Octobre 08
BBooîîttiieerrdd’’AAuuttoommaattiissmmee
Réf. 261 93 – Réf. 261 94
Y1958C
Table des matieres
3
1. Caractéristiques générales . . . . . . . . . . 41.1 Versions . . . . . . . . . . . . . . . . . . . . . . . . . . 41.2 Description . . . . . . . . . . . . . . . . . . . . . . . . 41.3 Applications . . . . . . . . . . . . . . . . . . . . . . . 41.4 Installation . . . . . . . . . . . . . . . . . . . . . . . . . 41.5 Alimentation . . . . . . . . . . . . . . . . . . . . . . . . 4
2. Description de la façade . . . . . . . . . . . . 52.1 Touches de sélection . . . . . . . . . . . . . . . . . . 52.2 Sélection mesures . . . . . . . . . . . . . . . . . . . 62.3 Indicateurs à diodes . . . . . . . . . . . . . . . . . . 6
3. Modes de fonctionnement . . . . . . . . . . . 83.1 Mode reset (voyant touche RESET rouge) . . . . 83.2 Mode manuelle (voyant touche MAN rouge) . 93.3 Mode automatique (voyant touche AUT rouge) . 93.4 Mode test off-load (hors-charge) . . . . . . . . . . . 93.5 Mode test on-load (en charge) . . . . . . . . . . . 9
4. Applications . . . . . . . . . . . . . . . . . . . . . . 104.1 Application Secteur-Groupe . . . . . . . . . . . . . 104.2 Application Secteur-Secteur . . . . . . . . . . . . . . 10
5. Commande appareils . . . . . . . . . . . . . . 115.1 Avec feedback . . . . . . . . . . . . . . . . . . . . . 115.2 Sans feedback . . . . . . . . . . . . . . . . . . . . . 12
6. Contrôles de tension . . . . . . . . . . . . . . . 13
7. Programmation . . . . . . . . . . . . . . . . . . . 157.1 Programmation des paramètres . . . . . . . . . . . 157.2 Tableau des menus . . . . . . . . . . . . . . . . . . . 167.3 Menu P0 - Données nominale . . . . . . . . . . . . 167.4 Menu P1 - Données générales . . . . . . . . . . . 177.5 Menu P2 - Contrôle tension ligne principale . . 187.6 Menu P3 - Contrôle tension ligne secondaire . . 197.7 Menu P4 - Entrées programmables . . . . . . . . . 207.8 Menu P5 - Sorties programmables . . . . . . . . 207.9 Menu P6 - Communication série . . . . . . . . . . 21
8. Messages de diagnostic . . . . . . . . . . . . . 22
9. Alarmes . . . . . . . . . . . . . . . . . . . . . . . . . 23
10. Branchements . . . . . . . . . . . . . . . . . . . . 25
11. Caractéristiques techniques . . . . . . . . . . 26
1. Caractéristiques générales
4
1.1 Versions• 261 93 - Version standard • 261 94 - Version évoluée + interface RS-485
1.2 Description• Commutateur automatique de secteur à micro-
processeur• Deux entrées de mesure de tensions triphasées• Alimentation CC 12-24-48 Vcc• Alimentation CA 220-240 Vca• 2 moniteurs à diodes, 3 chiffres de 7 segments • 20 diodes de visualisation états et mesures
• Clavier à membrane à 8 touches• Sortie série RS-232 (contrôle à distance et super-
vision)• Sortie RS-485 isolée pour protocole MODBUS
(261 94)• 2 entrées TOR (tout ou rien) programmables • 3 sorties à relais (1 NO + 2 NO/NF) program-
mables
1.3 Applications• Commutation entre ligne-ligne et ligne-groupe
électrogène• Commande des appareils motorisés • Marche/arrêt groupe électrogène• Relevé tensions sur lignes triphasés, biphasés ou
monophasés
• Relevé tensions phase-phase (ou sur les tensionsphase-neutre dans le cas des lignes monophasés)
• Contrôles de tension minimum, de tension maxi-mum, d’absence de phase, d’asymétrie, de fré-quence minimum et de fréquence maximum avecvalidation et retard indépendants
• Seuil de tension avec hystérésis programmable
1.4 Installation• Installer l’appareil en suivant les schémas de bran-
chement (voir dernières pages du manuel) • Utiliser le schéma de branchement correspondant
à l’application
• Programmer les paramètres en fonction du sché-ma de branchement adopté, en faisant particu-lièrement attention à la programmation desentrées/sorties
1.5 Alimentation• 261 93 et 261 94 ont un double circuit d’ali-
mentation ; ils peuvent être alimentés en CA etCC en même temps, ou seulement en CA ou enCC indifféremment
• Quand le boîtier est alimenté en CA et CC enmême temps, l’énergie est prélevé en CA
2. Description de la façade
5
• La façade du boîtier dispose de deux afficheurs àdiodes pour indiquer les tensions des deuxsources d’alimentation avec les deux touches cor-respondantes: ligne principale (A) et ligne secon-daire (B) pour la sélection des mesures.
• Quatre touches SET (E) - AUT (F) - MAN (G) - RESET(H) permettent de sélectionner la mode de fonction-nement indiquée par le voyant correspondant.
• Au centre la façade est représenté un synoptiquequi indique l’état des appareils pour la connexionde la charge.
• Deux boutons (C) et (D) permettent d’ouvrir/fermerles appareils (boutons actifs uniquement aprèsavoir appuyé sur la touche MAN).
2.1 Touches de sélection
A B
E
F
G
H
C D
6
• En appuyant à plusieurs reprises sur la touche situéesous chaque moniteur (A) et (B), il est possible devisualiser successivement les différentes mesures de laligne correspondante.
• Pour chaque ligne, sont disponibles les tensionsphase-phase et les tensions phase-neutre (en pré-sence de ligne monophasée).
• Les combinaisons des diodes rouges indiquent lesmesures sélectionnées. La liste des mesures varieselon que l’appareil est configuré pour le contrôletriphasé, biphasé ou monophasé.
• Au bout de 1 minute sans que la touche ait étéenfoncée, est rétablie la mesure par défaut quipeut être la première tension phase-phase ou lapremière tension phase-neutre en fonction de laconfiguration du contrôle de tension.
• En cas d’alarmes ou de messages, affichage du lemessage d’alarme. En appuyant sur la touche de sélection, il estpossible de masquer temporairement l’alarme etd’accéder aux mesures.
2.2 Sélections des mesures
Exemple de liste des mesures sur un boîtier configuré pour le contrôle
triphasé.
• Sur la façade sont présents un certain nombre de témoins qui indiquent l’état de l’appareil et/ou desappareils qu’il commandent.
2.3 Indicateurs à diodes
Diode ALARME(rouge)
Diode ALIMENTATION(verte)
Diode touche SET(rouge)
Diode touche AUT(rouge)
Diode touche MAN(rouge)
Diode touche RESET(rouge)
Diodes L1/L2/L3Présence tension ligne
principale (rouges)
Diode COMMANDESligne principale /ligne secondaire(bicolore)
Diode d’état int. ligne principale
Diode d’état int. ligne secondaire
Diodes L1/L2/L3Présence tension ligne
secondaire (rouges)
7
• Dans le tableau ci-dessus est indiquée la signification des différents témoins.Certains d’entre eux sont bicolores à savoir que leur signification est différente selon la couleur.
✱ Si les contacts auxiliaires ont été branchés, le voyant représente l’état de l’appareil, sinon il reste éteint.✱✱ Si les contacts correspondants ont été branchés à cet effet, le voyant représente l’état de l’appareil, sinon les
voyants restent éteints.
Voyant Allumé Éteint Clignotant
ALARME Aucune alarme active Un ou plusieurs alarmes actives (ROUGE)
ALIMENTATION Boîtier alimentée (VERT) Absence alimentation
COMMANDE OUVERTURE/FERMETURE
Commande fermeture (ROUGE)
Commande ouverture (VERT)
Aucune commande
FERMÉ/OUVERT � Appareil fermé (ROUGE)Appareil ouvert (VERT)
Contacts auxiliaires non branchés
NON ENCLENCHÉ �� Appareil non enclenché sur la base
Appareil enclenché ou contrôle enclenchement
désactivé
DÉCLENCHÉ �� Appareil déclenchéAppareil non déclenché
ou contact SDnon connecté
PRÉSENCEL1/L2/L3 Présence tension Absence tension
1HZ = Temps présence absence en cours5HZ = Sélection mesures moniteur
3. Modes de fonctionnement
8
• A l’aide des quatre touches SET / AUT / MAN/ RESET il est possible de sélectionner le modede fonctionnement voulu et indiqué par l’allumagedu voyant rouge correspondant.
• Si le voyant qui indique le mode de fonctionne-ment sélectionné clignote, cela indique que l’ap-pareil est en communication à travers l’interfacesérie et qu’il est susceptible d’effectuer des com-mandes transmises à distance (par exemple unecommande de changement de mode).
A B
E
F
G
H
C D
• Le boîtier n’effectue aucune opération et se limiteà afficher l’état des tensions et des appareils.
• Les sorties de commande de fermeture et ouvertu-re des appareils restent toutes ouvertes permettantla commande manuelle des motorisations. Si l’en-trée «arrêt d’urgence» est activée, le boîtier com-mande l’ouverture des appareils.
• La sortie de commande générateur se positionnepour l’arrêt du groupe.
• Les alarmes d’état des appareils sont désactivées. • Lorsqu’une alarme se déclenche, elle doit être
réarmée en appuyant sur la touche RESET. Dans lecas où l’on se trouverait déjà dans ce mode,appuyer à nouveau sur la touche RESET.
3.1 Mode reset (voyant touche RESET rouge)
• En mode Automatique l’appareil effectue demanière autonome les opérations d’ouverture etde fermeture des appareils ainsi que la mise enmarche et l’arrêt de l’éventuel groupe électrogène.
• Quand la ligne principale (MAIN) se trouve horsdes limites, à l’issue des temps de retard program-més, l’appareil déconnecte la charge de la ligneprioritaire et la connecte à la ligne secondaire(SEC), en contrôlant aussi bien la mise en marche
de l’éventuel groupe électrogène que les temps decommande d’inter-verrouillage entre les appareils.
• Quand la ligne principale rentre à nouveau dansles limites, le boîtier commute à nouveau la chargesur la ligne principale et assure l’éventuel cycle derefroidissement du groupe électrogène.
• Les cycles de fonctionnement automatique varienten fonction du type d’application (secteur-secteurou secteur-groupe).
9
Attention:L’exécut ionde ce test pré-voit le trans-fert de lacharge, àsavoir unecoupure del’alimentationsur celle-cipendant lacommutationdue auxtemps d’inter-verrouillage.
3.2 Mode Manuel (voyant touche MAN rouge)• Le mode manuel permet à l’opérateur d’ouvrir/fer-
mer électriquement les appareils à l’aide destouches présentes sur la façade de l’appareil.
• Dans ce mode les tensions sont constammentcontrôlées mais le boîtier se limite à en visualiserl’état.
• En appuyant pendant au moins 300 ms sur unedes touches de commande, le boîtier commutel’état de l’appareil correspondant (d’ouvert àfermé et vice-versa).
• Dans le cas où serait commandé la fermetured’un appareil alors que l’autre est déjà fermé, le
boîtier ouvre initialement l’autre appareil, laisses’écouler le temps d’inter-verrouillage puis fermel’appareil voulu.
• En Manuel toutes les alarmes relatives à l’état desappareils (non enclenchés et déclenchés) sontdésactivées. L’alarme est indiquée sur le voyantcorrespondant mais n’est pas mémorisée.
• Il est possible de commander manuellement lamise en marche et l’arrêt du groupe électrogèneen maintenant enfoncée la touche (G) MAN pen-dant 5 secondes d’affilée. Tant que l’on reste enmode manuel, l’état du groupe reste celui voulu.
3.3 Mode Automatique (voyant touche AUT rouge)
• En partant du mode Automatique et en appuyant sur latouche (F) pendant 5 secondes, alors s’enclenche untest du groupe électrogène d’une durée de 5 minutes.
• Le groupe électrogène est mis en marche manuel-lement pour qu’en soit contrôlé le fonctionnement,mais les contrôles de tension restent actifs puisquele boîtier est en mode automatique.
• De la sorte il est possible de s’assurer du bonfonctionnement du groupe en maintenant la
couverture de la charge. En conditions nor-males, la charge reste connectée à la ligneprincipale, à savoir que le groupe fonctionnesans charge (off-load groupe électrogène).
• L’exécution du test off-load est signalée par l’indi-cation TES fixe sur le boîtier.
• Pour anticiper la fin du test, appuyer à nouveau surla touche (F) pendant 5 secondes ou bien passeren mode Reset.
• En partant du mode automatique et en appuyantsimultanément sur les touches (F) et (D) pendant5 secondes, alors est activé un test fonctionnel(test on-load) qui simule une coupure d’une duréed’une minute.
• Le boîtier si comporte ensuite exactement commesi le secteur était sorti des limites, en utilisantpour la commutation tous les temps et tous les
paramètres programmés, de façon à en contrô-ler la validité.
• L’exécution du test on-load est signalée par l’indi-cation TES clignotante sur le boîtier.
• Pour anticiper la fin du test, répéter la procédure àl’aide des touches (F) et (D) pendant 5 secondesou bien passer en mode Reset.
3.5 Mode test on-load
3.4 Mode test off-load
4. Applications
10
4.1 Application Secteur-Groupe• Sur l’application secteur-groupe (U-G, configura-
tion par défaut) la charge est en principe connec-tée à la ligne principale. En présence d’une ano-malie sur le secteur ou en cas de signal de trans-fert imposé de l’extérieur, il est transmis un signalde mise en marche au groupe présent sur la lignesecondaire.
• Quand la tension du groupe rentre dans les limitesprogrammées, le boîtier commande la commuta-tion sur la ligne secondaire.
• Au retour de la ligne principale la charge estretransférée et le groupe est maintenu en marchesans charge pendant une durée préétablie defaçon à en permettre le refroidissement.
• Le boîtier envoie au groupe une commande destart/stop par l’intermédiaire d’une sortie à relaiset peut recevoir des signaux numériques du grou-pe qui en indiquent l’état à travers des entréesprogrammables.
4.2 Application Secteur-Secteur• Sur l’application secteur-secteur (U-U, utility-utili-
ty), la charge est en principe connectée au sec-teur prioritaire et le transfert sur le secteur secon-
daire intervient en cas d’anomalie sur le secteurprimaire ou de signal de transfert imposé del’extérieur.
