Design and maintenance of safety shower installations · recommendations were published in a...

16
CIB W062 Symposium 2005 1 Design and maintenance of safety shower installations Ing. O.W.W. Nuijten (1) [email protected] ISSO, Sanitary and Gas installations, The Netherlands, Rotterdam Ir. J. van Wolferen (2) [email protected] TNO-MEP, The Netherlands, Apeldoorn Ing. J.A.G.M Wittens (3) [email protected] Avans Hogeschool, The Netherlands, Den Bosch Abstract The law and regulations in various countries make demands on the application of safety or emergency showers and eye/facewash equipment. Large companies or industries often have their own guidelines. In The Netherlands, the regulations and requirements for these showers are described very globally. For almost every project, the designer has to find answers to a lot of questions. Probably the situation in other countries is comparable to that of The Netherlands. The designer, in his search for answers, has to cope with questions like: What type of safety shower do I have to use in certain situations? Where can I find guidelines and standards? Can I use the American, DIN or other standards? What microbiological water quality is needed? What water temperature is required? How can I connect these to the (potable) water system? What are the design flow rates and design pressures? How can I heat the required flow rate to the required temperature during the required flushing time? What about maintenance and testing? That is why Uneto-VNI and TVVL took the initiative for a preliminary study. The results of this study have to lead to more detailed regulations and technical guidelines for

Transcript of Design and maintenance of safety shower installations · recommendations were published in a...

Page 1: Design and maintenance of safety shower installations · recommendations were published in a technical TVVL-report, ST-11 [1]. In 2004 and 2005, Hans Wittens (3) carried out a complete

CIB W062 Symposium 2005

1

Design and maintenance of safety shower installations Ing. O.W.W. Nuijten (1) [email protected] ISSO, Sanitary and Gas installations, The Netherlands, Rotterdam Ir. J. van Wolferen (2) [email protected] TNO-MEP, The Netherlands, Apeldoorn Ing. J.A.G.M Wittens (3) [email protected] Avans Hogeschool, The Netherlands, Den Bosch

Abstract

The law and regulations in various countries make demands on the application of safety or emergency showers and eye/facewash equipment. Large companies or industries often have their own guidelines. In The Netherlands, the regulations and requirements for these showers are described very globally. For almost every project, the designer has to find answers to a lot of questions. Probably the situation in other countries is comparable to that of The Netherlands. The designer, in his search for answers, has to cope with questions like:

What type of safety shower do I have to use in certain situations? Where can I find guidelines and standards? Can I use the American, DIN or other standards? What microbiological water quality is needed? What water temperature is required? How can I connect these to the (potable) water system? What are the design flow rates and design pressures? How can I heat the required flow rate to the required temperature during the

required flushing time? What about maintenance and testing?

That is why Uneto-VNI and TVVL took the initiative for a preliminary study. The results of this study have to lead to more detailed regulations and technical guidelines for

Page 2: Design and maintenance of safety shower installations · recommendations were published in a technical TVVL-report, ST-11 [1]. In 2004 and 2005, Hans Wittens (3) carried out a complete

CIB W062 Symposium 2005

2

design and maintenance of watersupplysystems for emergency shower, drench hoses and eye/facewash equipment. The literature study was carried out by Hans Van Wolferen (2) and the results and recommendations were published in a technical TVVL-report, ST-11 [1].

In 2004 and 2005, Hans Wittens (3) carried out a complete investigation on the recommendations in ST-11 with the purpose to advise about detailed regulations and technical guidelines that are acceptable to the government of the Netherlands and other parties involved. That resulted in technical TVVL-report ST-16 [2].

Keywords

Emergency shower, safety shower, eye/face wash, drench hose, potable water, tepid water, Legionella, process water, flushing, flow rate, simultaneously, flow pressure, duration of use, maintenance, testing, employees, victim, burns, medical expert, chemical, microbiological..

