou -4160 daN/m2

SERF - SARL - RCS. 408 196 293 RM 782 SIEGE SOCIAL: 12, RUE MATHILDE BURGUE - 95 600 EAUBONNE

TEL : 01.34.17.49.19. - FAX –01.34.17.47.42

6

Page 7: Note n 1 Hypotheses Radier Alfort Fifi

S.E.R.F.Vue - MXX (Tm), (COMB1 – gp=1.25t/mp,ge=5.41t/mp)

SERF - SARL - RCS. 408 196 293 RM 782 SIEGE SOCIAL: 12, RUE MATHILDE BURGUE - 95 600 EAUBONNE

TEL : 01.34.17.49.19. - FAX –01.34.17.47.42

7

Page 8: Note n 1 Hypotheses Radier Alfort Fifi

S.E.R.F.Vue - MYY (Tm), (COMB1 – gp=1.25t/mp,ge=5.41t/mp)

SERF - SARL - RCS. 408 196 293 RM 782 SIEGE SOCIAL: 12, RUE MATHILDE BURGUE - 95 600 EAUBONNE

TEL : 01.34.17.49.19. - FAX –01.34.17.47.42

8

Page 9: Note n 1 Hypotheses Radier Alfort Fifi

S.E.R.F.Vue - MXX+, (COMB1 – gp=1.25t/mp,ge=5.41t/mp)

SERF - SARL - RCS. 408 196 293 RM 782 SIEGE SOCIAL: 12, RUE MATHILDE BURGUE - 95 600 EAUBONNE

TEL : 01.34.17.49.19. - FAX –01.34.17.47.42

9

Page 10: Note n 1 Hypotheses Radier Alfort Fifi

S.E.R.F.Vue – MXX-, (COMB1– gp=1.25t/mp,ge=5.41t/mp )

SERF - SARL - RCS. 408 196 293 RM 782 SIEGE SOCIAL: 12, RUE MATHILDE BURGUE - 95 600 EAUBONNE

TEL : 01.34.17.49.19. - FAX –01.34.17.47.42

10

Page 11: Note n 1 Hypotheses Radier Alfort Fifi

S.E.R.F.Vue - MYY+, (COMB1 – gp=1.25t/mp,ge=5.41t/mp)

SERF - SARL - RCS. 408 196 293 RM 782 SIEGE SOCIAL: 12, RUE MATHILDE BURGUE - 95 600 EAUBONNE

TEL : 01.34.17.49.19. - FAX –01.34.17.47.42

11

Page 12: Note n 1 Hypotheses Radier Alfort Fifi

S.E.R.F.Vue - MYY-, (COMB1 – gp=1.25t/mp,ge=5.41t/mp)

SERF - SARL - RCS. 408 196 293 RM 782 SIEGE SOCIAL: 12, RUE MATHILDE BURGUE - 95 600 EAUBONNE

TEL : 01.34.17.49.19. - FAX –01.34.17.47.42

12

Page 13: Note n 1 Hypotheses Radier Alfort Fifi

S.E.R.F.

5. ARMATURES POUR LE COMB 1

SERF - SARL - RCS. 408 196 293 RM 782 SIEGE SOCIAL: 12, RUE MATHILDE BURGUE - 95 600 EAUBONNE

TEL : 01.34.17.49.19. - FAX –01.34.17.47.42

13

Page 14: Note n 1 Hypotheses Radier Alfort Fifi

S.E.R.F.Vue - [+] Principal (cm2/m)

SERF - SARL - RCS. 408 196 293 RM 782 SIEGE SOCIAL: 12, RUE MATHILDE BURGUE - 95 600 EAUBONNE

TEL : 01.34.17.49.19. - FAX –01.34.17.47.42

14

Page 15: Note n 1 Hypotheses Radier Alfort Fifi

S.E.R.F.Vue - [-] Principal (cm2/m)

SERF - SARL - RCS. 408 196 293 RM 782 SIEGE SOCIAL: 12, RUE MATHILDE BURGUE - 95 600 EAUBONNE

TEL : 01.34.17.49.19. - FAX –01.34.17.47.42

15

Page 16: Note n 1 Hypotheses Radier Alfort Fifi

S.E.R.F.Vue - [+] Perpendiculaire (cm2/m)

SERF - SARL - RCS. 408 196 293 RM 782 SIEGE SOCIAL: 12, RUE MATHILDE BURGUE - 95 600 EAUBONNE

TEL : 01.34.17.49.19. - FAX –01.34.17.47.42

16

Page 17: Note n 1 Hypotheses Radier Alfort Fifi

S.E.R.F.Vue - [-] Perpendiculaire (cm2/m)

SERF - SARL - RCS. 408 196 293 RM 782 SIEGE SOCIAL: 12, RUE MATHILDE BURGUE - 95 600 EAUBONNE

TEL : 01.34.17.49.19. - FAX –01.34.17.47.42

17

Page 18: Note n 1 Hypotheses Radier Alfort Fifi

S.E.R.F.