5. Commande appareils
11
• La commande de la motorisation des appareils estassurée par deux relais distincts, l’un pour la fer-meture et l’autre pour l’ouverture.
• En mode Reset, les deux relais de commande restentouverts, sauf en condition d’urgence dans laquellel’ouverture de l’appareil peut être commandée.
• Suite à une anomalie sur l’appareil provoquantune alarme, les sorties de commande sont toutesdeux ouvertes jusqu’à l’élimination de l’alarme.
• Ils existent deux modes distincts de contrôle desappareils, sélectionnables par l’intermédiaire duparamètre P1.03
Les contactsauxiliares CAde l’appareil
sont câblés surles entrées
respectives duboîtier.
En modalitéfeedback est
nécessaire d’utiliser pourl’ouverture du
DPX 250-630-1600
des déclencheures a
emition de courant ou a
minimum de tension.
Exemple de commande des appareilsavec feedback en supposant une
commutation secteur-secteur. En bleu estindiqué l’état des entrées de feedback.En vert l’état des sorties de commande.
En jaune le temps de commutation.
0.5 s
15 s
0.5 s
LED VMAIN OK
LED VSEC OK
46
115
18
3
1s
1s
15 s
5.1 Avec feedback • Les voyants bicolores frontaux indiquent l’état des
appareils en commutation grâce aux contactsauxiliaires CA.
• Les alarmes Timeout sont actives. Elles se déclen-chent si l’appareil ne se place en position requiseau bout d’une durée programmable P1.04 ouimmédiatement s’il change de position sansqu’une commande n’ait été envoyée.
• Les sorties de commande sont temporisées. Unefois que l’appareil a effectué l’opération voulue, la
sortie reste activée pendant une certaine durée(+1 seconde en phase de fermeture et +15secondes en phase d’ouverture pour permettre lechargement complet des ressorts) puis elle estdésactivée
• L’état normal des sorties de commande est l’étatouvert pour les deux sorties.
• Le temps d’inter-verrouillage est décompté à partirde l’ouverture effective du premier appareil, et ilest de 0,5 seconde.
12
5.2 Sans feedback
Les contactsauxiliaires CA
de l’appareil nesont pas câbléssur les entrées
respectives,donc le boîtier
n’est pasinformée de leur
état effectif.
Exemple de commande des appareilssans feedback.
En bleu est indiqué l’état effectif desappareils.
En vert l’état des sorties de commande.En jaune le temps de commutation.
6 sec 6 sec
LED VMAIN OK
LED VSEC. OK
INT. MAIN
INT. SEC.46
13
• Les voyants d’état de l’appareil restent éteints. • Les alarmes de Timeout sont désactivées.• Les sorties des commandes Ouverture/Fermetu-
re restent constamment dans la position requisepour l’appareil.
• Les temps d’inter-verrouillage entre l’ouvertured’un appareil et la fermeture de l’autre estdécompté à partir de la commutation des sor-ties et il est de 6 secondes.
6. Contrôles de tension
13
• Toutes les conditions, servant à établir si une sour-ce d’alimentation est appropriée ou non, sont défi-nies par l’utilisateur par l’intermédiaire du menuP0 (données nominales de l’installation) et desmenus P2 et P3 (respectivement contrôle tensionde la ligne principale et de la ligne secondaire).
• Par l’intermédiaire du menu P0 il est possible dedéfinir les données nominales telles que tension etfréquence nominale, utilisées ensuite comme réfé-rence pour la programmation des seuils (en pour-centage) des menus suivants.
• Il est possible de programmer un rapport de trans-formation TU dans le cas où serait appliquée auxentrées de tension du boîtier une tension inférieureà la tension effective de l’installation. Dans ce caségalement, la visualisation et la programmationdes seuils sont effectuées en grandeurs réelles parrapport à l’installation.
• Le boîtier peut être programmée pour effectuerles contrôles de tension sur secteurs triphasés,biphasés ou monophasés (par l’intermédiaire duparamètre P0.03).
Contrôle 261 93 261 94 Description
Tension minimum • • Une ou plusieurs phases trop basses
Tension maximum • Une ou plusieurs phases trop hautes
Absence phase • • Seuil en deçà duquel líappa reil intervient plus rapidement par rapport à un abaissement normal
Asymétrie(déséquilibrage) • Phases comprises sur l’intervalle Maximum-Minimum
mais trop différentes l’une de l’autre
Fréquence minimum • Fréquence trop basse
Fréquence maximum • Fréquence trop haute
Séquence phases • Rotation inverse des phases
Ci-après sont indiquées les anomalies dont la gestion est assuré par le contrôle de tension.Les colonnes 261 93 et 261 94 indiquent la présence de la fonction sur les différents modèles du boîtier.
14
• Chacune des anomalies a un temps de retardindépendant. L’anomalie doit avoir une durée inin-terrompue supérieure au temps indiqué pour inva-lider le signal de présence tension.
• Tous les contrôles, exception faite du contrôle detension minimum, peuvent être exclus indépendam-ment les uns des autres en plaçant le paramètrecorrespondant sur OFF.
• Les limites de tension minimum et maximum sontdéfinies par la programmation de deux seuils spé-cifiques, l’un définissant le point au-delà duquel latension est considérée comme n’étant plus accep-table (ex. P2.01), l’autre, plus proche de la ten-sion nominale, définissant le point à partir duquel
elle est de nouveau acceptable (ex. P2.02). Ladistance entre ces deux points définit l’hystérésis.Par exemple, on peut établir qu’en deçà de 80%de la valeur nominale, la tension n’est plus utili-sable et qu’elle est à nouveau acceptable une foisqu’elle est à nouveau supérieure à 85%, l’hystéré-sis étant dans ce cas de 5%.Le même principe s’applique à la tension maximum.
• Pour les seuils de fréquence existe une hystérésisfixe de 1% de la fréquence nominale.
• Le rétablissement à l’issue d’une absence dephase est obtenue quand la tension repasse au-dessus du seuil de rétablissement de tensionminimum.
Exemple de variation de la tension de laligne principale à l’intérieur des seuils
minimum et maximum et compte tenu deshystérésis correspondantes,
avec indication des temps de retardprésence/absence. Sur l’exemple, la tension de ligne secondaire est
considérée comme absente et l’appareilcorrespondant ouvert, aussi les temps
d’inter-verrouillage ne sont pas indiqués.La barre INTERR. représente l’état voulu
de l’appareil de la ligne principale.
P2.04
P2.05
P2.02
V MAIN
P2.01
LED VOK
INTERR.P2.03 P2.15 P2.15P2.06 P2.05<
7. Programmation
15
7.1 Programmation des paramètres
Touche E- Accès programmation - Quitter vers niveau supérieur
Touche ADéplacement au
même niveau
Touche B- Validation modification- Confirmation configuration
Touche FAugmenter valeur paramètre
Touche GAbaisser valeur paramètre
Touche HAccès au niveau inférieur
• Pour accéder à la programmation, appuyer sur lestouches H et E simultanément pendant 5 secondesd’affilée
• Le voyant de la touche E clignotant indique que laprogrammation est en cours
• L’afficheur de la ligne principale indique le para-mètre sélectionné par l’intermédiaire du code (parexemple P0.01)
• L’afficheur de la ligne secondaire indique la valeurde programmation du paramètre sélectionné (parexemple 400)
• Changement de paramètre d’un même groupe enappuyant sur la touche A
• Passage au groupe suivant avec la touche E• Passage au groupe précédent avec la touche H
• Validation de la modification du paramètre avecla touche B
• Augmentation de la valeur du paramètre sélection-né avec la touche F
• Diminution de la valeur du paramètre sélectionnéavec la touche G
• Confirmation en appuyant sur la touche B• Lors de la modification d’un paramètre, l’afficheur
de la ligne secondaire affiche la valeur actuelleclignotante du paramètre. Durant cette phase iln’est pas possible de se déplacer sur un autreparamètre avant d’avoir validé
• Pour quitter la programmation, appuyer simultané-ment sur les touches E et H
16
7.2 Tableau des menus
7.3 Menu P0 - Données nominales
Menu Description
P0 Données nominales de l’installation
P1 Données générales
P2 Contrôle tension ligne principale
P3 Contrôle tension ligne secondaire
P4 Entrées programmables
P5 Sorties programmables
P6 Port de communication
Prog. Description Plage Par défaut
P0.01 B Tension nominale Ue 100 … 690 Vca 380 Vca
P0.02 B Rapport de transformation TU 1.00 … 9.99 1.00
P0.03 B Type de reseau3Ph = Triphasée2PH = Biphasée1Ph = Monophasée
3Ph
P0.04 B Fréquence nominale Fe 50H = 50Hz60H = 60Hz 50Hz
P0.05 B Tension nominale batterie
OFF = Sans batterie12 = 12 Vcc24 = 24 Vcc48 = 48 Vcc
OFF
P0.01 - Tension nominale utilisée pour le calcul des seuils P0.02 - Maintenir la programmation par défaut en cas de non-utilisation de TUP0.04 - Fréquence nominale utilisée comme référence pour le calcul des seuils de fréquence P0.05 - Utilisé pour les alarmes sur la tension de batterie
17
7.4 Menu P1 - Données généralesProg. Description Plage Par défaut
P1.01 Type d’application U-G = Secteur-GroupeU-U = Secteur-Secteur U-G
P1.02 Contrôle séquence phaseOFF - Désactivé123 - Direct321 - Inverse
OFF
P1.03 Contrôle commutation FEE - Avec feedback NOF - Sans feedback FEE
P1.04 Temps maximum de commande appareil OFF / 1…900s 5 s
P1.05 Activation contrôle appareils extraits OFF (Contrôle désactivé)ON (Contrôle activé) OFF
P1.06 Temps maximum charge non alimentée (retard intervention alarme A07) OFF / 1…3600s OFF
P1.07 Temps de retard mise en marche groupe 0 …. 900 s 1 s
P1.08 Temps de refroidissement groupe 1…3600s 120 s
P1.09 Seuil minimum tension batterie OFF / 70…100% 75%
P1.10 Seuil maximum tension batterie OFF / 110…140% 130%
P1.11 Temps de retard seuils batterie 0…60 s 10 s
P1.01 - Définit le type de commutation (secteur-secteur / secteur-groupe)P1.04 - Dans le cas où après la transmission d’une commande d’ouverture ou de fermeture à un appareil, celui-ci ne se
positionnerait pas correctement avant que cette durée ne se soit écoulée, alors activation de l’alarme A03 ouA04
P1.05 - Activer le contrôle uniquement si les contacts correspondants sont câblésP1.06 - En mode Automatique, si aucune des deux sources n’est disponible avant la fin de cette temporisation, alors
activation de l’alarme A07P1.07 - Temporisation enclenchée lors de l’absence de tension sur la ligne principale, si fin de tempo ordre de démarrage
groupe.Il s’agit d’une durée indépendante du temps d’ouverture des appareils
P1.08 - Temps pendant lequel le groupe est maintenu en marche pour son refroidissement après qu’il ait été isolé de lacharge
Les paramètresen évidence
sont présentsuniquement
sur la version261 94
18
7.5 Menu P2 - Contrôle tension ligne principaleProg. Description Plage Par défaut
P2.01 Seuil tension minimum - décrochage 70…98% Ue 85% Ue
P2.02 Seuil tension minimum - rétablissement 75…100% Ue 90% Ue
P2.03 Retard seuil tension minimum 0.1 …. 900 s 1.0 s
P2.04 Seuil tension maximum - décrochage 102…120% Ue / OFF 115% Ue
P2.05 Seuil tension maximum - rétablissement 100…115% Ue 110% Ue
P2.06 Retard seuil tension maximum 0.1 …. 900 s 1.0 s
P2.07 Seuil absence phase 60 … 85% Ue / OFF 70% Ue
P2.08 Retard seuil absence phase 0.1 … 30.0 s 0.1 s
P2.09 Seuil déséquilibrage tensions 1 … 20% Ue / OFF 10%
P2.10 Retard seuil déséquilibrage tensions 0.1 … 900 s 5.0 s
P2.11 Seuil minimum fréquence OFF / 80… 100% Fe 95% Fe
P2.12 Retard seuil minimum fréquence 0.1 … 900 s 5.0 s
P2.13 Seuil maximum fréquence 101 … 120% Fe / OFF 105% Fe
P2.14 Retard seuil maximum fréquence 0.1 … 900 s 3.0 s
P2.15 Retard retour tension ligne principale dans les limites (quand int. ligne secondaire ouvert) 1 … 3600 s 10 s
P2.16 Retard retour tension ligne principale dans les limites (quand charge sur ligne secondaire) 1 … 3600 s 60 s
Les paramètresen évidence
sont présentsuniquement
sur la version261 94
P2.01 - P2.02 - P2.03 - Les deux premiers paramètres définissent le seuil de tension minimum et l’hystérésis corres-pondante au rétablissement. P2.02 ne peut pas être programmé sur une valeur inférieure à P2.01. P2.03 définit le tempsde retard pour l’intervention de cette protection. Voir chapitre Contrôles de tensionP2.04 - P2.05 - P2.06 - Les deux premiers paramètres définissent le seuil de tension maximum et l’hystérésis corres-pondante au rétablissement. P2.05 ne peut être programmé sur une valeur supérieure à P2.04. En programmant P2.04sur OFF, le contrôle de tension maximum est désactivé. P2.06 définit le retard d’intervention de tension maximum. Voirchapitre Contrôles de tensionP2.07 - P2.08 - Seuil de tension en deçà duquel se déclenche une intervention pour absence de phase, géné-ralement plus rapide que l’abaissement. Le temps de retard pour l’absence phase est indiqué par P2.08P2.09 - P2.10 - P2.09 définit le seuil maximum de déséquilibre entre les phases, en rapport à la tension nominale,et P2.10 le retard d’intervention correspondant.Ce contrôle peut être désactivé en programmant P2.09 sur OFF P2.11 - P2.12 - Seuil (désactivable) et retard d’intervention de fréquence minimum P2.13 - P2.14 - Seuil (désactivable) et retard d’intervention de fréquence maximumP2.15 - Temps de retard retour ligne principale dans les limites, utilisé quand la source de la ligne secondaire n’est pasdisponible. Généralement plus court que P2.16, puisque, la charge n’étant pas alimentée, il est urgent de fournir unetensionP2.16 - Temps de retard retour ligne principale dans les limites, utilisé quand la charge peut être connectée à laligne secondaire. Généralement plus long que P2.15, puisque, la charge étant sous tension il est possible d’attendreplus longtemps avant de considérer la tension comme rétablie et stable
19
7.6 Menu P3* - Contrôle tension ligne secondaireProg. Description Plage Par défaut
P3.01 Seuil tension minimum - décrochage 70…98 % Ue 85 % Ue
P3.02 Seuil tension minimum - rétablissement 75…100 % Ue 90 % Ue
P3.03 Retard seuil tension minimum 0.1 …. 900 s 1.0 s
P3.04 Seuil tension maximum - décrochage 102…120 % Ue / OFF 115 % Ue
P3.05 Seuil tension maximum - rétablissement 100…115 % Ue 110 % Ue
P3.06 Retard seuil tension maximum 0.1 …. 900 s 1.0 s
P3.07 Seuil absence phase 60 … 85% Ue / OFF 70 % Ue
P3.08 Retard seuil absence phase 0.1 … 30.0 s 0.1 s
P3.09 Seuil déséquilibrage tensions 1 … 20 % / OFF 10 %
P3.10 Retard seuil déséquilibrage tensions 0.1 … 900 s 5.0 s
P3.11 Seuil minimum fréquence 99 … 80 % Fe / OFF 95 % Fe
P3.12 Retard seuil minimum fréquence 0.1 … 900 s 5.0 s
P3.13 Seuil maximum fréquence 101 … 120% Fe / OFF 105 % Fe
P3.14 Retard seuil maximum fréquence 0.1 … 900 s 3.0 s
P3.15 Retard tension ligne secondaire dans les limites 1 … 3600 s 20 s
Les paramètresen évidence
sont présentsuniquement
sur la version261 94
Note: Pourl’explicationde la fonc-tion desparamètres,se reporter àla page pré-c é d e n t e(menu ligneprincipale).