1 Introduction

The investigation has three phases: 1. Phase of preliminary investigation:

- Study of technical report ST-11 [1] 2. Phase of analysis:

- Interviews with various experts in the field of legislation on this matter - Formulating of thesises (questions) - Presenting these thesises to a large forum of experts and discuss these.

3. Phase of recommendations

- Working out proposals for guidelines 2 The research

2.1 The organization of the research

2.1.1 Preliminary study The literature study (ST-11) has provided a clear image of rules, guidelines and standards that are valid for the above mentioned equipment and installations in the USA (ANSI), Germany (DIN) and The Netherlands (Legislation and guidelines on working conditions and potable water supply).

Page 3: Design and maintenance of safety shower installations · recommendations were published in a technical TVVL-report, ST-11 [1]. In 2004 and 2005, Hans Wittens (3) carried out a complete

CIB W062 Symposium 2005

3

In this phase, experts were interviewed based on the results of literature study ST-11 .[1]. Out of these interviews a table with a survey was developped. (see par. 2.2.1). 2.1.2 Phase of analysis Questions of investigation From the missing answers out of the preliminary study, questions of investigation were formulated: 1. Are the Dutch ARBO-policy instructions (concerning working conditions)

sufficient for watersupply installations that are feeding plumbed emergency equipment?

2. Which requirements have to be met with the waterquality in watersupply installations that are feeding plumbed emergency equipment and under which condiotions is it allowed to use process water for this purpose?

3. Which guidelines can be recommended for the: - watertemperature, - design flowrate, - flow pressure - time of use - testing and maintenance - prevention of Legionella risk?

4. Which factors of simultaneity have to be used for the sizing of watersupply lines that are feeding combined installations for sanitary purpose, fire-hose spools and safetyshowers.

Interviews Interviews were held with experts of:

- Dutch Ministry of Social Affairs and Employment (SZW) and their department of Labour / Factory Inspection (AI)

- Netherlands Ministry of Housing, Spatial Planning and Environment (VROM) - KIWA, Certification Institute - RIVM, National Institute for Public Health and Environment

From the results of the interviews a list of items was developed. Thesises Thesises were formulated arising from the results of the interviews with the experts. Those thesises were presented to a forum of experts of the most important parties involved in this matter. That’s what made it possible to reach consensus and give a solid basis to the recommendations for uniform guidelines in The Netherlands. The forum of experts

Page 4: Design and maintenance of safety shower installations · recommendations were published in a technical TVVL-report, ST-11 [1]. In 2004 and 2005, Hans Wittens (3) carried out a complete

CIB W062 Symposium 2005

4

could not agree upon all propositions. The persons present, advised to give the medical experts the last word on these subjects. 2.1.3 Phase of recommendations In this phase recommendations were given for Dutch guidelines (VEWIN [4], ISSO 55 [5]) and policy instructions for Legionella prevention (ARBO) concerning design and maintenance of potable water installations for plumbed emergency equipment. 2.2 Results 2.2.1 Preliminary study The results from literaturestudy ST-11..[1] and comparison between German [8], American [9] and Dutch legislation, standards and guidelines are summarized in tables 1 to 10.

Table 1 – Microbiological and chemical waterquality Type of safetyshower DIN ANSI NL-Leg. or Std’s Emergencyshower (body) potable(1) potable potable (2) Eyewash potable(1) potable potable (2) Facewash potable(1) potable potable (2) Hand held drench hose potable(1) potable potable (2) (1) Potable water or water with equal quality for this purpose (This does not need to comply with hall the microbiological requirements of potable water) (2) Connected to (public) waterdistributionsystem

Table 2 – Water temperature

Type of safetyshower DIN ANSI NL-Leg. or Std’s [oC] [oC] [oC] Emergencyshower (body) - >15 - Eyewash - >15 - Facewash - >15 - Hand held drench hose - >15 -

Table 3 – Measures against freezing

Type of safetyshower DIN ANSI NL-Leg. or Std’s Emergencyshower (body) - yes - Eyewash - yes - Facewash - yes - Hand held drench hose - yes -

Table 4 – Minimum flowrate

Type of safetyshower DIN ANSI NL-Leg. or Std’s [l/min] [l/min] [l/min] Emergencyshower (body) - all types 76 80 - for laboraties 30 - - - industry&outside single showerhead - industry&outside multiple showerh.