6. CONTRAINTES POUR LE COMB 1

SERF - SARL - RCS. 408 196 293 RM 782 SIEGE SOCIAL: 12, RUE MATHILDE BURGUE - 95 600 EAUBONNE

TEL : 01.34.17.49.19. - FAX –01.34.17.47.42

18

Page 19: Note n 1 Hypotheses Radier Alfort Fifi

S.E.R.F.Vue – Contraintes SYY (MPa) COMB1

SERF - SARL - RCS. 408 196 293 RM 782 SIEGE SOCIAL: 12, RUE MATHILDE BURGUE - 95 600 EAUBONNE

TEL : 01.34.17.49.19. - FAX –01.34.17.47.42

19

Page 20: Note n 1 Hypotheses Radier Alfort Fifi

S.E.R.F.Vue – Contraintes SXX (MPa) COMB1

SERF - SARL - RCS. 408 196 293 RM 782 SIEGE SOCIAL: 12, RUE MATHILDE BURGUE - 95 600 EAUBONNE

TEL : 01.34.17.49.19. - FAX –01.34.17.47.42

20

Page 21: Note n 1 Hypotheses Radier Alfort Fifi

S.E.R.F.

7. MOMENTS POUR LE COMB 2

gp = 1.25 t/m2 ou 1250 daN/m2

q = 0.25 t/m2 ou 250 daN/m2

COMB 2 - gpx1.35 + qx1.50

SERF - SARL - RCS. 408 196 293 RM 782 SIEGE SOCIAL: 12, RUE MATHILDE BURGUE - 95 600 EAUBONNE

TEL : 01.34.17.49.19. - FAX –01.34.17.47.42

21

Page 22: Note n 1 Hypotheses Radier Alfort Fifi

S.E.R.F.Vue - MYY-, (COMB2)

Vue - MYY+, (COMB2) SERF - SARL - RCS. 408 196 293 RM 782

SIEGE SOCIAL: 12, RUE MATHILDE BURGUE - 95 600 EAUBONNETEL : 01.34.17.49.19. - FAX –01.34.17.47.42

22

Page 23: Note n 1 Hypotheses Radier Alfort Fifi

S.E.R.F.

Vue – MXX-, (COMB2)

SERF - SARL - RCS. 408 196 293 RM 782 SIEGE SOCIAL: 12, RUE MATHILDE BURGUE - 95 600 EAUBONNE

TEL : 01.34.17.49.19. - FAX –01.34.17.47.42

23

Page 24: Note n 1 Hypotheses Radier Alfort Fifi

S.E.R.F.

Vue - MXX+, (COMB2)

SERF - SARL - RCS. 408 196 293 RM 782 SIEGE SOCIAL: 12, RUE MATHILDE BURGUE - 95 600 EAUBONNE

TEL : 01.34.17.49.19. - FAX –01.34.17.47.42

24

Page 25: Note n 1 Hypotheses Radier Alfort Fifi

S.E.R.F.

SERF - SARL - RCS. 408 196 293 RM 782 SIEGE SOCIAL: 12, RUE MATHILDE BURGUE - 95 600 EAUBONNE

TEL : 01.34.17.49.19. - FAX –01.34.17.47.42

25

Page 26: Note n 1 Hypotheses Radier Alfort Fifi

S.E.R.F.

8. CONTRAINTES POUR LE COMB 2

SERF - SARL - RCS. 408 196 293 RM 782 SIEGE SOCIAL: 12, RUE MATHILDE BURGUE - 95 600 EAUBONNE

TEL : 01.34.17.49.19. - FAX –01.34.17.47.42

26

Page 27: Note n 1 Hypotheses Radier Alfort Fifi

S.E.R.F.Vue – Contraintes SYY (MPa) COMB2

SERF - SARL - RCS. 408 196 293 RM 782 SIEGE SOCIAL: 12, RUE MATHILDE BURGUE - 95 600 EAUBONNE

TEL : 01.34.17.49.19. - FAX –01.34.17.47.42

27

Page 28: Note n 1 Hypotheses Radier Alfort Fifi

S.E.R.F.Vue – Contraintes SXX (MPa) COMB2

SERF - SARL - RCS. 408 196 293 RM 782 SIEGE SOCIAL: 12, RUE MATHILDE BURGUE - 95 600 EAUBONNE

TEL : 01.34.17.49.19. - FAX –01.34.17.47.42

28