* Commentaires identiques au Menu P2
7.7 Menu P4 - Entrées programmablesProg. Description Plage Par défaut
P4.01 Fonction entrée - Programmable 1Voir liste
“Fonctions entrées programmables”
ForForçage sur ligne secondaire
P4.02 Fonction entrée - Programmable 2In.rInhibition sur ligne principale
Fonctions entrées programmables
Fonction Description Notes
OFF OFF Entrée non utilisée
ForCommutation forcée sur ligne secondaire (fonction EJP)
Quand elle est fermée, force la commutation sur la ligne secondaire y compris si la tension de la ligne principale est dans les limites. La commutation sur la ligne principale intervient quand l’entrée est libérée ou dans le cas où la tension de la ligne secondaire ne serait pas dans les limites
IN.R Inhibition retour sur ligne principale
En mode automatique, quand elle est fermée, elle bloque le retour en automatique sur la ligne principale après que la tension soit revenue dans les limites. Sert à éviter que la seconde interruption de courant due au re-transfert intervienne automatiquement à un moment imprévisible
S.GEMise en marche/arrêt volontaire groupe
En mode automatique, quand elle est fermée, provoque la mise en marche du groupe
EME Urgence Contact NF: si ouvert provoque l’ouverture des appareils et déclenche une alarme
G.rE Générateur prêtSi elle est fermée, indique que le générateur est en automatique et non en alarme. Si elle est ouverte, génère un code d’alarme
Loc Blocage total clavier Si elle est fermée bloque toutes les fonctions du clavier à l’exception des mesures
L.PA Blocage accès paramètres Si elle est fermée bloque l’accès aux configurations
20
7.8 Menu P5 - Sorties programmablesProg. Description Plage Par défaut
P5.01 Fonction sortie Programmable 1 Voir liste “Fonctions sorties programmables” S.GE
Start generator
P5.02 Fonction sortie Programmable 2 Voir liste “Fonctions sorties programmables” RDY
ATS Ready
P5.03 Fonction sortie Programmable 3 Voir liste “Fonctions sorties programmables” ALA
Alarme générale
21
Fonctions sorties programmables
Fonction Description Notes
OFF OFF Sortie non utilisée
S.GE Validation mise en marche générateurQuand elle est fermée, le générateur doit être à l’arrêt.Contact ouvert pour mettre en marche le générateur.Si la boîtier n’est pas alimentée, le générateur se met en marche
RDY Commutation transfert automatique prêt Signal que le boîtier est en mode automatique et sans alarmes, prêt à intervenir
ALA Alarme générale Signalisation alarme à distance
MCMBobine à minimum de tensionLigne principale
Commande bobine à minimum de tension de l’appareil ligne principal
MCSBobine à minimum de tensionLigne secondaire
Commande bobine à minimum de tension de l’appareil ligne secondaire
L.SHDébranchement charges non prioritaires
Débranchement des charges non prioritaires qui ne sont pas alimentées par la ligne secondaire.Elle est également commandée sur ligne principale.Contact fermé avant la commande de fermeture ligne secondaire et ouvert avant la commande de fermeture ligne principale
7.9 Menu P6 - Communication sérieProg. Description Plage Par défaut
P6.01 Adresse sérielle RS-232 1…245 01
P6.02 Vitesse (bauds) RS-232
240 = 2400 480 = 4800960 = 9600 19.2 = 19200 38.4 = 38400
960
P6.03 Protocole RS-232 Rtu = Modbus RTUASC = Modbus ASCII RTU
P6.04 Parité RS-232No = AucuneEVE = Even (Paire)Odd = Odd (Impaire)
No
P6.05 Adresse série RS-485 1…245 01
P6.06 Vitesse (bauds) RS-485
240 = 2400 480 = 4800960 = 9600 19.2 = 19200 38.4 = 38400
960
P6.07 Protocole RS-485 Rtu = Modbus RTUASC = Modbus ASCII RTU
P6.08 Parité RS-485No = AucuneEVE = Even (Paire) Odd = Odd (Impaire)
No
P6.01…P6.04 - Définissent le format de transmission et le protocole utilisé sur le port de communication RS-232P6.05…P6.08 - Définissent le format de transmission et le protocole utilisé sur le port de communication RS-485,
disponible uniquement sur la version 261 94
Les paramètresen évidence
sont présentesuniquement
sur la version261 94
8. Messages de diagnostic
22
Sur les afficheurs peuvent être visualisés à différents moments les messages suivants:
Code Description
- - -(Tirets) - La temporisation d’inter-verrouillage est active.S’affichent du côté vers lequel la charge est en cours de transfert
Sta (Start) - Commande de mise en marche générateur
Coo (Cooling) - Le générateur est maintenu en marche pour effectuer le refroidissement
Tes(Test) - Si fixe, test off-load en cours, à savoir un test du groupe électrogène avec les contrôles de tension actifs
Tes (Test) - Si clignotant, test on-load en cours, à savoir une simulation de l’absence secteur en automatique
Loc (Locked) - Indique que la fonction que l’on tente d’exécuter depuis le clavier est bloqué
9. Alarmes
23
• Durant le fonctionnement du boîtier, peut se pré-senter toute une série de situations anormales, les-quelles sont signalées de différentes manières.
• Certaines alarmes (déclenché, non réarmé) ontun voyant spécifique qui en cas d’intervention semet à clignoter.
• D’autres alarmes sont signalées par l’intermédiaired’un code constitué d’un A (alarme) et d’une réfé-rence numérique qui indique de quelle alarme ils’agit. Ce code se visualise en clignotant sur undes afficheurs. Si le code est relatif à la ligne prin-cipale, l’alarme est visualisée sur l’afficheur degauche. En revanche, s’il se réfère à la lignesecondaire ou s’il s’agit d’une alarme générale (ex.batterie) il est visualisé sur l’afficheur de droite.
• Quand une alarme se déclenche, le voyant rouge“ALARME” clignote en synchronisation avec levoyant spécifique ou le code d’alarme.
• La sortie à relais Alarme générale est désactivéeen condition alarme, alors qu’elle est activée encondition normale. Le non-fonctionnement du boî-tier pour cause d’anomalie ou problème d’alimen-tation déclenche par conséquent la conditiond’alarme sur le contact correspondant.
• Certaines alarmes sont automatiquement désacti-vées lorsque les conditions qui ont donnés lieu àleurs déclenchements sont éliminées.
• D’autres alarmes, indiquées dans le tableau de lacolonne MEM, sont en revanche à retenue et sontmémorisées.
• Une fois que l’alarme a été mémorisée, pour êtredésactivée, il est nécessaire que les conditionsanormales soient éliminées et que l’opérateurappuie sur la touche RESET ou envoie un messagespécifique par l’intermédiaire de l’interface série.
24
Liste alarmes
Code Voyant Description alarme Cause MEM RESET MAN AUT
A01 Tension batterie trop basse
Se déclenche si le paramètre P0.06 n’est pas sur OFF et si la tension de batterie mesurée reste inférieure au seuil % programmé sur P1.09 pendant la durée programmée sur P1.11
OUI OUI OUI OUI
A02 Tension batterie trop élevée
Se déclenche si le paramètre P0.06 n’est pas sur OFF et si la tension de batterie mesurée reste supérieure au seuil % programmé sur P1.10 pendant la durée programmée sur P1.11
OUI OUI OUI OUI
A03 Timeout appareil ligne principale
Se déclenche si l’appareil de ligne principale ne se place pas dans la position commandée par le boîtier avant que ne s’écoule la temporisation sur P1.04 ou s’il quitte de lui-même la position requise. L’alarme peut se déclencher aussi bien en fermeture qu’en ouverture. Si la tension est absente sur les deux lignes, l’alarme ne se déclenche pas
OUI NON NON OUI
A04 Timeout appareil ligne secondaire
Se déclenche si l’appareil de ligne secondaire ne se place pas dans la position commandée par la boitier avant que ne s’écoule la temporisation sur P1.04 ou s’il quitte de lui-même la position requise. L’alarme peut se déclencher aussi bien en fermeture qu’en ouverture. Si la tension est absente sur les deux lignes, l’alarme ne se déclenche pas
OUI NON NON OUI
A05Erreur séquence phase sur ligne principale
Si elle est activée par le paramètre P1.02, cette alarme se déclenche quand est détectée une séquence de phase différente de celle prévue par le paramètre P1.02, après un retard d’environ 500 ms. Pour que la séquence puisse être détectée, les trois phases doivent être > 50Vca
OUI OUI OUI OUI
A06Erreur séquence phase sur ligne secondaire
Idem alarme précédente en référence à la tension de la ligne secondaire OUI OUI OUI OUI
A07 Timeout charge non alimentée
La charge est restée sans tension pendant une durée supérieure à P1.06.Ligne principale et ligne secondaire sont restées indisponibles (absence tension ou appareil non fermé)
NON NON NON YES
A08 Générateur non disponible
Une des entrées programmables est programmée sur “Generator ready” et signale que le générateur n’est pas disponible NON OUI OUI OUI
A09 Urgence Une des entrées programmables est programmée sur bouton d’arrêt d’urgence et le contact correspondant est ouvert OUI OUI OUI OUI
A11Fréquence ligne principale hors limites
La fréquence de la ligne principale est hors des limites définies par P2.11 et P2.13 NON OUI OUI OUI
A12Fréquence ligne secondaire hors limites
La fréquence de la ligne secondaire est hors des limites définies par P3.11 et P3.13 NON OUI OUI OUI
A13 Asymétrie tensions ligne principale
La différence entre la tension phase-phase la plus haute et la plus basse de la ligne principale excède la limite définie par P2.09
NON OUI OUI OUI
A14 Asymétrie tensions ligne secondaire
La différence entre la tension phase-phase la plus haute et la plus basse de la ligne secondaire excède la limite définie par P3.09
NON OUI OUI OUI
•
Ligne principale/ secondaire non enclenché.Appareil extrait
Le contrôle des entrées de “non activé” est validé par le paramètre P1.05 et le contact correspondant d’entrée de ligne principale ou ligne secondaire est ouvert
OUI OUI OUI OUI
•
Ligne principale/secondaire déclenchement. Intervention protection. Appareil
Le contact d’entrée “déclenché” est fermé.Cette condition est ignorée pendant une durée de 15 sec. décomptée aussitôt après avoir commandé l’ouverture d’un appareil, pour éviter les erreurs de signal quand est utilisée une bobine de décrochage
OUI VIS VIS OUI
Les alarmes enévidence sont
présentes uniquement
sur la version261 94
10. Branchements
25
Borne Fonction
1 Ouverture appareil ligne principale
2 Commun commande ligne principale
3 Fermeture appareil ligne principale
4 Ouverture appareil ligne secondaire
5 Commun commandes ligne secondaire
6 Fermeture appareil ligne secondaire
7 Relais programmable 1 (Fonction par défaut = Start/Stop générateur)
8 Commun relais programmable
9
Relais programmable 2/NF (Fonction par défaut = Boîtier prête)
10 Relais programmable 2/NO (Fonction par défaut = Boîtier prête)
11
Commun relais programmable 2
12
Relais de programmable 3/NF (Fonction par défaut = Alarme générale)
13Relais de programmable 3/NO (Fonction par défaut = Alarme globale - fermé quand ok)
14
Commun relais programmable 3
15 Entrée contact CA appareil ligne principale
Borne Fonction
16 Entrée contact SD appareil ligne principale
17 Entrée contact appareil débrochable ligne principale
18 Entrée contact CA appareil ligne secondaire
19 Entrée contact SD appareil ligne secondaire
20 Entrée contact appareil débrochable ligne secondaire
21 Entrée programmable 1 (Par défaut = Fonction EJP)
22 Entrée programmable 2 (Par défaut = Inhibition retour sur ligne principale)
23 + Alimentation CC
24 – Alimentation CC
25 Commun pour entrées (de 15 à 22)
26 Alimentation AC
27 Alimentation AC
MAIN L1 L2 L3 N
Entrée de mesure triphasée ligne principale
SEC. L1 L2 L3 N
Entrée de mesure triphasée ligne secondaire
11. Caractéristiques techniques
26
Alimentation auxiliaireChamp d’alimentation CC 9...70Vcc (Us=12-24-48Vcc)Champ d’alimentation CA 187…264Vca (Us=220…240Vca)Fréquence 45…65HzPuissance absorbée max. 6VA (Us=240Vca)Puissance dissipée max. 4,8W (Us= 240Vca ou Us=48Vcc)Courant absorbé max. 420mA à 12Vcc; 200mA à 24Vcc; 100mA à 48VccTemps d’immunité à la micro-coupure 50msEntrées voltmétriquesTension nominale max. (Ue) 690Vca phase-phase (400Vca phase-neutre)Donnée d’utilisation UL 600Vca phase-phase (340Vca phase-neutre)Champ de mesure 80…800Vc phase--phaseChamp de fréquence 45…65HzType de mesure TRMS (valeur efficace réelle)Impédance de l’entrée de mesure >1,1M Ω phase-phase et > 0,5M Ω phase-neutreMode d’activation Monophasée, biphasée, triphaséeErreur de mesure Classe 0,5 ±0,25% f.s. ±1digitEntrées numériques Type d’entrée NégativeCourant d’entrée ≤10mASignal d’entrée état logique “0” ≤1,5 (type 2,9V)Signal d’entrée état logique “1” ≥5,3 (type 4,3V)Retard du signal d’entrée ≥50msecSorties à relais bornes 1-2 et 4-5Type de contact 1 NOPortée nominale à 250VAC 12APortée nominale contact 16A sur AC1 250V - B300Courant maximum sur la borne 1.2 12ASorties à relais bornes 2-3 et 5-6Type de contact 1 NO
Portée nominale contact 8A sur AC1 250V - B30030Vcc 1A Service auxiliaire
Courant maximum sur la borne 2.2 12ASorties à relais bornes 7-8Type de contact 1 NO
Portée nominale contact 8A sur AC1 250V - B30030Vcc 1A Service auxiliaire
Sorties à relais bornes 9-10-11 et 12-13-14 Type de contact 1 contact NO/NF
Portée nominale contact 8A sur AC1 250V - B30030Vcc 1A Service auxiliaire
Lignes de communication
Interface série RS232 Vitesse de transmission de 1200…38400 baudsConnexion par l’intermédiaire du connecteur RJ6/6
Interface série RS485(261 94 uniquement)
Isolée avec vitesse de transmission programmable 1200…38400 bauds. Connexion par l’intermédiaire de bornes extractibles
IsolationTension nominale d’isolation (Ui) 690VConditions ambiantes de fonctionnementTempérature d’utilisation -20…+60°CTempérature de stockage -30…+80°CHumidité relative <90% Pollution ambiante maximum Degré 3Catégorie de surtension 3BranchementsType de bornes ExtractiblesSection des conducteurs (min. et max.) 0,2…2,5 mm2 (24÷12 AWG)Couple de serrage 0,5 Nm (4,5 LBin)BoîtierMatériau Thermoplastique LEXAN 3412RType EncastréDimensions L x H x P 144 x 144 x 94mmDegré de protection IP41 sur partie frontale, IP20 sur partie arrièrePoids 950gRéférences normativesIEC/EN 61010-1, IEC/EN 61000-6-2, CISPR 11/EN 55011, IEC/EN 61000-3-2, IEC/EN 61000-3-3, IEC/EN 60068-2-61, IEC/EN 60068-2-27, IEC/EN 60068-2-6, UL508 C22.2-N°14-95