30 100

- -

- -

Eyewash 12 3 - Facewash 24 11,4 - Hand held drench hose 10 - -

Page 5: Design and maintenance of safety shower installations · recommendations were published in a technical TVVL-report, ST-11 [1]. In 2004 and 2005, Hans Wittens (3) carried out a complete

CIB W062 Symposium 2005

5

Table 5 – Minimum operating time Type of safetyshower DIN ANSI NL-Leg. or Std’s [min.] [min.] [min.] Emergencyshower (body) - all types - for laboraties - industry & outside

-

30

15

-

Eyewash - 15 - Facewash - 15 - Hand held drench hose - 15 -

Table 6 – Minimum pressure

Type of safetyshower DIN ANSI NL-Leg. or Std’s [kPa] [kPa] [kPa] Emergencyshower (body) 100 200 - Eyewash 100 - - Facewash 100 - - Hand held drench hose 100 - -

Table 7 – Testing of functioning

Type of safetyshower DIN ANSI NL-Leg. or Std’s Emergencyshower (body) - weekly - Eyewash - weekly - Facewash - weekly - Hand held drench hose - weekly -

Table 8 – Maintenance of watersupply

Type of safetyshower DIN ANSI NL-Leg. or Std’s Emergencyshower (body) - annually - annually(3) Eyewash - annually - annually(3) Facewash - annually - annually(3) Hand held drench hose - annually - annually(3) (3) According Dutch regulations for potable water installations [5]

Table 9 – Connection to watersupplylines

Type of safetyshower DIN ANSI NL-Leg. or Std’s Emergencyshower (body) - yes(4) - Eyewash - - Facewash - - Hand held drench hose - - (4): Valves for maintenance are not allowed to be closed unauthorized..

Table 10 – Sizing of watersupplylines

Type of safetyshower DIN ANSI NL-Leg. or Std’s Emergencyshower (body) yes(5) Eyewash yes(5) Facewash yes(5) Hand held drench hose yes(5) (5) At combination of more showers the flowrate must be sufficient for simultaneous use.

Page 6: Design and maintenance of safety shower installations · recommendations were published in a technical TVVL-report, ST-11 [1]. In 2004 and 2005, Hans Wittens (3) carried out a complete

CIB W062 Symposium 2005

6

Emergency shower

Handheld drench hose

Eyewash

Facewash

Figure 1 – Examples of plumbed safety equipment

Page 7: Design and maintenance of safety shower installations · recommendations were published in a technical TVVL-report, ST-11 [1]. In 2004 and 2005, Hans Wittens (3) carried out a complete

CIB W062 Symposium 2005

7

2.2.2 Analysis Microbiological and chemical waterquality In general, one agrees upon the demand that for emergency showers potable water is needed or water of equal quality. But what is “equal quality” in this case? In the Netherlands potable water delivered to users has to comply to very strict demands on the (microbiological and chemical) quality. Medical experts state that in water for use with emergency showers:

- the concentration of van Pseudomonas aeruginosa at 22 ºC < 100 cfu/ml (geometric year mean value).

- Ill-making micro-organismes of faecale origin are not allowed under any circumstance.