October 08
EElleeccttrroonniiccCCoonnttrrooll BBooxx
Item 261 93 – Item 261 94
Y1958C
Contents
29
1. General features . . . . . . . . . . . . . . . . . . 301.1 Versions . . . . . . . . . . . . . . . . . . . . . . . . . . 301.2 Description . . . . . . . . . . . . . . . . . . . . . . . . 301.3 Applications . . . . . . . . . . . . . . . . . . . . . . . 301.4 Installation . . . . . . . . . . . . . . . . . . . . . . . . . 301.5 Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
2. Description of the front panel . . . . . . . . 312.1 Selection keys . . . . . . . . . . . . . . . . . . . . . . 312.2 Measurement selection . . . . . . . . . . . . . . . . 322.3 LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3. Operating mode . . . . . . . . . . . . . . . . . . . 343.1 Reset mode (red LED of RESET key) . . . . . . . . 343.2 Manual mode (red LED of MAN key) . . . . . . 353.3 Automatic mode (red LED of AUT key) . . . . . . 353.4 Off-load test mode (without load) . . . . . . . . . . 353.5 On-load test mode (under load) . . . . . . . . . . . 35
4. Applications . . . . . . . . . . . . . . . . . . . . . . 364.1 Utility-to-generator Application . . . . . . . . . . . 364.2 Utility-to-utility Application . . . . . . . . . . . . . . . 36
5. Circuit breakers Control . . . . . . . . . . . . 375.1 With feedback (default setup) . . . . . . . . . . . 375.2 Without feedback . . . . . . . . . . . . . . . . . . . 38
6. Voltage controls . . . . . . . . . . . . . . . . . . . 39
7. Programming . . . . . . . . . . . . . . . . . . . . . 417.1 Setting the parameters . . . . . . . . . . . . . . . . . 417.2 Table of menus . . . . . . . . . . . . . . . . . . . . . . 427.3 P0 menu - Nominal data . . . . . . . . . . . . . . . 427.4 P1 menu - General data . . . . . . . . . . . . . . . 437.5 P2 menu - Main line voltage control . . . . . . . 447.6 P3 menu - Secondary line voltage control . . . . 457.7 P4 menu - Programmable inputs . . . . . . . . . . . 467.8 P5 menu - Programmable outputs . . . . . . . . . 467.9 P6 menu - Serial communication . . . . . . . . . . 47
8. Diagnostic messages . . . . . . . . . . . . . . . 48
9. Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . 49
10. Connections . . . . . . . . . . . . . . . . . . . . . . 51
11. Technical features . . . . . . . . . . . . . . . . . 52
1. General features
30
1.1 Versions• 261 93 - Standard version • 261 94 - Evoluted version + interface RS-485
1.2 Description• Electronic Control Box - microprocessor• Two inputs of three-phase voltage measurement • Power supply DC 12-24-48 VDC• Power supply AC 220-240 VAC• 2 LED displays, 3 digits 7 segments • 20 status and measurement LED indicators
• 8-key membrane keypad• RS-232 serial interface for set-up, remote control
and supervision• RS-485 opto-isolated interface for MODBUS pro-
tocol (261 94)• 2 programmable digital inputs • 3 programmable relay outputs (1NO + 2 C/O)
1.3 Applications• Changeover between utility-to-utility, utility-to-
generator• Control of motorized circuit breakers, motorized
switches • Start/stop generator• Three-phase, two-phase or single-phase voltage
controls
• L-L voltage (or L-N voltage in case of monophaselines)
• Controls on minimum voltage, maximum voltage,phase loss, asymmetry, minimum frequency, max-imum frequency, with independent enabling anddelay
• Voltage thresholds with programmable hysteresis
1.4 Installation• Install the electronic control box according to the
wiring diagrams shown in the last pages of themanual
• Use the right wiring diagram for the application
• Set the parameters according to the requiredwiring diagram, paying special attention whenprogramming the inputs / outputs
1.5 Supply• 261 93 and 261 94 have a double power sup-
ply circuit, that means that they can operate withboth AC and DC supply or with only one of thetwo indifferently
• In presence of both power supplies, the energy istaken from the AC source
2. Description of the front panel
31
• The front panel of the electronic control box hastwo LED displays showing the voltages of the twopower sources with their correspondent keys – (A)for Main line and (B) for Secondary line – whichallows to select the measurements.
• The following keys: SET (E) - AUT (F) - MAN (G) -RESET (H) allow to select the operating mode,which is indicated by the corresponding LED.
• A mimic diagram is located at the center of thefront panel; it shows the status of the circuit break-ers for load connection.
• Two keys – (C) and (D) – can open and close thecircuit breakers (buttons are active only after press-ing the MAN key).
2.1 Selection keys
A B
E
F
G
H
C D
32
• When the key located under each display (A) and(B) is pressed several times, it will be possible to viewthe various measurements of the line sequentially.
• Line-to-line voltages, line-to-neutral voltages (in caseof single-phase lines) are available for each line.
• The combinations of the red LEDs indicate whichmeasurement is selected. The list of measurementsmay change depending on whether the electroniccontrol box is set up for the three-phase, two-phaseor single-phase control.
• After 1 minute without touching the key, the meas-urement returns to the default measurement, whichmay be the first voltage line-to-line or the first volt-age line-to-neutral, depending on how the voltagecontrol is set up.
• In case of alarms or messages, the display will beoccupied by the alarm code. By pressing the selection key, it is possible totemporarily hide the alarm and access the meas-urements.
2.2 Measurement selection
Example of a list of measurements on an electronic control box set up for a
three-phase control.
• The front panel has some LEDs which indicate the status of the circuit breakers controlled by the electroniccontrol box.
2.3 LEDs
ALARM LED(red)
POWER SUPPLY LED(green)
SET key LED(red)
AUT key LED(red)
MAN key LED(red)
RESET key LED(red)
Led L1/L2/L3Presence of voltage
on main line (red)
Main line / secondary line CONTROLS LED(two-colors)
Status LED, main line circuit breaker
Status LED, secondary line circuit breaker
Led L1/L2/L3Presence of voltage on
secondary line (red)
33
• The following table describes the meaning of the various LEDs.Some of them are bicolor and have a different meaning according to the color.
✱ If the auxiliary contacts have been connected, the LED will represent the status of the circuit breakers, otherwise it willremain off.
✱✱ If the contacts have been connected properly, the LED will represent the status of the circuit breakers, otherwise theLEDs will remain off.
LED On Off Flashing
ALARM No alarm enabled One or more alarms enabled (RED)
POWER SUPPLY Device powered (GREEN) No power
OPEN/CLOSE CONTROL
Close control (RED)Open control (GREEN) No control
OPEN/CLOSED �Circuit breaker closed
(RED)Circuit breaker open
(GREEN)
Auxiliary contactsnot connected
DISCONNECTED �� Circuit breaker not inserted in its base
Circuit breaker inserted or not-inserted-control
disabled
TRIPPED �� Circuit breaker trippedCircuit breaker not
tripped or AL contact not connected
PRESENCEL1/L2/L3 Voltage present No voltage
1HZ = Time of presence/absence in progress5HZ = Display measurements selection
3. Operating mode
34
• The four keys SET / AUT / MAN / RESET canbe used to select the required operating mode,which will be indicated when the correspondingred LED lights up.
• If the LED indicating the selected operating modeflashes, it means that the device is communicatingthrough the serial interface and that it could exe-cute remote commands, including the modechange as well.
A B
E
F
G
H
C D
• The electronic control box does not execute oper-ations but it just displays the status of the voltagesand the circuit breakers.
• The opening and closing control outputs of theswitches remain all open, hence allowing for themanual control from the front side of the motor con-trols. If the emergency input is activated, the unitwill in any case order the opening of the switches.
• The generator control output will set up for switch-ing off the group.
• The status alarms of the circuit breakers aredisabled.
• When an alarm occurs, it must be reset by press-ing the RESET key. If you are already in this oper-ating mode, press the RESET button again.
3.1 Reset mode (red RESET key LED)
• In automatic mode, the device independently exe-cutes both opening and closing operations of thecircuit breakers as well as the startup and shut-down of the generator, if any.
• When the main line (MAIN) goes beyond the lim-its, after the set delay times, the device disconnectsthe load from the main line and connects it to thesecondary line (SEC), thus controlling both the
startup of the generator, if any, and thechangeover times between the circuit breakers.
• When the main line falls within the limits, the deviceswitches again the load on it and determines thecooling cycle, if required, of the generator.
• The automatic cycles of operation vary accordingto the type of application (utility-to-utility, utility-to-generator).
35
P l e a s enote: Theexecution ofthis testinvolves trans-ferring theload, hence apower failureduring thechangeoverdue to theinterlockingtimes.
3.2 Manual mode (red MAN key LED)• The manual mode allows the operator to electrical-
ly open/close the circuit breakers with the specialkeys located at the front side of the device.
• In this mode, the voltages are constantly monitoredbut the device just displays their status.
• When one of the control keys is pressed for atleast 300 ms, the electronic control box changesthe status of the circuit breakers from open toclosed and vice-versa.
• If a command is given to close a circuit breakerwhile the other is already closed, the unit will ini-tially open the other circuit breaker, wait for the
interlocking time and then it will close the requiredcircuit breaker.
• In manual mode, all the status alarms of the circuitbreakers (disconnected and tripped) are disabled.The anomalous condition is signaled on the LEDbut it will not be stored or dealt with as an alarm.
• It is possible to manually control the startup andshutdown of the generator by holding down thekey (G) MAN for 5 consecutive seconds. As longas the manual mode is kept, the status of the gen-erator will remain the one required.
3.3 Automatic mode (red AUT key LED)
• By starting from the automatic mode and by press-ing the (F) key for 5 seconds, it will be possible totest the generator for 5 minutes.
• The generator is manually started in order to checkits operation but since the electronic control box isin automatic mode, the voltage controls willremain active.
• By doing so, it is possible to verify the correctoperation of the generator, thus maintaining
the coverage of the load. Under normal condi-tions, the load remains connected to the mainline, hence the generator operates with noload (off-load generator).
• The execution of the off-load test is determined byTES written steadily on the display.
• To end the execution of the test in advance, pressthe (F) key again for 5 seconds or start the resetmode.
• By starting from the automatic mode and by press-ing the (F) and (D) key simultaneously for 5 con-secutive seconds, it will be possible to carry out anoperational test (on-load test) which will totally sim-ulate a lack of the power line voltage lasting oneminute.
• Hence, the unit behaves exactly as if the line hasfallen out of the limits, thereby using all pro-
grammed times and parameters for thechangeover so as to verify their adequacy.
• The execution of the on-load test is determined byTES flashing on the display.
• To end the execution of the test in advance, repeatthe procedure with keys (F) and (D) for 5 secondsor start the reset mode.
3.5 On-load test mode
3.4 Off-load test mode
4. Applications
36
4.1 Utility-to-generator Application• In the Utility-to-generator application (U-G, default
setup) the load is normally connected to the mainline. If there is an anomaly on the line or in caseof a transfer signal set from the outside, a start sig-nal will be sent to the generator which supplies thesecondary line.
• When the voltage of the generator reaches theprogrammed limits, the electronic control box willorder the changeover on the secondary line.
• When the main line returns, the load is transferredagain and the generator is kept in operation withno load for a certain period of time so as to allowits cooling.
• The unit sends a start/stop command to the groupthrough a relay output and can receive digital sig-nals from the group indicating its status throughprogrammable inputs.
4.2 Utility-to-utility Application• In the utility-to-utility application (U-U), the load is
normally connected to the main line and thechangeover to the secondary line occurs if there is
an anomaly on the main line or in case there is atransfer signal set from the outside.
5. Circuit breakers control
37
• The circuit breakers control is carried out throughtwo separate relays, one for closing and one foropening.
• In reset mode, both control relays remain open,except for the emergency condition where theopening can be controlled.
• In case of an anomaly on the switch, hence caus-ing an alarm, the control outputs will both beopened till the resetting of the alarm.
• There are two separate modes for controlling thecircuit breakers. These can be selected by usingthe parameter P1.03
The auxiliarycontacts of the
circuit breakersare wired intheir imputs.
With the feedback is
necessary to usefor the opening
operation ofDPX
250-630-1600the shunth trip
relay or theundervoltage
relay.