- Acanth-amoebe = 0 cfu/ml. In water dissolved pipeline material or other small particles are normally no problem for emergency showers. That is why it is basically allowed to use “dead” turbid water for this purpose. For eye-- and face wash, turbid water is not wanted. Table 11 shows the recommended minimum quality of water for emergency showers and eye-/facewash and the frequency of analysis. Table 11 – Recommended minimum biological and chemical waterquality for use

with safetyshowers (RIVM, ir. Ans Versteegh) Parameter Maximum value Analyse-frequency per year Pseudomonas Aeruginosa 100 cfu/100 ml 2 Acanthamoebe 0 cfu/100 ml 2 Nitrite 0,1 mg/l 2 Ammonium 0,2 mg/l 2 Bacteriës Coli 0 cfu/100 ml 4 Colonynumber 22 oC 100 cfu/ml 2 pH 7,0<pH<9,5 2 Oxigen >2 mg/l 2 Smell No change 2 Troublinggrade < 4 FTE 2 Legionella: Legionella can grow in the waterinstallation. When an emergency shower or eye/facewash is used in case of an accident, it is a matter of very incidental exposure. A good advice is to analyse the water at the showerhead after use. Use of process water in laboratoria: In laboratories, one often sees a (limited) potable water installation for sanitary purpose and a process water installation for the equipment in the laboraty. This laboratory installation can be fed with potable water. In the connection there must be a break unit.with a pump or an equal backflowprevention device. After this break the potable water has become process water, as defined in NL (see figure 2A)

Page 8: Design and maintenance of safety shower installations · recommendations were published in a technical TVVL-report, ST-11 [1]. In 2004 and 2005, Hans Wittens (3) carried out a complete

CIB W062 Symposium 2005

8

The forum of experts concluded that it is required to frequently analyse the water according a certain simplified measurement program, if the emergency shower equipment is connected to a process water installation. Backflow prevention: When emergency showers are connected to the process water installation in a laboraty, it is possible that the supplied water gets polluted as a result of backflow from the connected laboraty equipment The forum of experts concluded that the emergy showers must be connected to the potable water system if there is a chance of microbiological contamination (see figure 2A). This is also preferred if there is a chance of chemical contamination, but an alternative can be the mounting of individual backflow preventors at each wateroutlet, combined with regular testing and maintenance of these devices (see figure 2B).

Emergency-equipment connected to potable water

Emergency-equipment connected to process water

Figure 2 – Process water installations with emergency showers

Page 9: Design and maintenance of safety shower installations · recommendations were published in a technical TVVL-report, ST-11 [1]. In 2004 and 2005, Hans Wittens (3) carried out a complete

CIB W062 Symposium 2005

9

Watertemperature The watertemperature is important to prevent undercooling, damage or acceleration of chemical reactions. When the water suplied has to be cooled or heated it can have considerable effect on the installation (and costs). Too cold:

For emergyshowers a watertemperature of < 15 °C in the first tens of seconds is no problem. But after a longer time undercooling can occur.

For an eyewash flushing with water < 20 °C is so unpleasant that the victim cannot hold on the flushing long.

Water with temperatures < 5 °C can even cause a temperatureshock. Too warm: In some cases, a too high temperatures can occur. For emergency showers 20-25 °C is ideal.

Temperatures > 38 °C are harmful. For eye-/facewash the maximum is 30 °C. ANSI Z 358 [8] says that when chemical reactions can be accelerated, a medical

expert has to be consulted to advise about the temperature limit. The forum of experts indicates that the temperature that are given by the medical experts requirements have to be used in the guidelines. Information is asked from prof. Boeckx (burnwound specialist, of hospital AZM in Maastricht). Based on consultation of literature and college,s he advises as follows:

Emergency shower for all burn wounds (also chemical): > 15 °C Facewash: > 15°C Eyewash: > 25°C

Minimum flowrate Rules in the Netherlands:

The only rule in the Netherlands is that the minimum flowrate of an emergency shower has to be 80 l/min.

Rules in Germany and the USA:

The German standard DIN 12 899 and American standard ANSI Z 358 are different. (see table 4).

The German standard mentiones a minimum flowrate of 30 l/min for an emergency shower in a laboratory.