Example of a changeover with feedback, assuming a utility-to-utility commutation.
The feedback input status is shown in blue. The status of the control outputsis shown in green. The changeover time
is shown in yellow.
0.5 s
15 s
0.5 s
LED VMAIN OK
LED VSEC OK
46
115
18
3
1s
1s
15 s
5.1 With feedback (default setup)• The status indicated by the two-color front LED is
the one detected by the auxiliary contacts.• The timeout alarms are enabled. They are gener-
ated if the circuit breakers do not reach therequired position within a programmable timeP1.04 or immediately if they change positionwhen no command has been sent.
• The control outputs are timed. When the circuitbreaker has executed the required operation, the
output still remains energized for a certain periodof time (+1 second during closing and +15 sec-onds during opening, in order to allow the springsof the motor operators to be completely charged)and then it is released.
• The normal status of the control outputs is open. • The interlocking times start when the first circuit
breaker is actually opened, detected by the input,and last for 0.5 steady seconds.
38
5.2 Without feedback
The auxiliarycontacts of the
circuit breakersare not wired in
their inputs,hence the electronic
control box isnot informed on
their actualstate.
Example of a changeover with no feedback. The actual status of the circuit
breakers is shown in blue. The status of the control outputs is shown in green.
The changeover time is shown in yellow.
6 sec 6 sec
LED VMAIN OK
LED VSEC. OK
INT. MAIN
INT. SEC.46
13
• The circuit breakers status LEDs remain off. • The timeout alarms are disabled.• The Opening/Closing control outputs remain
constantly in the required position for the circuitbreaker.
• The changeover times between the opening ofa switch and the closing of another start duringthe commutation of the outputs and are steadyat 6 sec.
6. Voltage controls
39
• Any condition required to determine whether asupply source is or is not suitable is determined bythe user through the P0 menu (system nominaldata) and the P2 and P3 menus (voltage control,main line and secondary line, respectively).
• It is possible to set up the system nominal data,such as nominal voltage and frequency, throughthe P0 menu, which will be used as a referencefor setting up the percentage thresholds of the fol-lowing menus.
• It is possible to set up a TV transformation ratio incase a lower voltage, relative to the actual voltageof the system, is applied to the voltage inputs ofthe unit. Here, again, the display and the setup ofthe thresholds will be executed in actual sizesreferred to the system.
• The electronic control box can be programmedto perform voltage controls on three-phase, two-phase or single-phase nets (via the P0.03parameter).
Control 261 93 261 94 Description
Minimum voltage • • One or more phases too low
Maximum voltage • One or more phases too high
Phase failure • • Threshold under which the device can operate faster compared to a normal reduction
Asymmetry (unbalance) • Phases included in the Maximum-Minimum interval, yet too different between each other
Minimum frequency • Frequency too low
Maximum frequency • Frequency too high
Sequence of phases • Reverse rotation of phases
The following describes the anomalies monitored by the voltage control.Columns 261 93 and 261 94 point out the presence of the function within their unit models.
40
• Each anomaly has an independent delay time.The anomaly must last consecutively longer thanthe time specified for invalidating the voltage pres-ence signal.
• All controls, except for the minimum voltage con-trol, can be excluded separately by setting therelated parameter to OFF.
• The minimum and maximum voltage limits arespecified by setting up two thresholds each, onewhich determines the point beyond which the volt-age is no longer considered acceptable (e.g.P2.01) and the other, closer to the nominal volt-age, which determines the point in which itbecomes compatible again (e.g. P2.02). The dis-
tance between these two thresholds determines thehysteresis. For instance, it may be considered thatwhen the nominal value is below 80%, the voltagemay no longer be useable and that in order to beconsidered useful, it must rise over 85%, therebydetermining a 5% hysteresis.The same concept applies to the maximumvoltage.
• As for the frequency thresholds, there is a fixed 1%hysteresis of the nominal frequency.
• The retrieval after a phase failure occurs when thevoltage rises above the minimum voltage retrievalthreshold.
Example of variation of the main line voltage within the minimum and maximum thresholds and relative hystereses, with indication of the
presence / absence delay times. Theexample considers the secondary linevoltage absent with its circuit breaker
open, hence the changeover times arenot shown. The INTERR. bar represents the required status
of the main line switch.
P2.04
P2.05
P2.02
V MAIN
P2.01
LED VOK
INTERR.P2.03 P2.15 P2.15P2.06 P2.05<
7. Programming
41
7.1 Setting the parameters
Key E- Goes to Setup - Exits to higher level
Key AIt moves
at same level
Key B- Enable modification- Confirms setup
Key FIncreases parameter value
Key GDecreases parameter value
Key HGoes to lower level
• Press the H and E keys together for 5 consecutiveseconds to start programming
• The flashing LED of the E key indicates that pro-gramming is in progress
• Main line display indicates the parameter selectedvia the code (for instance P0.01)
• Secondary line display indicates the set value ofthe selected parameter (for instance 400)
• Changing of parameters of the same group bypressing the key A
• Movement to next group with key E• Movement to previous group with key H
• Enable modification of the parameter with key B• Increase the value of the selected parameter with
key F• Decrease the value of the selected parameter with
key G• Confirm by pressing key B• While modifying a parameter, the secondary line
display flashes with the current value of the param-eter. In this situation it is not possible to move toanother parameter without first confirming
• Exit from Setup by pressing E and H simultaneously
42
7.2 Table of menus
7.3 P0 menu - Nominal data
Menu Description
P0 System nominal data
P1 General Data
P2 Main line voltage control
P3 Secondary line voltage control
P4 Programmable inputs
P5 Programmable outputs
P6 Communication port
Setup Description Range Default
P0.01 B Nominal voltage Ue 100 … 690 VAC 380 VAC
P0.02 B Transformation ratio TV 1.00 … 9.99 1.00
P0.03 B Type of Network3Ph = Three-phase2PH = Two-phase1Ph = Single-phase
3Ph
P0.04 B Nominal frequency Fe 50H = 50Hz60H = 60Hz 50Hz
P0.05 B Nominal battery voltage
OFF = No battery12 = 12 VDC24 = 24 VDC48 = 48 VDC
OFF
P0.01 - Nominal voltage used for calculating the thresholds P0.02 - Leave default setup in case a TV is not used P0.04 - Nominal frequency used as a reference for calculating the frequency thresholds P0.05 - Used for the alarms on the battery voltage
43
7.4 P1 menu - General dataSetup Description Range Default
P1.01 Type of application U-G = Utility-to-GeneratorU-U = Utility-to-Utility U-G
P1.02 Control of phase sequenceOFF - Disabled123 - Direct321 - Opposite
OFF
P1.03 Changeover control FEE - With feedback NOF - Without feedback FEE
P1.04 Circuit breakers Timeout OFF / 1…900s 5 s
P1.05 Enable control of withdrawn OFF (Control disabled) ON (Control enabled) OFF
P1.06 Maximum time load not powered (A07 alarm delay) OFF / 1…3600s OFF
P1.07 Startup delay time, generator 0 …. 900 s 1 s
P1.08 Cooling time, generator 1…3600s 120 s
P1.09 Minimum battery voltage threshold OFF / 70…100% 75%
P1.10 Maximum battery voltage threshold OFF / 110…140% 130%
P1.11 Battery threshold delay time 0…60 s 10 s
P1.01 - Determines the type of commutation (utility-to-utility/utility-to-generator) P1.04 - If, after sending an opening or closing command to a switch, it does not place itself correctly within this time,
the A03 or A04 alarms will be generatedP1.05 - Enable the control only if their contacts are wiredP1.06 - If both sources are simultaneously unavailable in automatic mode for a period of time longer than P1.06, the
A07 alarm will be generatedP1.07 - Time between the line failure used below and transmission of the startup signal to the generator on the secondary
line.It is a time which is independent from the circuit breaker opening time
P1.08 - Time whereby the generator is left in operation in order to cool down after being disconnected from the load
The highlightedparameters are
included only inversion 261 94
44
7.5 P2 menu - Main line voltage controlSetup Description Range Default
P2.01 Minimum voltage threshold - release 70…98% Ue 85% Ue
P2.02 Minimum voltage threshold - retrieval 75…100% Ue 90% Ue
P2.03 Minimum voltage threshold delay 0.1 …. 900 s 1.0 s
P2.04 Maximum voltage threshold - release 102…120% Ue / OFF 115% Ue
P2.05 Maximum voltage threshold - retrieval 100…115% Ue 110% Ue
P2.06 Maximum voltage threshold delay 0.1 …. 900 s 1.0 s
P2.07 Threshold of phase failure 60 … 85% Ue / OFF 70% Ue
P2.08 Phase failure threshold delay 0.1 … 30.0 s 0.1 s
P2.09 Voltage unbalance threshold 1 … 20% Ue / OFF 10 %
P2.10 Voltage unbalance threshold delay 0.1 … 900 s 5.0 s
P2.11 Threshold of minimum frequency OFF / 80… 100% Fe 95% Fe
P2.12 Minimum frequency threshold delay 0.1 … 900 s 5.0 s
P2.13 Threshold of maximum frequency 101 … 120% Fe / OFF 105% Fe
P2.14 Maximum frequency threshold delay 0.1 … 900 s 3.0 s
P2.15 Voltage return delay on main line within the limits (when circuit breaker secondary line open) 1 … 3600 s 10 s
P2.16 Voltage return delay on main line within the limits (when load on secondary line) 1 … 3600 s 60 s
The highlightedparameters are
included only inversion 261 94
P2.01 - P2.02 - P2.03 - The first two parameters determine the minimum voltage threshold and its hysteresis whenretrieved. P2.02 cannot be set to a value which is lower than P2.01. P2.03 determines the delay time for the activationof this protection. See chapter on Voltage controlsP2.04 - P2.05 - P2.06 - The first two parameters determine the maximum voltage threshold and its hysteresis whenretrieved. P2.05 cannot be set to a value which is higher than P2.04. Setting P2.04 to OFF will disable the maximumvoltage control. P2.06 determines the maximum voltage tripping delay. See chapter on Voltage controlsP2.07 - P2.08 - Voltage threshold under which there is an activation due to phase failure, usually faster than thereduction. The delay time for the phase failure is specified by P2.08P2.09 - P2.10 - P2.09 determines the maximum unbalance threshold between the phases, referred to the nominalvoltage; P2.10 determines the relative tripping delay. This control can be disabled by setting P2.09 to OFF P2.11 - P2.12 - Threshold (disabled) and minimum frequency tripping delay P2.13 - P2.14 - Threshold (disabled) and maximum frequency tripping delayP2.15 - Return delay time on main line within the limits, used when the source of the secondary line is not available.Normally shorter than P2.16: since the load is not powered, it is necessary to supply voltageP2.16 - Return delay time on main line within the limits, used when the load can be connected to the secondary line.Normally longer than P2.15: since the load is “covered”, it is possible to wait longer before considering the voltagestably retrieved
45
7.6 P3 menu - Secondary line voltage controlSetup Description Range Default
P3.01 Minimum voltage threshold - release 70…98 % Ue 85 % Ue
P3.02 Minimum voltage threshold - retrieval 75…100 % Ue 90 % Ue
P3.03 Minimum voltage threshold delay 0.1 …. 900 s 1.0 s
P3.04 Maximum voltage threshold - release 102…120 % Ue / OFF 115 % Ue
P3.05 Maximum voltage threshold - retrieval 100…115 % Ue 110 % Ue
P3.06 Maximum voltage threshold delay 0.1 …. 900 s 1.0 s
P3.07 Threshold of phase failure 60 … 85% Ue / OFF 70 % Ue
P3.08 Phase failure threshold delay 0.1 … 30.0 s 0.1 s
P3.09 Voltage unbalance threshold 1 … 20 % / OFF 10 %
P3.10 Voltage unbalance threshold delay 0.1 … 900 s 5.0 s
P3.11 Threshold of minimum frequency 99 … 80 % Fe / OFF 95 % Fe
P3.12 Minimum frequency threshold delay 0.1 … 900 s 5.0 s
P3.13 Threshold of maximum frequency 101 … 120% Fe / OFF 105 % Fe
P3.14 Maximum frequency threshold delay 0.1 … 900 s 3.0 s
P3.15 Voltage delay of secondary line within the limits 1 … 3600 s 20 s
The highlightedparameters are
included only inversion 261 94
Note: Forexplanationson the opera-tion ofparameters,see previouspage con-cerning themain linemenu.
7.7 P4 menu - Programmable inputsSetup Description Range Default
P4.01 Programmable input function 1See list ìP rogrammable
input functions”
ForForced changeover on secondary line
P4.02 Programmable input function 2In.rInhibition return on main line
Programmable input functions
Function Description Notes
OFF OFF Input not used
For Forced changeover on secondary line
When closed, it forces the changeover on the secondary line even if main line voltage is within the limits. Re-commutation occurs on the main line when the input is released or in case the secondary line voltage is not within the limits
IN.R Inhibition return on main line
In automatic mode, when closed, it blocks the automatic return on the main line after the main line voltage has returned within the limits. It is used for preventing the second power cutoff, due to the re-transferal, from occurring automatically in an unexpected moment
S.GE Generator voluntary Start/stop In automatic mode, when closed, it starts up the generator
EME Emergency NC contact which, if opened, opens both circuit breakers and generates an alarm
G.rE Generator ready If closed, it refers to a Generator in automatic mode and not in alarm mode. If opened, it generates an alarm code
Loc Keyboard total lock If closed, it locks all keyboard functions except for measurement views
L.PA Lock parameter access If closed, it locks the access to setups
46
7.8 P5 menu - Programmable outputsSetup Description Range Default
P5.01 Output functionProgrammable 1 See list “Programmable output functions” S.GE
Start generator
P5.02 Output functionProgrammable 2 See list “Programmable output functions” RDY
ATS Ready
P5.03 Output function Programmable 3 See list “Programmable output functions” ALA
Global alarm
47
Programmable output functions
Function Description Notes
OFF OFF Output not used
S.GE Consent to start up the generatorWhen closed, the generator must be inactive. Contact opens to start generator. If the unit is not powered, the generator starts
RDY Automatic transfer switch ready Indicates unit automatically and without alarms, ready to start operating
ALA Global alarm De-energizes in case of an alarm
MCMMinimum coilMain line Main line switch voltage minimum opening coil command
MCSMinimum coilSecondary line
Secondary line switch voltage minimum opening coil command
L.SH Non-priority load disconnection
Disconnection of the non-priority loads that are not powered by the secondary line branch. It is also controlled on the secondary line.Contact which is closed before the secondary line closing command and opened before the main line closing command
7.9 P6 menu - Serial communicationSetup Description Range Default
P6.01 Serial address RS-232 1…245 01
P6.02 Speed (baudrate) RS-232
240 = 2400 480 = 4800960 = 9600 19.2 = 19200 38.4 = 38400
960
P6.03 Protocol RS-232 Rtu = Modbus RTUASC = Modbus ASCII RTU
P6.04 Parity RS-232No = NoneEVE = EvenOdd = Odd
No
P6.05 Serial address RS-485 1…245 01
P6.06 Speed (baudrate) RS-485
240 = 2400 480 = 4800960 = 9600 19.2 = 19200 38.4 = 38400
960
P6.07 Protocol RS-485 Rtu = Modbus RTUASC = Modbus ASCII RTU
P6.08 Parity RS-485No = NoneEVE = Even Odd = Odd
No
P6.01…P6.04 - They determine the transmission format and the protocol used on communication port RS-232P6.05…P6.08 - They determine the transmission format and the protocol used on communication port RS-485,
available only on 261 94
The highlightedparameters are
included only inversion 261 94
8. Diagnostic messages
48
The following messages can be displayed, at different moments:
Code Description
- - -(Dashes) - The interlocking time is in progress.They are displayed from the side in which the load is being transferred
Sta (Start) - Indicates that the Start Generator command has been sent
Coo (Cooling) - Indicates that the generator is being left running for the cooling
Tes(Test) - When steady, it indicates that an off-load test - namely a power unit test with the voltage controls active - is currently in progress
Tes(Test) - When flashing, it indicates that an on-load test, namely an automatic net failure simulation, is currently in progress
Loc (Locked) - It indicates that the keyboard function one is trying to execute is locked
9. Alarms
49
• When the unit is running, it is possible to verify anumber of abnormal situations which are signaledin different ways.
• Some alarms (tripped, withdrawn) have a dedi-cated LED which begins to flash when thealarms go on.
• Other alarms are signaled through a code whichconsists of an A (alarm) and a number indicatingwhich alarm it is. This code will be flashing on oneof the displays. If the code refers to the main linebranch, the alarm will be displayed on the left.Conversely, if the code refers to the secondary linebranch or if it is a generic alarm (e.g. battery), itwill be displayed on the right.
• When an alarm goes on, the red LED “ALARM”flashes in sync with the dedicated LED or with thealarm code.
• The Global alarm relay output is de-energized dur-ing alarm conditions whereas it is energized undernormal conditions. If the unit does not operate dueto a failure or power supply problems, it will gen-erate an alarm condition on its contact.
• Some alarms are automatically reset when theconditions generating them fail to work.
• Other alarms, described in the chart in the RIT col-umn, are retentive, thus they are stored.
• Once the alarm has been stored, the abnormalconditions must be eliminated in order to be reset.Also, the operator must press the RESET key orsend a special message via the serial interface.
50
Alarm list
Code Led Description alarm Causes RIT RESET MAN AUT
A01 Battery voltage too low
This occurs if the P0.06 parameter is OFF and if the battery voltage measured remains lower than the threshold % set with P1.09 for the time set with P1.11
YES YES YES YES
A02 Battery voltage too high
This occurs if the P0.06 parameter is not OFF and if the battery voltage measured remains higher than the threshold % set with P1.10 for the time set with P1.11
YES YES YES YES
A03 Main line switch timeout
It is generated if the main line switch does not move to the position controlled by the unit within the time determined by P1.04 or if it comes out of the required position on its own. The alarm can be generated when closing and when opening. If there is no power on both lines, the alarm will not be generated
YES NO NO YES
A04 Secondary line switch timeout
It is generated if the secondary line switch does not move to the position controlled by the unit within the time determined by P1.04 or if it comes out of the required position on its own. The alarm can be generated when closing and when opening. If there is no power on both lines, the alarm will not be generated
YES NO NO YES
A05 Main line incorrect phase sequence
If enabled by parameter P1.02, it is generated when a phase sequence – different from what has been specified in P1.02 – is detected, after a delay of about 500 ms.In order for the sequence to be detected, all three phases must be > 50VAC
YES YES YES YES
A06Secondary line incorrect phase sequence
As the previous, referred to the secondary line voltage YES YES YES YES
A07 Timeout load not powered
The load was left with no voltage for a period of time longer than P1.06. The main line and the secondary line were not available (no power or switch not closed)
NO NO NO YES
A08 Generator not available
One of the programmable inputs is set to “Generator ready”, hence signaling that the generator is not available NO YES YES YES
A09 Emergency One of the programmable inputs is set to the emergency button and the corresponding input contact is open YES YES YES YES
A11Main line frequency outside limits
The frequency of the main line is not within the limits determined with P2.11 and P2.13 NO YES YES YES
A12Secondary line frequency outside limits
The frequency of the secondary line is not within the limits determined with P3.11 and P3.13 NO YES YES YES
A13 Main line voltage asymmetry
The difference between the higher and lower voltage between lines of the main line exceeds the limit determined with P2.09
NO YES YES YES
A14 Secondary line voltage asymmetry
The difference between the higher and lower voltage between lines of the secondary line exceeds the limit determined with P3.09
NO YES YES YES
•Main/secondary line withdrawn.Switch removed
The withdrawn input control is enabled by parameter P1.05 and the corresponding main line or secondary line input contact is open
YES VIS VIS YES
•
Main/secondary line tripped.Protection activation. Switch
The tripped input contact it is closed. This condition is ignored for 15 seconds which begins immediately after giving the command to open a switch so as to avoid false signalings when using a release coil
YES VIS VIS YES
The highlightedalarm are
included only inversion 261 94
10. Connections
51
Mors. Function
1 Main line circuit breaker opening
2 Common main line commands
3 Main line circuit breaker closing
4 Secondary line circuit breaker opening
5 Common secondary line commands
6 Secondary line circuit breaker closing
7 Programmable relay 1 (Default function = Start/Stop generator)
8 Common programmable relay 1
9
Programmable relay 2/NC (Default function = Unit ready)
10 Programmable relay 2/NO (Default function = Unit ready)
11
Common programmable relay 2
12
Programmable relay 3/NC (Default function = Global alarm)
13Programmable relay 3/NO (Default function = Global alarm - closed when ok)
14
Common programmable relay 3
15 AUX input of Main line circuit breaker
Mors. Function
16 AL input of Main line circuit breaker
17 DISCONNECTED input of Main line circuit breaker
18 AUX input of Secondary line circuit breaker
19 AL input of Secondary line circuit breaker
20 DISCONNECTED input of Secondary line circuit breaker
21 Programmable input 1 (Default = Forcing on secondary line)
22 Programmable input 2 (Default = Inhibition return on main line)
23 + VDC supply
24 – VDC supply
25 Common for inputs (from 15 to 22)
26 AC supply
27 AC supply
MAIN L1 L2 L3 N
Main line three-phase measurement input
SEC. L1 L2 L3 N
Secondary line three-phase measurement input
11. Technical features
52
Auxiliary power supplyDC power supply operating limits 9...70VDC (Us=12-24-48VDC)AC power supply operating limits 187…264VAC (Us=220…240VAC)Frequency 45…65HzMax. absorbed power 6VA (Us=240VAC)Max. dissipated power 4,8W (Us= 240VAC or Us=48VDC)Max. absorbed current 420mA to 12VDC; 200mA to 24VDC; 100mA to 48VDCMicro-breaking immunity time 50msVoltage inputsMax. rated voltage (Ue) 690VAC phase-phase (400VAC phase-neutral)UL usage data 600VAC phase-phase (340VAC phase-neutral)Measuring range 80…800VAC phase--phaseFrequency range 45…65HzType of measurement TRMS (true effective value)Measurement input impedance > 1,1 M Ω phase-phase and > 0,5 M Ω phase-neutralType of connection One, two or three phaseMeasurement error Class 0,5 ±0,25% f.s. ±1digitDigital inputsType of input NegativeInput current ≤10mAInput current “0” state ≤1,5 (typical 2,9V)Input current “1” state ≥5,3 (typical 4,3V)Input signal delay ≥50msecRelay outputs terminals 1-2 and 4-5Type of contact 1 NONominal range at 250VAC 12AContact nominal range 16A in AC1 250V - B300Maximum current on terminal 1.2 12ARelay outputs terminals 2-3 and 5-6Type of contact 1 NO
Contact nominal range 8A in AC1 250V - B30030VDC 1A Auxiliary service supply
Maximum current on terminal 2.2 12ARelay outputs terminals 7-8Type of contact 1 NO
Contact nominal range 8A in AC1 250V - B30030VDC 1A Auxiliary service supply
Relay outputs terminals 9-10-11 and 12-13-14Type of contact 1 change-over contact
Contact nominal range 8A in AC1 250V - B30030VDC 1A Auxiliary service supply
Communication interfaces
RS232 serial interface Programmable Baud-rate 1200…38400 bps Connection via RJ6/6 connector
RS485 serial interface(COM only)
Isolated with programmable Baud-rate 1200…38400 bpsConnection via removable terminals
InsulationRated insulation Voltage (Ui) 690VEnvironmental operating conditions Operating temperature -20…+60°CTemperature -30…+80°CRelative humidity <90% Maximum Pollution degree Degree 3Overvoltage category 3ConnectionsType of terminal RemovableConductor section (min. and max.) 0,2…2,5 mmq (24÷12 AWG)Tightening torque 0,5 Nm (4,5 LBin)HousingMaterial Thermoplastic LEXAN 3412RVersion Flush mountingDimensions L x H x D 144 x 144 x 94mmProtection degree IP41 on front, IP20 on backWeight 950gCertifications and compliance
IEC/EN 61010-1, IEC/EN 61000-6-2, CISPR 11/EN 55011, IEC/EN 61000-3-2, IEC/EN 61000-3-3, IEC/EN 60068-2-61, IEC/EN 60068-2-27, IEC/EN 60068-2-6, UL508 C22.2-N°14-95
ParamètreParameter
SchémaWiring diagram
53
Alimentation boitier et moteurs en 12-24-48VdcElectronic Control Box and motors supply in 12-24-48Vdc
Programmation des paramètres pour le schéma représenté sur la figure:Parameter setting for the wiring diagram in picture:
P0.05 24
ProgrammationSetting
~_
Pour DPX 125/160 ➞ 1000W filtréPour DPX 250/630/1600 et DMX ➞ 1000WFor DPX 125/160 ➞ 1000W filtredFor DPX 250/630/1600 et DMX ➞ 1000W
Moteurs Motors
230Vac / 24Vdc
ref. 04055
Principal Main
Secondaire Sec
23
+
24
-
25 26 27
ALIM. AUX.DC
DC AUXSUPPLY
ALIM. AUX.AC
AC AUXSUPPLY
0V~
220-
240V
~
Co
mm
un e
ntré
esC
om d
igita
l inp
uts
LG1B
ParamètreParameter
SchémaWiring diagram
Alimentation boitier en 230Vac et 12Vdc et moteurs en 230VacElectronic Control Box supply 230Vac and 12Vdc and motor supply in 230Vac
Programmation des paramètres pour le schéma représenté sur la figure:Parameter setting for the wiring diagram in picture:
P1.04 OFF
ProgrammationSetting
Moteurs Motors
ref. 04055
Principal Main
Secondaire Sec
23
+
24
-
25 26 27
ALIM. AUX.AC
AC AUXSUPPLY
0V~
220-
240V
~
Co
mm
un e
ntré
esC
om d
igita
l inp
uts
3A 3A
ALIM. AUX.DC
DC AUXSUPPLY
ref. 0421012Vcc 0,8A
54
LG3
ParamètreParameter
SchémaWiring diagram
Relevé de tensions monophaséesSingle-phase voltage inputs
Programmation des paramètres pour le schéma représenté sur la figure:Parameter setting for the wiring diagram in picture:
P0.03 1Ph
ProgrammationSetting
Principal Main
Secondaire Sec
N N100 - 690 Vac50/60 Hz
1A gG
1A gG
N L1 L2 L3 N L1 L2 L3
RELEVE DE TENSIONVOLTAGE INPUTS
100-690 Vac 50/60 Hz
PRINCIPALMAIN
SECONDAIRE SEC.
55
LG4
ParamètreParameter
SchémaWiring diagram
Relevé de tensions monophaséesSingle-phase voltage inputs
Programmation des paramètres pour le schéma représenté sur la figure:Parameter setting for the wiring diagram in picture:
P0.03 1Ph
ProgrammationSetting
Principal Main
Secondaire Sec
N N100 - 690 Vac50/60 Hz
1A
1A
N L1 L2 L3 N L1 L2 L3
RELEVE DE TENSIONVOLTAGE INPUTS
100-690 Vac 50/60 Hz
PRINCIPALMAIN
SECONDAIRE SEC.
56
LG5
57
ParamètreParameter
SchémaWiring diagram
Relevé de tensions biphaséesTwo-phase voltage inputs
Programmation des paramètres pour le schéma représenté sur la figure:Parameter setting for the wiring diagram in picture:
P0.03 2Ph
ProgrammationSetting
Principal Main
Secondaire Sec.
R S R S
1A gG
1A gG
N L1 L2 L3 N L1 L2 L3
RELEVE DE TENSIONVOLTAGE INPUTS
100-690 Vac 50/60 Hz
PRINCIPALMAIN
SECONDAIRE SEC.
100 - 690 Vac50/60 Hz
LG8
58
ParamètreParameter
SchémaWiring diagram
Relevé de tensions biphaséesTwo-phase voltage inputs
Programmation des paramètres pour le schéma représenté sur la figure:Parameter setting for the wiring diagram in picture:
P0.03 2Ph
ProgrammationSetting
100 - 690 Vac50/60 Hz
PrincipalMain
SecondaireSec.
SSR R
1A
1A
N L1 L2 L3
RELEVE DE TENSIONVOLTAGE INPUTS
N L1 L2 L3
100-690 Vac 50/60 Hz
PRINCIPALMAIN
SECONDAIRE SEC.
LG9
59
ParamètreParameter
SchémaWiring diagram
Relevé de tensions triphaséesThree-phase voltage inputs
Programmation des paramètres pour le schéma représenté sur la figure:Parameter setting for the wiring diagram in picture:
P0.03 3Ph
ProgrammationSetting
Principal Main
Secondaire Sec
N R S T N R S T
1A gG
1A gG
N L1 L2 L3 N L1 L2 L3
RELEVE DE TENSIONVOLTAGE INPUTS
100-690 Vac 50/60 Hz
PRINCIPALMAIN
SECONDAIRE SEC.