For eyewash and facewashequipment the demands are also quite different (see table 4)

Duration of use

ANSI mentions a possible duration of use of 15 minutes. DIN does not mentione a duration of use in laboraties, but it mentions 30

minutes for emergencyshowers that are placed outside (industry) The Dutch Brandwonden Stichting from Beverwijk (David Mackie) mentions a

time of at least 10 minuten for cooling fire burns. For cooling of chemical burns a time of 60 minutes is mentioned.

Page 10: Design and maintenance of safety shower installations · recommendations were published in a technical TVVL-report, ST-11 [1]. In 2004 and 2005, Hans Wittens (3) carried out a complete

CIB W062 Symposium 2005

10

Flow pressure Flow rates are related to a certain flow pressures at the showerhead. ANSI prescribes a minimum flow pressure of 200 kPa, and DIN 100 kPa. ANSI mentiones also a maximum pressure of 550 kPa above which one has to take care for a too strong waterstream that can injure the victim. The forum of experts advises a minimum flow pressure of 100 kPa. At higher pressures than 300 kPa the pressure has to b e reduced on indication of the manufacturer, to maintain the proper spraypattern and to prevent a to strong waterstream. Testing and maintenance The literaturestudy ST-11 says that maintenance and testfrequency of emergencyshowers depend on the conditions at their location. Dirt, soot and chemicals can affect and cover operating devices and sprayheads. showerheads. .

Under such dirty circumstances weekly or monthly inspection is required. In a clean outside location once per month or three month will do. In a laboraty with clean air and other inside locations once per three month or

once per year is okay. The maintenance frequency has to be determined after an Analysis of the circumstances.

The functional testing of an emergency shower consists of a short flushing action.

Maintenance has to be according manufacturers instructions. Legionella risk There is a distinction between the following risks:

1. infection of the victim and helper by using the emergency shower or eye/facewash

2. infection of the maintenance personnel while testing the equipment. 3. contamination of the potable water supply lines, that are feeding sanitary

showers and other spray forming wateroutlets. Ad 1. Because there is only a very incidental exposure at a possible infected waterspray the chance of infection of the victim and helper is small.

Dutch guidelines tell: “The use of the emergencysystem always prevails above infection or contamination with Legionella”.

The victim and his physician can be informed about the possible effects of Legionella, so they can recognize infection before it is too late.

Page 11: Design and maintenance of safety shower installations · recommendations were published in a technical TVVL-report, ST-11 [1]. In 2004 and 2005, Hans Wittens (3) carried out a complete

CIB W062 Symposium 2005

11

Ad 2. When emergencyshowers are frequently tested the duration of exposure is longer. In this case:

the watersupply installation has to be kept free of Legionella or the maintenance personnel has to take protective measures so they cannot inhale

aerosoles.

Figure 3 – Legionella-safe testing of emergency shower Ad 3. Contamination of the watersupplysystem due to emergency showers can be prevented with the measures shown in figure 4, in case of roomtemperatures < 25 oC.

Figure 4 – Four ways to connect emergency showers “Legionellasafe” to watersupplylines

. .

Watersupplyline with flow

Legionella-

safe

Legionella-

safe at

weekly

flushing

Legionella-

safe

Legionella-

safe at

weekly

flushing or

yearly check

of seal.

. .

Watersupplyline with flow

Legionella-

safe

Legionella-

safe at

weekly

flushing

Legionella-

safe

Legionella-

safe at

weekly

flushing or

yearly check

of seal. = 0,15 m

1 2 3 4

Page 12: Design and maintenance of safety shower installations · recommendations were published in a technical TVVL-report, ST-11 [1]. In 2004 and 2005, Hans Wittens (3) carried out a complete

CIB W062 Symposium 2005

12

Sizing (capacity) of watersupplylines: During the use of an emergency shower, the flow in the rest of the potable water system is maintained. Sometimes there are circumstances that even a firehose spool has to be used simultaneaously. For the calculation of the design flowrate of a potable water system with plumbed emergy equipment, the following formulas are applied in The Netherlands:

If qmmd ≤ qlim then qmmc = qe + f * qmmd If qmmd > qlim then qmmc = qmmd

In which: qmmc = maximum moment flowrate of combined potable water and emergency

installation. [l/s]

qmmd = maximum moment flowrate of the potable water installation. [l/s] qlim = limited flowrate = qe / (1 – f) [l/s] qe = maximum moment flowrate of emergencyinstallation [l/s] f = Factor of simultaneity for qmmc and qmmd [-] In Dutch guidelines there is given that factor f = 0,7. That is rather large. For example if qmmc is only for sanitary use than this flowrate will only be reached very occasionally. A lower value of factor f may be justified depending on circumstances. Other values could be used based on an analysis of the use of the waterinstallation, for example f = 0,25, f = 0,50 or f = 0,75. If more plumbed emergency equipment is connected to the watersupplyline in the building, then simultaneous use of the differenent showers, eyewash and firehose spools has to be taken into account. The following can be of influence on the simultaneity of different and/or more emergency-equipments: - possibility of more victims at the same time; - possibility of fire in the building and fire burn wounds at the same time; - the amount of emergency equipments; - the lay out, purpose and size of the building. The forum of experts advises that a risk analysis has to be made under the responsibility of the customer. The results of this risk analysis has to give information about the location/type/sizes of emergency-equipments and their simultaneous use. The results have to be included in the specifications of the building installations.

Page 13: Design and maintenance of safety shower installations · recommendations were published in a technical TVVL-report, ST-11 [1]. In 2004 and 2005, Hans Wittens (3) carried out a complete

CIB W062 Symposium 2005

13

3 Conclusions and recommendations In this paragraph the results of the investigation are presented with a summary of the answers to the four questions of investigation and proposed guidelines for design and maintenance of safety shower installations in The Netherlands. 3.1 Answers and proposed guidelines 1. Are the Dutch ARBO-policy instructions (concerning working conditions) sufficient

for watersupply installations that are feeding plumbed emergency equipment?

Answer: No Motivation: ARBO-policy instruction 4.4-5 prescribes that an emergency shower installation

has to be connected to a potable water installation.This instruction does not mention the possibility to use process water of equal quality for this purpose.

In the ARBO-policy instruction no requirements are prescribed for the watertemperatures and duration of use.

The ARBO-policy instruction does not make a distinction between design flowrates of emergency showers depending on sorts of danger.

The ARBO-policy instruction does mention the possibity of simulteneous use of emergency-equipment.

2. Which requirements have to be met with the chemical and biological quality in

watersupply installations that are feeding plumbed emergency equipment and under which condiotions is it allowed to use process water for this purpose?

Answer: When connected to a (public) potable watersupply system there are no extra

requirements. When connected to a process water installation there are extra requirements.

Proposed guidelinesL:

It is preferred that plumbed emergency equipment is connected to a potable water system that complies with Dutch legislation..

Eye- and facewash must be connected to a potable water line in which there is regular flow to keep the water fresh.

In microbiological laboraties the emergency equipment shall NOT be connected to the processwater installation.

In chemical laboraties it is advised not to connect emergency equipment to the process water installation.

When connected to a process water installation the quality should be monitored by a simplified measuring programm (table 11).

When connected to a process water installation in a chemical laboratory, the wateroutlets to the laboraty equipment shoud be equipped with indiviual backflowpreventors (fig. 2B). The functioning of these devices should be checked annualy.

Emergengy equipment, connected to process water, must have a warning “Non- potable water”

An (extra) measure can be to analyse the water on Legionella after use of the equipment by a victim and helper.

Page 14: Design and maintenance of safety shower installations · recommendations were published in a technical TVVL-report, ST-11 [1]. In 2004 and 2005, Hans Wittens (3) carried out a complete

CIB W062 Symposium 2005

14

Continuation of answers and proposed guidelines

3. Which guidelines can be given for the: watertemperature design flowrate flow pressure time of use testing and maintenance prevention of Legionella?

Answer:

The guidelines concerning watertemperature, design flowrates, flowpressure and duration of use in The Netherlands are given in table 12.