100 - 690 Vac50/60 Hz
LG6
60
ParamètreParameter
SchémaWiring diagram
Relevé de tensions triphaséesThree-phase voltage inputs
Programmation des paramètres pour le schéma représenté sur la figure:Parameter setting for the wiring diagram in picture:
P0.03 3Ph
ProgrammationSetting
Principal Main
Secondaire Sec
N R S T N R S T
1A
1A
N L1 L2 L3 N L1 L2 L3
RELEVE DE TENSIONVOLTAGE INPUTS
100-690 Vac 50/60 Hz
PRINCIPALMAIN
SECONDAIRE SEC.
100 - 690 Vac50/60 Hz
LG7
ParamètreParameter
SchémaWiring diagram
DPX 125/160 sans feedbackDPX 125/160 without feedback
Programmation des paramètres pour le schéma représenté sur la figure:Parameter setting for the wiring diagram in picture:
P1.03P1.04P1.05
NOFOFFOFF
ProgrammationSetting
34
53
45
12
12
Mo
teur
seco
urs
Sec
. mot
or
Mo
teur
norm
alM
ain
mot
or
Alim
enta
tio
nél
ectr
ique
des
mo
teur
sTe
nsio
nel
ectr
ic m
otor
s
Violet
Orange
BlueBlack
Red
Black
Red
Violet
Orange
Blue
1213
1415
1718
1920
2122
2324
2526
27N
L1L2
L3N
L1L2
L311
12
34
56
SE
CO
ND
AIR
ES
EC
.P
RIN
CIP
AL
MA
IN
0V~
220-240V~
Commun entréesCom digital inputs
-+
Aux. sec.
Trip sec.
Withdrawn sec.
Input prog. 1
Input prog. 2
Aux. main
Trip main
Withdrawn main
CA normal
SD normal
Contact débro normal
CA secours
SD secours
Contact débro secours
Entrée prog. 1
Entrée prog. 2
BO
ÎTIE
R D
’AU
TO
MA
TIS
ME
ELE
CTR
ON
IC C
ON
TRO
L B
OX
réf:
261
93/
94
RE
LAIS
PR
OG
RA
MM
AB
LE 3
PR
OG
. 3 R
ELA
Y10
0-69
0 Va
c
50/6
0Hz
RE
LEV
E D
E T
EN
SIO
NV
OLT
AG
E IN
PU
TSA
LIM
. AU
X.
AC
AC
AU
XS
UP
PLY
EN
TR
EE
S D
IGIT
ALE
SD
IGIT
AL
INP
UTS
RE
LAIS
SE
CO
UR
SS
EC
. RE
LAY
Ferm
etur
eC
losi
ngC
om
Com
Ouv
ertu
reO
pen
ing
RE
LAIS
NO
RM
AL
MA
IN R
ELA
Y
Ferm
etur
eC
losi
ngC
om
Com
Ouv
ertu
reO
pen
ing
R
ELA
IS P
RO
G.
1P
RO
G. 1
RE
LAY
RE
LAIS
PR
OG
RA
MM
AB
LE 2
PR
OG
. 2 R
ELA
Y
78
910
16
ALI
M. A
UX
.D
CD
C A
UX
SU
PP
LY
DPX 125: verrouillage mécanique non disponible
DPX 125: mechanical interlock not available
61
LG10
ParamètreParameter
SchémaWiring diagram
DPX 125/160 avec feedbackDPX 125/160 with feedback
Programmation des paramètres pour le schéma représenté sur la figure:Parameter setting for the wiring diagram in picture:
34
53
45
12
12
1213
1415
1718
1920
2122
2324
2526
27N
L1L2
L3N
L1L2
L311
12
34
56
Déb
ro s
eco
ndai
reW
ithd
raw
nse
c.
Déb
ro p
rinc
ipal
With
dra
wn
mai
n
3-White
1-Black
2-Red
3-White
1-Black
2-Red
SD
Sec
ond
aire
Trip
sec.
CA
Sec
ond
aire
Aux
. Sec
.C
A P
rinc
ipal
Aux
. mai
n
Mo
teur
seco
ndai
reS
ec. m
otor
Mo
teur
pri
ncip
alM
ain
mot
or
Alim
enta
tio
nél
ectr
ique
des
mo
teur
sTe
nsio
nel
ectr
ic m
otor
s
54-Red
51-Black
52-White
54-Red
51-Black
52-White
11-Black
14-White
12-Red
11-Black
14-White
12-Red
Violet
Orange
BlueBlack
Red
Black
Red
Violet
Orange
Blue
SE
CO
ND
AIR
ES
EC
.P
RIN
CIP
AL
MA
IN
0V~
220-240V~
Commun entréesCom digital inputs
-+
Aux. sec.
Trip sec.
Withdrawn sec.
Input prog. 1
Input prog. 2
Aux. main
Trip main
Withdrawn main
CA normal
SD normal
Contact débro normal
CA secours
SD secours
Contact débro secours
Entrée prog. 1
Entrée prog. 2
BO
ÎTIE
R D
’AU
TO
MA
TIS
ME
ELE
CTR
ON
IC C
ON
TRO
L B
OX
réf:
261
93/
94
RE
LAIS
PR
OG
RA
MM
AB
LE 3
PR
OG
. 3 R
ELA
Y10
0-69
0 Va
c
50/6
0Hz
RE
LEV
E D
E T
EN
SIO
NV
OLT
AG
E IN
PU
TSA
LIM
. AU
X.
AC
AC
AU
XS
UP
PLY
EN
TR
EE
S D
IGIT
ALE
SD
IGIT
AL
INP
UTS
RE
LAIS
SE
CO
UR
SS
EC
. RE
LAY
Ferm
etur
eC
losi
ngC
om
Com
Ouv
ertu
reO
pen
ing
RE
LAIS
NO
RM
AL
MA
IN R
ELA
Y
Ferm
etur
eC
losi
ngC
om
Com
Ouv
ertu
reO
pen
ing
R
ELA
IS P
RO
G.
1P
RO
G. 1
RE
LAY
RE
LAIS
PR
OG
RA
MM
AB
LE 2
PR
OG
. 2 R
ELA
Y
SD
Pri
ncip
alTr
ipm
ain
78
910
16
ALI
M. A
UX
.D
CD
C A
UX
SU
PP
LY
DPX 125: contact de condition “non enclenché” non disponible
DPX 125: not-inserted contact not available
DPX 125: verrouillage mécanique non disponible
DPX 125: mechanical interlock not available
62
P1.03P1.05
FEEON
ProgrammationSetting
LG11
ParamètreParameter
SchémaWiring diagram
DPX 125/160 avec EJP + feedbackDPX 125/160 with EJP and feedback
Programmation des paramètres pour le schéma représenté sur la figure:Parameter setting for the wiring diagram in picture:
EJP
34
53
45
12
12
1213
1415
1718
1920
2122
2324
2526
27N
L1L2
L3N
L1L2
L311
12
34
56
Déb
ro s
eco
ndai
reW
ithd
raw
nse
c.
Déb
ro p
rinc
ipal
With
dra
wn
mai
n
3-White
1-Black
2-Red
3-White
1-Black
2-Red
SD
Sec
ond
aire
Trip
sec.
CA
Sec
ond
aire
Feed
bac
kS
ec.
CA
Pri
ncip
alFe
edb
ack
mai
n
Mo
teur
seco
ndai
reS
ec. m
otor
Mo
teur
pri
ncip
alM
ain
mot
or
Alim
enta
tio
nél
ectr
ique
des
mo
teur
sTe
nsio
nel
ectr
ic m
otor
s
54-Red
51-Black
52-White
54-Red
51-Black
52-White
11-Black
14-White
12-Red
11-Black
14-White
12-Red
Violet
Orange
BlueBlack
Red
Black
Red
Violet
Orange
Blue
SE
CO
ND
AIR
ES
EC
.P
RIN
CIP
AL
MA
IN
0V~
220-240V~
Commun entréesCom digital inputs
-+
Aux. sec.
Trip sec.
Withdrawn sec.
Input prog. 1
Input prog. 2
Aux. main
Trip main
Withdrawn main
CA normal
SD normal
Contact débro normal
CA secours
SD secours
Contact débro secours
Entrée prog. 1
Entrée prog. 2
BO
ÎTIE
R D
’AU
TO
MA
TIS
ME
ELE
CTR
ON
IC C
ON
TRO
L B
OX
réf:
261
93/
94
RE
LAIS
PR
OG
RA
MM
AB
LE 3
PR
OG
. 3 R
ELA
Y10
0-69
0 Va
c
50/6
0Hz
RE
LEV
E D
E T
EN
SIO
NV
OLT
AG
E IN
PU
TSA
LIM
. AU
X.
AC
AC
AU
XS
UP
PLY
EN
TR
EE
S D
IGIT
ALE
SD
IGIT
AL
INP
UTS
RE
LAIS
SE
CO
UR
SS
EC
. RE
LAY
Ferm
etur
eC
losi
ngC
om
Com
Ouv
ertu
reO
pen
ing
RE
LAIS
NO
RM
AL
MA
IN R
ELA
Y
Ferm
etur
eC
losi
ngC
om
Com
Ouv
ertu
reO
pen
ing
R
ELA
IS P
RO
G.
1P
RO
G. 1
RE
LAY
RE
LAIS
PR
OG
RA
MM
AB
LE 2
PR
OG
. 2 R
ELA
Y
SD
Pri
ncip
alTr
ipm
ain
78
910
16
ALI
M. A
UX
.D
CD
C A
UX
SU
PP
LY
DPX 125: contact de condition “non enclenché” non disponible
DPX 125: not-inserted contact not available
DPX 125: verrouillage mécanique non disponible
DPX 125: mechanical interlock not available
63
P1.03P1.05
FEEON
ProgrammationSetting
LG12
ParamètreParameter
SchémaWiring diagram
DPX 250/630 sans feedbackDPX 250/630 without feedback
Programmation des paramètres pour le schéma représenté sur la figure:Parameter setting for the wiring diagram in picture:
13
5
24
6
1213
1415
1718
1920
2122
2324
2526
27N
L1L2
L3N
L1L2
L311
12
34
56
Alim
enta
tio
nél
ectr
ique
des
mo
teur
sTe
nsio
nel
ectr
ic m
otor
s
Bl
Rd
Wh
SE
CO
ND
AIR
ES
EC
.P
RIN
CIP
AL
MA
IN
0V~
220-240V~
Commun entréesCom digital inputs
-+
Aux. sec.
Trip sec.
Withdrawn sec.
Input prog. 1
Input prog. 2
Aux. main
Trip main
Withdrawn main
CA normal
SD normal
Contact débro normal
CA secours
SD secours
Contact débro secours
Entrée prog. 1
Entrée prog. 2
BO
ÎTIE
R D
’AU
TO
MA
TIS
ME
ELE
CTR
ON
IC C
ON
TRO
L B
OX
réf:
261
93/
94
RE
LAIS
PR
OG
RA
MM
AB
LE 3
PR
OG
. 3 R
ELA
Y10
0-69
0 Va
c
50/6
0Hz
RE
LEV
E D
E T
EN
SIO
NV
OLT
AG
E IN
PU
TSA
LIM
. AU
X.
AC
AC
AU
XS
UP
PLY
EN
TR
EE
S D
IGIT
ALE
SD
IGIT
AL
INP
UTS
RE
LAIS
SE
CO
UR
SS
EC
. RE
LAY
Ferm
etur
eC
losi
ngC
om
Com
Ouv
ertu
reO
pen
ing
RE
LAIS
NO
RM
AL
MA
IN R
ELA
Y
Ferm
etur
eC
losi
ngC
om
Com
Ouv
ertu
reO
pen
ing
R
ELA
IS P
RO
G.
1P
RO
G. 1
RE
LAY
RE
LAIS
PR
OG
RA
MM
AB
LE 2
PR
OG
. 2 R
ELA
Y
78
910
16
Bl
Rd
Wh
13
5
Mo
teur
pri
ncip
alM
ain
mot
or
24
6
Mo
teur
seco
ndai
reS
ec. m
otor
Bl
Rd
Wh
Bl
Rd
Wh
ALI
M. A
UX
.D
CD
C A
UX
SU
PP
LY
64
P1.03P1.04P1.05
NOFOFFOFF
ProgrammationSetting
LG13
ParamètreParameter
SchémaWiring diagram
DPX 250/630 avec EJP + feedback + declencheur EMDPX 250/630 with EJP + feedback + shunt trip
Programmation des paramètres pour le schéma représenté sur la figure:Parameter setting for the wiring diagram in picture:
1213
1415
1718
1920
2122
2324
2526
27N
L1L2
L3N
L1L2
L311
12
34
56
Alim
enta
tio
nél
ectr
ique
des
mo
teur
sTe
nsio
nel
ectr
ic m
otor
s
SE
CO
ND
AIR
ES
EC
.P
RIN
CIP
AL
MA
IN
0V~
220-240V~
Commun entréesCom digital inputs
-+
Aux. sec.
Trip sec.
Withdrawn sec.
Input prog. 1
Input prog. 2
Aux. main
Trip main
Withdrawn main
CA normal
SD normal
Contact débro normal
CA secours
SD secours
Contact débro secours
Entrée prog. 1
Entrée prog. 2
BO
ÎTIE
R D
’AU
TO
MA
TIS
ME
ELE
CTR
ON
IC C
ON
TRO
L B
OX
réf:
261
93/
94
RE
LAIS
PR
OG
RA
MM
AB
LE 3
PR
OG
. 3 R
ELA
Y10
0-69
0 Va
c
50/6
0Hz
RE
LEV
E D
E T
EN
SIO
NV
OLT
AG
E IN
PU
TSA
LIM
. AU
X.
AC
AC
AU
XS
UP
PLY
EN
TR
EE
S D
IGIT
ALE
SD
IGIT
AL
INP
UTS
RE
LAIS
SE
CO
UR
SS
EC
. RE
LAY
Ferm
etur
eC
losi
ngC
om
Com
Ouv
ertu
reO
pen
ing
RE
LAIS
NO
RM
AL
MA
IN R
ELA
Y
Ferm
etur
eC
losi
ngC
om
Com
Ouv
ertu
reO
pen
ing
R
ELA
IS P
RO
G.
1P
RO
G. 1
RE
LAY
RE
LAIS
PR
OG
RA
MM
AB
LE 2
PR
OG
. 2 R
ELA
Y
78
910
16
Mo
teur
pri
ncip
alM
ain
mot
orBl
Rd
Wh
Bl
Rd
Wh
Déb
ro s
eco
ndai
reW
ithd
raw
nse
c.
Déb
ro p
rinc
ipal
With
dra
wn
mai
n
3-White
1-Black
2-Red
3-White
1-Black
2-Red
SD
Sec
ond
aire
Trip
sec.