For prevention of Legionella contamination of the watersupply system use ISSO-publication 55.1 [6] or 55.2. [7] (see also fig. 4).

4. Which factors of simultaneity have to used for the sizing of watersupply lines that are feeding combined installations for sanitary, fire-hose spools and safetyshowers.

Answer: At first a riskanalysis about the quantity, place, and simultaneity of the

emergency equipment has to be made under the responsibility of the customer.

For understanding about simultaneity and the sizing of the watersupplylines see also par. 2.2.2, subject Sizing (capacity) of watersupplylines:

Proposed guidelines:

In chemical laboraties (also in schools) an emergency shower and eyewash have to be installed and it must be possible to use these simultaneously.

Calculate the flowrate in combined installations according the general formula.with a factor for simultaneity.

In combined installations with normal sanitary use.a standard value f = 0,25 can be used for the watersupplyline at the watermeter.

In other situations, for example with continuous flows, and in other downflow linesections, the factor f has to be determined by an analysis.

Page 15: Design and maintenance of safety shower installations · recommendations were published in a technical TVVL-report, ST-11 [1]. In 2004 and 2005, Hans Wittens (3) carried out a complete

CIB W062 Symposium 2005

15

Table 12 – Proposed guidelines for minimum flowrates, temperatures, duration of

use and flowpressure q

[l/min] θmin [ºC]

tuse [min]

pmin [kPa]

Remarks

Eye wash 12 25 10 100 2 heads at 6 l/min. Face wash 24 15 10 100 4 heads at 6 l/min. Emergency shower I

30 15 10 100 For fire burns in for example a kitchen in a restaurant

30 15 20 100 For chemical burns at small stores of chemical goods or (school) laboratories

Emergency shower II

80 15 20 100 For chemical burns at large stores of chemical goods and chemical industry.

The selection of a 30 or 80 l/min shower must be the result of a riskanalysis. The flowrate and spraypattern and sprayvelocity have to be in compliance with the

flowpressure specified by the manufacturer. For reasons of Legionellaprevention the maximum temperature can be limited to max. 25

°C. For prevention of eyedamage the max. temperature at an eye wash = 30 °C. For prevention of skindamage the max. temperature at a shower and face wash = 35 °C.

Page 16: Design and maintenance of safety shower installations · recommendations were published in a technical TVVL-report, ST-11 [1]. In 2004 and 2005, Hans Wittens (3) carried out a complete

CIB W062 Symposium 2005

16

4 References

1. TVVL Technical report ST-11 , Literature study “Emergency showers” (see www.tvvl.nl)

Ir. J. van Wolferen 2003

2. TVVL Technical report ST-16, Recommandations for guidelines concerning design & maintenance of watersupply installations for emergency equipment in the Netherlands (see www.tvvl.nl)

Ing. J. Wittens 2005

3. NEN 1006, Regulations for potable water installations (see www.nen.nl)

NEN, Delft 2002

4. VEWIN Werkbladen, Guidelines to NEN 1006

VEWIN, Rijswijk 2004

5. ISSO-publication 55, Tapwaterinstallations in residential and public buildings (see www.isso.nl)

ISSO 2001

6. ISSO-publication 55.1, Guidelines for Legionellaprevention in high risk potable water systems (see www.isso.nl)

ISSO 2005

7. ISSO-publication 55.2, Guidelines for Legionellaprevention in collective potable water systems (see www.isso.nl)

ISSO 2005

8. ANSI Z358.1, American National Standard for Emergency Eyewash and Shower Equipment

ISEA 1998

9 DIN 12 899, Laboratory installations, emergency shower installations, body showers, safety Requirements, Tests, Part 1 and 2.

Beuth Verlag 1990

5 Presentation of Author

Oscar Nuijten is currently working as a project coordinator with ISSO (knowledge centre for building services) in Rotterdam, The Netherlands), where he is responsible for the realisation of technical publications in the field of sanitary and gas installations.