54-Red
51-Black
52-White
54-Red
51-Black
52-White
SD
Pri
ncip
alTr
ipm
ain
CA
Sec
ond
aire
Aux
. Sec
.C
A P
rinc
ipal
Aux
. mai
n
11-Black
14-White
12-Red
11-Black
14-White
Mo
teur
seco
ndai
reS
ec. m
otor
Bl
Rd
Wh
Bl
Rd
Wh
12-Red
C1 C2
C1 C2
Pri
ncip
al
Mai
nS
eco
ndai
re
Sec
EJP
ALI
M. A
UX
.D
CD
C A
UX
SU
PP
LY
13
5
24
6
13
5
24
6
66
P1.03P1.05
FEEON
ProgrammationSetting
LG15
ParamètreParameter
SchémaWiring diagram
DPX 250/630 avec feedback + declencheur EM + arrêt d’urgenceDPX 250/630 with feedback + shunt trip + emergency stop
Programmation des paramètres pour le schéma représenté sur la figure:Parameter setting for the wiring diagram in picture:
1213
1415
1718
1920
2122
2324
2526
27N
L1L2
L3N
L1L2
L311
12
34
56
Alim
enta
tio
nél
ectr
ique
des
mo
teur
sTe
nsio
nel
ectr
ic m
otor
s
SE
CO
ND
AIR
ES
EC
.P
RIN
CIP
AL
MA
IN
0V~
220-240V~
Commun entréesCom digital inputs
-+
Aux. sec.
Trip sec.
Withdrawn sec.
Input prog. 1
Input prog. 2
Aux. main
Trip main
Withdrawn main
CA normal
SD normal
Contact débro normal
CA secours
SD secours
Contact débro secours
Entrée prog. 1
Entrée prog. 2
BO
ÎTIE
R D
’AU
TO
MA
TIS
ME
ELE
CTR
ON
IC C
ON
TRO
L B
OX
réf:
261
93/
94
RE
LAIS
PR
OG
RA
MM
AB
LE 3
PR
OG
. 3 R
ELA
Y10
0-69
0 Va
c
50/6
0Hz
RE
LEV
E D
E T
EN
SIO
NV
OLT
AG
E IN
PU
TSA
LIM
. AU
X.
AC
AC
AU
XS
UP
PLY
EN
TR
EE
S D
IGIT
ALE
SD
IGIT
AL
INP
UTS
RE
LAIS
SE
CO
UR
SS
EC
. RE
LAY
Ferm
etur
eC
losi
ngC
om
Com
Ouv
ertu
reO
pen
ing
RE
LAIS
NO
RM
AL
MA
IN R
ELA
Y
Ferm
etur
eC
losi
ngC
om
Com
Ouv
ertu
reO
pen
ing
R
ELA
IS P
RO
G.
1P
RO
G. 1
RE
LAY
RE
LAIS
PR
OG
RA
MM
AB
LE 2
PR
OG
. 2 R
ELA
Y
78
910
16
13
5
Mo
teur
pri
ncip
alM
ain
mot
orBl
Rd
Wh
Bl
Rd
Wh
24
6
Déb
ro s
eco
ndai
reW
ithd
raw
nse
c.
Déb
ro p
rinc
ipal
With
dra
wn
mai
n
3-White
1-Black
2-Red
3-White
1-Black
2-Red
SD
Sec
ond
aire
Trip
sec.
54-Red
51-Black
52-White
54-Red
51-Black
52-White
SD
Pri
ncip
alTr
ipm
ain
CA
Sec
ond
aire
Aux
. Sec
.C
A P
rinc
ipal
Aux
. mai
n
11-Black
14-White
12-Red
11-Black
14-White
Mo
teur
seco
ndai
reS
ec. m
otor
Bl
Rd
Wh
Bl
Rd
Wh
13
5
46
12-Red
C1 C2
C1 C2
Pri
ncip
al
Mai
nS
eco
ndai
re
Sec
Arr
êtd
’urg
ence
Em
erge
ncy
stop
2
ALI
M. A
UX
.D
CD
C A
UX
SU
PP
LY
67
P1.03P1.05
FEEON
ProgrammationSetting
LG16
ParamètreParameter
SchémaWiring diagram
DPX 1600 sans feedbackDPX 1600 without feedback
Programmation des paramètres pour le schéma représenté sur la figure:Parameter setting for the wiring diagram in picture:
Alim
enta
tio
nél
ectr
ique
des
mo
teur
sTe
nsio
nel
ectr
ic m
otor
s
1213
1415
1718
1920
2122
2324
2526
27N
L1L2
L3N
L1L2
L311
12
34
56
SE
CO
ND
AIR
ES
EC
.P
RIN
CIP
AL
MA
IN
0V~
220-240V~
Commun entréesCom digital inputs
-+
Aux. sec.
Trip sec.
Withdrawn sec.
Input prog. 1
Input prog. 2
Aux. main
Trip main
Withdrawn main
CA normal
SD normal
Contact débro normal
CA secours
SD secours
Contact débro secours
Entrée prog. 1
Entrée prog. 2
BO
ÎTIE
R D
’AU
TO
MA
TIS
ME
ELE
CTR
ON
IC C
ON
TRO
L B
OX
réf:
261
93/
94
RE
LAIS
PR
OG
RA
MM
AB
LE 3
PR
OG
. 3 R
ELA
Y10
0-69
0 Va
c
50/6
0Hz
RE
LEV
E D
E T
EN
SIO
NV
OLT
AG
E IN
PU
TSA
LIM
. AU
X.
AC
AC
AU
XS
UP
PLY
EN
TR
EE
S D
IGIT
ALE
SD
IGIT
AL
INP
UTS
RE
LAIS
SE
CO
UR
SS
EC
. RE
LAY
Ferm
etur
eC
losi
ngC
om
Com
Ouv
ertu
reO
pen
ing
RE
LAIS
NO
RM
AL
MA
IN R
ELA
Y
Ferm
etur
eC
losi
ngC
om
Com
Ouv
ertu
reO
pen
ing
R
ELA
IS P
RO
G.
1P
RO
G. 1
RE
LAY
RE
LAIS
PR
OG
RA
MM
AB
LE 2
PR
OG
. 2 R
ELA
Y
78
910
16
46
8
Mo
teur
pri
ncip
alM
ain
mot
or
35
7
Mo
teur
seco
ndai
reS
ec. m
otor
46
8
57
1 221
3
ALI
M. A
UX
.D
CD
C A
UX
SU
PP
LY
68
P1.03P1.04P1.05
NOFOFFOFF
ProgrammationSetting
LG17
ParamètreParameter
SchémaWiring diagram
DPX 1600 avec feedback + declencheur EM + arrêt d’urgenceDPX 1600 with feedback + shunt trip + emergency stop
Programmation des paramètres pour le schéma représenté sur la figure:Parameter setting for the wiring diagram in picture:
1213
1415
1718
1920
2122
2324
2526
27N
L1L2
L3N
L1L2
L311
12
34
56
Alim
enta
tio
nél
ectr
ique
des
mo
teur
sTe
nsio
nel
ectr
ic m
otor
s
SE
CO
ND
AIR
ES
EC
.P
RIN
CIP
AL
MA
IN
0V~
220-240V~
Commun entréesCom digital inputs
-+
Aux. sec.
Trip sec.
Withdrawn sec.
Input prog. 1
Input prog. 2
Aux. main
Trip main
Withdrawn main
CA normal
SD normal
Contact débro normal
CA secours
SD secours
Contact débro secours
Entrée prog. 1
Entrée prog. 2
BO
ÎTIE
R D
’AU
TO
MA
TIS
ME
ELE
CTR
ON
IC C
ON
TRO
L B
OX
réf:
261
93/
94
RE
LAIS
PR
OG
RA
MM
AB
LE 3
PR
OG
. 3 R
ELA
Y10
0-69
0 Va
c
50/6
0Hz
RE
LEV
E D
E T
EN
SIO
NV
OLT
AG
E IN
PU
TSA
LIM
. AU
X.
AC
AC
AU
XS
UP
PLY
EN
TR
EE
S D
IGIT
ALE
SD
IGIT
AL
INP
UTS
RE
LAIS
SE
CO
UR
SS
EC
. RE
LAY
Ferm
etur
eC
losi
ngC
om
Com
Ouv
ertu
reO
pen
ing
RE
LAIS
NO
RM
AL
MA
IN R
ELA
Y
Ferm
etur
eC
losi
ngC
om
Com
Ouv
ertu
reO
pen
ing
R
ELA
IS P
RO
G.
1P
RO
G. 1
RE
LAY
RE
LAIS
PR
OG
RA
MM
AB
LE 2
PR
OG
. 2 R
ELA
Y
78
910
16
42
68
Mo
teur
pri
ncip
alM
ain
mot
or
31
57
Déb
ro s
eco
urs
With
dra
wn
sec.
Déb
ro n
orm
alW
ithd
raw
nm
ain
3-White
1-Black
2-Red
3-White
1-Black
2-Red
SD
Sec
our
sTr
ipse
c.
54-Red
51-Black
52-White
54-Red
51-Black
52-White
SD
No
rmal
Trip
mai
n
CA
Sec
our
sFe
edb
ack
Sec
.
CA
No
rmal
Feed
bac
km
ain
11-Black
14-White
12-Red
11-Black
14-White
Mo
teur
seco
ndai
reS
ec. m
otor
84
26
31
57
12-Red
C1 C2
C1 C2
Pri
ncip
al
Mai
nS
eco
ndai
re
Sec
Arr
êtd
’urg
ence
Em
erge
ncy
stop
6
ALI
M. A
UX
.D
CD
C A
UX
SU
PP
LY
70
P1.03P1.05
FEEON
ProgrammationSetting
LG19
ParamètreParameter
SchémaWiring diagram
DPX 1600 avec EJP + feedbackDPX 1600 with EJP + feedback
Programmation des paramètres pour le schéma représenté sur la figure:Parameter setting for the wiring diagram in picture:
1213
1415
1718
1920
2122
2324
2526
27N
L1L2
L3N
L1L2
L311
12
34
56
Alim
enta
tio
nél
ectr
ique
des
mo
teur
sTe
nsio
nel
ectr
ic m
otor
s
SE
CO
ND
AIR
ES
EC
.P
RIN
CIP
AL
MA
IN
0V~
220-240V~
Commun entréesCom digital inputs
-+
Aux. sec.
Trip sec.
Withdrawn sec.
Input prog. 1
Input prog. 2
Aux. main
Trip main
Withdrawn main
CA normal
SD normal
Contact débro normal
CA secours
SD secours
Contact débro secours
Entrée prog. 1
Entrée prog. 2
BO
ÎTIE
R D
’AU
TO
MA
TIS
ME
ELE
CTR
ON
IC C
ON
TRO
L B
OX
réf:
261
93/
94
RE
LAIS
PR
OG
RA
MM
AB
LE 3
PR
OG
. 3 R
ELA
Y10
0-69
0 Va
c
50/6
0Hz
RE
LEV
E D
E T
EN
SIO
NV
OLT
AG
E IN
PU
TSA
LIM
. AU
X.
AC
AC
AU
XS
UP
PLY
EN
TR
EE
S D
IGIT
ALE
SD
IGIT
AL
INP
UTS
RE
LAIS
SE
CO
UR
SS
EC
. RE
LAY
Ferm
etur
eC
losi
ngC
om
Com
Ouv
ertu
reO
pen
ing
RE
LAIS
NO
RM
AL
MA
IN R
ELA
Y
Ferm
etur
eC
losi
ngC
om
Com
Ouv
ertu
reO
pen
ing
R
ELA
IS P
RO
G.
1P
RO
G. 1
RE
LAY
RE
LAIS
PR
OG
RA
MM
AB
LE 2
PR
OG
. 2 R
ELA
Y
78
910
16
42
68
Mo
teur
pri
ncip
alM
ain
mot
or
31
57
Déb
ro s
eco
ndai
reW
ithd
raw
nse
c.
Déb
ro p
rinc
ipal
With
dra
wn
mai
n
3-White
1-Black
2-Red
3-White
1-Black
2-Red
SD
Sec
ond
aire
Trip
sec.
54-Red
51-Black
52-White
54-Red
51-Black
52-White
SD
Pri
ncip
alTr
ipm
ain
CA
Sec
ond
aire
Aux
. Sec
.C
A P
rinc
ipal
Aux
. mai
n
11-Black
14-White
12-Red
11-Black
14-White
Mo
teur
seco
ndai
reS
ec. m
otor
84
26
31
57
12-Red
C1 C2
C1 C2
Pri
ncip
al
Mai
nS
eco
ndai
re
Sec
EJP
ALI
M. A
UX
.D
CD
C A
UX
SU
PP
LY
71
P1.03P1.05
FEEON
ProgrammationSetting
LG20
ParamètreParameter
SchémaWiring diagram
DPX 125 �� 1600 avec declencheur MT + arrêt d’urgenceDPX 125 �� 1600 with UVR and emergency stop
Programmation des paramètres pour le schéma représenté sur la figure:Parameter setting for the wiring diagram in picture:
U < U <
12 13 1411
Tension électrique desbobinesTension
electric releases
RELAISPROGRAMMABLE 3
PROG. 3 RELAY
RELAISPROGRAMMABLE 2
PROG. 2 RELAY
9 10
Principal Main
Secondaire Sec
Arrêtd’urgenceEmergency
stop
P5.02P5.03P1.03
MCMMCSFEE
ProgrammationSetting
72
LG24B
L’alimentation des commandes motorisées doit être secours
Safety supply of the motor operators is required
Programmation des paramètresSetting of parameters
Setup ValeurValue Setup Valeur
ValueP0.01 P3.01P0.02 P3.02P0.03 P3.03P0.04 P3.04P0.05 P3.05P1.01 P3.06P1.02 P3.07P1.03 P3.08P1.04 P3.09P1.05 P3.10P1.06 P3.11P1.07 P3.12P1.08 P3.13P1.09 P3.14P1.10 P3.15P1.11 P4.01P2.01 P4.02P2.02 P5.01P2.03 P5.02P2.04 P5.03P2.05 P6.01P2.06 P6.02P2.07 P6.03P2.08 P6.04P2.09 P6.05P2.10 P6.06P2.11 P6.07P2.12 P6.08P2.13P2.14P2.15P2.16
Schémas de branchement utilisés:Wiring diagram used:
...............................................................................................................................................................................................................
...............................................................................................................................................................................................................
...............................................................................................................................................................................................................
...............................................................................................................................................................................................................
A compléter et à retourner au Service clients en cas de besoinTo be filled in and sent to Customer Service, if needed
73